Anhydrous AmmoniaChapter 296-826, WAC |
Effective Date: 09/01/06 |
Design, construction and installation |
![]()
YOUR RESPONSIBILITY:
To make sure containers and tanks used for storing, distributing, or transporting anhydrous ammonia meet design, construction and installation requirements
| CONTAINER LOCATION AND MARKING | |
General specifications |
|
| Specifications for portable DOT containers |
|
|
Nonrefrigerated stationary containers |
WAC 296-826-30015 |
| Refrigerated storage | WAC 296-826-30020 |
| Systems mounted on trucks, semi-trailers, and trailers | WAC 296-826-30025 |
| Systems mounted on farm trucks or trailers for transporting ammonia | WAC 296-826-30030 |
| Systems mounted on farm equipment for ammonia application | WAC 296-826-30035 |
| DOT containers | WAC 296-826-30040 |
| NONREFRIGERATED CONTAINERS | |
Installation |
WAC 296-826-30045 |
| Reinstallation | WAC 296-826-30050 |
| REFRIGERATED TANKS | |
Installation |
WAC 296-826-30055 |
| Reinstallation | WAC 296-826-30060 |
![]()
CONTAINER LOCATION AND MARKING
General specifications
You must
- Locate containers either:
- -In buildings or parts of the building
provided for ammonia storage
or - -Outside, away from densely populated areas.
- -In buildings or parts of the building
provided for ammonia storage
- Locate containers according to Table 1, Minimum Distances for Container Location.
Table
1 Minimum Distances for Container Location |
|||
Minimum Distances (feet) from Container to: |
|||
Nominal Capacity of Container |
Line of Adjoining Property Which may be Built upon, Highways & Mainline of Railroad |
Place of Public Assembly |
Institution Occupancy |
Over 500 to 2,000 |
25 |
150 |
250 |
Over 2,000 to 30,000
|
50 |
300 |
500
|
Over 30,000 to 100,000
|
50 |
450 |
750
|
Over 100,000
|
50 |
600 |
1,000
|
You must
- Make sure containers are located to meet all
of the following:
- -Away from readily ignitable materials such as weeds, long dry grass, and waste.
- -So there's no adverse impact on employee health through unnecessary exposure.
- -At least 50 feet away from dug wells and other sources of potable water.
- -If the container is a part of a water treatment installation, then this requirement doesn't apply.
- Maintain legibility of all container and valve markings.
Specifications for portable DOT containers
IMPORTANT:
This section applies to systems that use cylinders, portable tanks (DOT-51), or "ton containers" (DOT-106A, DOT-110A), constructed according to DOT specifications.
You must
- Locate containers aboveground, never buried below the ground.
- Put containers on firm ground or secure them.
- Guard against settling on the outlet piping by using a flexible connection or a special fitting.
- Protect containers from all of the following:
- -Ignitable debris
- -External damage including corrosion
- -Heat sources, like radiant flames and steam pipes
- -Moving vehicles.
- Prohibit the use of heat to raise the container pressure.
Nonrefrigerated stationary containers
You must
- Construct and test containers according to the Unfired Pressure Vessel Code.
- Make sure the minimum design pressure of the container is 250 psig
- Make sure all containers with a capacity exceeding
250 gallons are constructed to meet one or more of the following:
- -Stress relieved after fabrication according to the Unfired Pressure Vessel Code
- -Have stress relieved cold-formed heads
- -Hot-formed heads
Refrigerated storage
You must
- Make sure the minimum design temperature is the same as the refrigerated temperature of the tank.
- Construct and test containers, with a design pressure exceeding 15 psig, according to the Unfired Pressure Vessel Code.
- Select construction materials from those listed from API Standard 620, 4th Edition 2002, Recommended Rules for Design and Construction of Large, Welded Low Pressure Storage Tanks.
- Construct tanks with a design pressure with 15 psig or less according to API Standard 620, 4th Edition, 2002.
