Anhydrous Ammonia
Chapter 296-826, WAC
|
Effective
Date: 09/01/06 |
Contents
Index
Download
| WAC
296-826-300
Design, construction and installation
|
For
printing |

YOUR RESPONSIBILITY:
To make sure containers and tanks used for
storing, distributing, or transporting anhydrous ammonia meet
design, construction and installation requirements

CONTAINER LOCATION AND MARKING
WAC
296-826-30005
General specifications
You must
- Locate containers either:
- -In buildings or parts of the building
provided for ammonia storage
or
- -Outside, away from densely populated
areas.
- Locate containers according to Table 1, Minimum
Distances for Container Location.
Table
1
Minimum Distances for Container Location |
Minimum
Distances (feet) from Container to: |
Nominal
Capacity of Container |
Line
of Adjoining Property Which may be Built upon, Highways
& Mainline of Railroad |
Place
of Public Assembly |
Institution
Occupancy |
Over
500 to 2,000 |
25 |
150 |
250 |
Over
2,000 to 30,000
|
50
|
300
|
500
|
Over 30,000
to 100,000
|
50
|
450
|
750
|
Over 100,000
|
50
|
600
|
1,000
|
You must
- Make sure containers are located to meet all
of the following:
- -Away from readily ignitable materials
such as weeds, long dry grass, and waste.
- -So there's no adverse impact on employee
health through unnecessary exposure.
- -At least 50 feet away from dug wells
and other sources of potable water.
- -If the container is a part of a water
treatment installation, then this requirement doesn't apply.
- Maintain legibility of all container and valve
markings.
WAC
296-826-30010
Specifications for portable DOT containers
IMPORTANT:
This section applies to systems that
use cylinders, portable tanks (DOT-51), or "ton containers" (DOT-106A,
DOT-110A), constructed according to DOT specifications.
You must
- Locate containers aboveground, never buried
below the ground.
- Put containers on firm ground or secure them.
- Guard against settling on the outlet piping
by using a flexible connection or a special fitting.
- Protect containers from all of the following:
- -Ignitable debris
- -External damage including corrosion
- -Heat sources, like radiant flames and
steam pipes
- -Moving vehicles.
- Prohibit the use of heat to raise the container
pressure.
WAC
296-826-30015
Nonrefrigerated stationary containers
You must
- Construct and test containers according to
the Unfired Pressure Vessel Code.
- Make sure the minimum design pressure of the
container is 250 psig
- Make sure all containers with a capacity exceeding
250 gallons are constructed to meet one or more of the following:
- -Stress relieved after fabrication according
to the Unfired Pressure Vessel Code
- -Have stress relieved cold-formed heads
- -Hot-formed heads
WAC
296-826-30020
Refrigerated storage
You must
- Make sure the minimum design temperature is
the same as the refrigerated temperature of the tank.
- Construct and test containers, with a design
pressure exceeding 15 psig, according to the Unfired Pressure
Vessel Code.
- Select construction materials from those listed
from API Standard 620, 4th Edition 2002, Recommended Rules for
Design and Construction of Large, Welded Low Pressure Storage
Tanks.
- Construct tanks with a design pressure with
15 psig or less according to API Standard 620, 4th Edition,
2002.
- Use ASME Code as a guide in the selection
of austenitic steels or nonferrous materials, if used at the
design temperature.
WAC
296-826-30025
Systems mounted on trucks, semi-trailers,
and trailers
You must
- Construct and test containers, when transported
within the state of Washington, according to both of the following:
- -A minimum design pressure of 250 psig
- -The Unfired Pressure Vessel Code.
- Construct containers used for interstate transport
according to DOT regulations.
- Make sure the shell or head thickness of any
container is at least 3/16 of an inch.
- Make sure electrical lighting circuits meet
all of the following:
- -Have suitable over-current protection,
such as fuses or automatic circuit breakers.
- -Are suitably secured, insulated, and
protected against physical damage.
- -Have wiring with sufficient carrying
capacity and mechanical strength.
- Use only electric light.
WAC
296-826-30030
Systems mounted on farm trucks or trailers
for transporting ammonia
You must
- Construct and test containers, with a design
pressure exceeding 15 psig, according to the Unfired Pressure
Vessel Code.
WAC
296-826-30035
Systems mounted on farm equipment for ammonia
application
You must
- Construct and test containers according to
the Unfired Pressure Vessel Code.
WAC
296-826-30040
DOT containers
You must
- Make sure containers meet DOT specifications.
NONREFRIGERATED CONTAINERS
WAC
296-826-30045
Installation
You must
- Provide a minimum distance of 5 feet between
aboveground and underground containers that have more than a
1,200 gallon capacity each.
- Protect containers from floating away, in
areas with a potential for high flood waters, by providing either:
- -Secure anchorage
or
- -Adequate pier height.
- Follow Tabel 2 for
aboveground, nonrefrigerated containers.
Table
2
Aboveground Nonrefrigerated Container
Requirements |
If
you have |
Then |
Aboveground
containers
|
- Provide one of the following.
- -Substantial reinforced concrete
footings and foundations
or
- -Structural steel supports mounted
on reinforced concrete foundations.
- Make sure the reinforced concrete
foundation meets all of the following:
- -Extends below the established
frost line
- -Is of sufficient width and thickness
to support the total weight of the containers and
contents
- -Has the lowest point of the tank
at least 18 inches above the ground.
- Make sure the footings meet all of
the following:
- -Extend below the established frost
line
- -Are of sufficient width and thickness
to support the total weight of the containers and
contents.
|
Floating
type foundations on containers installed aboveground |
Make
sure they are designed to adequately support the tank,
contents, and pumping equipment. |
A
horizontal, aboveground container
|
- Mount the container on a foundation
that permits expansion and contraction.
- Prevent the weight of excessive loads
from resting on the supporting portion of the shell.
- Provide saddle bearing that extends
over at least 1/3 the circumference of the shell.
- Prevent corrosion on the portions
of the container in contact with the foundations or
saddles.
|
You must
- Follow Table 3 for
underground, non-refrigerated containers.
Table
3
Underground Nonrefrigerated Container
Requirements |
If you have |
Then |
Underground
containers
|
|
WAC
296-826-30050
Reinstallation
You must
- Prohibit the reinstallation of nonrefrigerated
, previously installed underground, containers unless they meet
both of the following:
- -Pass a hydrostatic pressure retest using
the original pressure specified by the Unfired Pressure
Vessel Code under which the tank was constructed
and
- -Show no evidence of serious corrosion.
- Maintain a corrosion resistant coating on
reinstalled underground containers.
REFRIGERATED STORAGE TANKS
WAC
296-826-30055
Installation
You must
- Support tanks on noncombustible foundations
designed for the type of tank.
- Provide protection against flotation or other
water damage, where high floodwater might occur.
- Prevent the effects of freezing and consequent
frost heaving, in tanks used for product storage at less than
32°F, by providing either support or heat supply.
- Prevent accidental discharge of liquids from
spreading into uncontrolled areas by providing, to the area
surrounding a refrigerated tank or group of tanks, one of the
following:
- -A drainage system provided with at least
a one percent slope that terminates in an impounding basin
with a capacity as large as the largest tank served
or
- -A diked enclosure with a capacity as large
as the largest tank served.
- Meet, when using a diked enclosure or an impounding
basin in a drainage system, the following requirements:
- -The wall is made of earth, steel, or concrete.
If made of earth, meet both of the following:
- The top is flat and at least 2 feet wide
and
- There's a stable slope consistent with the
angle of the earth used
- -Design the wall to be both:
- Liquid tight
and
- Able to withstand the hydrostatic pressure
and the temperature.
- Provide for drainage of rain water, that doesn't
permit the release of ammonia, from diked or impounding areas.
| 
|
Note:
- It's recommended that the ground
in an impounding basin or within a diked enclosure be
graded so that small spills or the early part of a large
spill will accumulate at one side or corner contacting
both:
- -A relatively small area of ground
and
- -Exposing a relatively small surface
area for heat gain.
|
- Shallow channels in the ground surface or
low curbs of earth can help guide the liquid to these low areas
without contacting a large ground area.
WAC
296-826-30060
Reinstallation
You must
- Make sure moved and reinstalled containers
of a size to require field fabrication are reconstructed and
reinspected to:
- -Meet the original Unfired Pressure Vessel
Code under which the tank was manufactured and do the following
according to the same code:
- A pressure retest
- Any necessary rerating.
|