- Use ASME Code as a guide in the selection of austenitic steels or nonferrous materials, if used at the design temperature.
Systems mounted on trucks, semi-trailers, and trailers
You must
- Construct and test containers, when transported
within the state of Washington, according to both of the following:
- -A minimum design pressure of 250 psig
- -The Unfired Pressure Vessel Code.
- Construct containers used for interstate transport according to DOT regulations.
- Make sure the shell or head thickness of any container is at least 3/16 of an inch.
- Make sure electrical lighting circuits meet
all of the following:
- -Have suitable over-current protection, such as fuses or automatic circuit breakers.
- -Are suitably secured, insulated, and protected against physical damage.
- -Have wiring with sufficient carrying capacity and mechanical strength.
- Use only electric light.
Systems mounted on farm trucks or trailers for transporting ammonia
You must
- Construct and test containers, with a design pressure exceeding 15 psig, according to the Unfired Pressure Vessel Code.
Systems mounted on farm equipment for ammonia application
You must
- Construct and test containers according to the Unfired Pressure Vessel Code.
DOT containers
You must
- Make sure containers meet DOT specifications.
NONREFRIGERATED CONTAINERS
Installation
You must
- Provide a minimum distance of 5 feet between aboveground and underground containers that have more than a 1,200 gallon capacity each.
- Protect containers from floating away, in
areas with a potential for high flood waters, by providing either:
- -Secure anchorage
or - -Adequate pier height.
- -Secure anchorage
- Follow Tabel 2 for aboveground, nonrefrigerated containers.
If you have |
Then |
|
Aboveground containers
|
|
|
Floating type foundations on containers installed aboveground |
Make sure they are designed to adequately support the tank, contents, and pumping equipment. |
|
A horizontal, aboveground container
|
|
|
You must
- Follow Table 3 for underground, non-refrigerated containers.
|
Underground Nonrefrigerated Container Requirements |
||
If you have |
Then |
|
Underground containers
|
|
|
Reinstallation
You must
- Prohibit the reinstallation of nonrefrigerated
, previously installed underground, containers unless they meet
both of the following:
- -Pass a hydrostatic pressure retest using the original pressure specified by the Unfired Pressure Vessel Code under which the tank was constructed and
- -Show no evidence of serious corrosion.
- Maintain a corrosion resistant coating on reinstalled underground containers.
REFRIGERATED STORAGE TANKS
Installation
You must
- Support tanks on noncombustible foundations designed for the type of tank.
- Provide protection against flotation or other water damage, where high floodwater might occur.
- Prevent the effects of freezing and consequent frost heaving, in tanks used for product storage at less than 32°F, by providing either support or heat supply.
- Prevent accidental discharge of liquids from spreading into uncontrolled areas by providing, to the area surrounding a refrigerated tank or group of tanks, one of the following:
- -A drainage system provided with at least
a one percent slope that terminates in an impounding basin
with a capacity as large as the largest tank served
or
- -A diked enclosure with a capacity as large as the largest tank served.
- Meet, when using a diked enclosure or an impounding basin in a drainage system, the following requirements:
- -The wall is made of earth, steel, or concrete. If made of earth, meet both of the following:
- The top is flat and at least 2 feet wide
and
- There's a stable slope consistent with the angle of the earth used
- -Design the wall to be both:
- Liquid tight
and
- Able to withstand the hydrostatic pressure and the temperature.
- Provide for drainage of rain water, that doesn't permit the release of ammonia, from diked or impounding areas.
|
|
Note:
|
- Shallow channels in the ground surface or low curbs of earth can help guide the liquid to these low areas without contacting a large ground area.
Reinstallation
You must
- Make sure moved and reinstalled containers
of a size to require field fabrication are reconstructed and
reinspected to:
- -Meet the original Unfired Pressure Vessel
Code under which the tank was manufactured and do the following
according to the same code:
- A pressure retest
- Any necessary rerating.
- -Meet the original Unfired Pressure Vessel
Code under which the tank was manufactured and do the following
according to the same code:
