General Safety & Health Standards |
|
WAC
296-24-956
Electrical.
296-24-95601
Definitions applicable to WAC
296-24-956 through 296-24-985.
296-24-95603
Electric utilization systems.
296-24-95605
General requirements.
296-24-95607
Wiring design and protection.
296-24-95609
Wiring methods, components, and equipment for general use.
296-24-95611
Specific purpose equipment and installations.
296-24-95613
Hazardous (classified) locations.
296-24-95615
Special systems.
296-24-95617
Reserved.
206-24-95699
Appendices. Appendix A - Reference documents.
296-24-960
Working on or near exposed energized parts.
296-24-965
Safety-related work practices.
296-24-970
Training.
296-24-975
Selection and use of work practices.
296-24-980
Safeguards for personnel protection.
296-24-985
Use of equipment
WAC 296-24-956 Electrical.
This section addresses electrical safety requirements that are necessary
for the practical safeguarding of employees in their workplaces.
[Statutory Authority: RCW 49.17.040 and
49.17.050. 82-08-026 (Order 82-10), 296-24-956, filed 3/30/82.]
WAC 296-24-95601
Definitions applicable to WAC 296-24-956 through 296-24-985.
Unless the context indicates otherwise, words used in this section shall
have the meaning given.
(1) Acceptable. An installation or equipment is acceptable to
the director of labor and industries, and approved within the meaning
of this section:
(a) If it is accepted, or certified, or listed, or labeled, or otherwise
determined to be safe by a nationally recognized testing laboratory;
or
(b) With respect to an installation or equipment of a kind which no
nationally recognized testing laboratory accepts, certifies, lists,
labels, or determines to be safe, if it is inspected or tested by another
federal agency, or by a state, municipal, or other local authority responsible
for enforcing occupational safety provisions of the National Electrical
Code, and found in compliance with the provisions of the National Electrical
Code as applied in this section; or
(c) With respect to custom-made equipment or related installations
which are designed, fabricated for, and intended for use by a particular
customer, if it is determined to be safe for its intended use by its
manufacturer on the basis of test data which the employer keeps and
makes available for inspection to the director and his/her authorized
representatives. Refer to federal regulation 29 CFR 1910.7 for definition
of nationally recognized testing laboratory.
(2) Accepted. An installation is "accepted" if it has been inspected
and found by a nationally recognized testing laboratory to conform to
specified plans or to procedures of applicable codes.
(3) Accessible. (As applied to wiring methods.) Capable of being
removed or exposed without damaging the building structure of finish,
or not permanently closed in by the structure or finish of the building.
(See "concealed" and "exposed.")
(4) Accessible. (As applied to equipment.) Admitting close approach;
not guarded by locked doors, elevation, or other effective means. (See
"readily accessible.")
(5) Ampacity. Current-carrying capacity of electric conductors
expressed in amperes.
(6) Appliances. Utilization equipment, generally other than industrial,
normally built in standardized sizes or types, which is installed or connected
as a unit to perform one or more functions such as clothes washing, air
conditioning, food mixing, deep frying, etc.
(7) Approved. Acceptable to the authority enforcing this section.
The authority enforcing this section is the director of labor and industries.
The definition of "acceptable" indicates what is acceptable to the director
and therefore approved within the meaning of this section.
(8) Approved for the purpose. Approved for a specific purpose,
environment, or application described in a particular standard requirement.
Suitability of equipment or materials for a specific purpose, environment
or application may be determined by a nationally recognized testing laboratory,
inspection agency or other organization concerned with product evaluation
as part of its listing and labeling program. (See "labeled" or "listed.")
(9) Armored cable. Type AC armored cable is a fabricated assembly
of insulated conductors in a flexible metallic enclosure.
(10) Askarel. A generic term for a group of nonflammable synthetic
chlorinated hydrocarbons used as electrical insulating media. Askarels
of various compositional types are used. Under arcing conditions the gases
produced, while consisting predominantly of noncombustible hydrogen chloride,
can include varying amounts of combustible gases depending upon the askarel
type.
(11) Attachment plug (plug cap) (cap). A device which, by insertion
in a receptacle, establishes connection between the conductors of the
attached flexible cord and the conductors connected permanently to the
receptacle.
(12) Automatic. Self-acting, operating by its own mechanism when
actuated by some impersonal influence, as, for example, a change in current
strength, pressure, temperature, or mechanical configuration.
(13) Bare conductor, see "conductor."
(14) Bonding. The permanent joining of metallic parts to form
an electrically conductive path which will assure electrical continuity
and the capacity to conduct safely any current likely to be imposed.
(15) Bonding jumper. A reliable conductor to assure the required
electrical conductivity between metal parts required to be electrically
connected.
(16) Branch circuit. The circuit conductors between the final
overcurrent device protecting the circuit and the outlet(s).
(17) Building. A structure which stands alone or which is cut
off from adjoining structures by fire walls with all openings therein
protected by approved fire doors.
(18) Cabinet. An enclosure designed either for surface or flush
mounting, and provided with a frame, mat, or trim in which a swinging
door or doors are or may be hung.
(19) Cable tray system. A cable tray system is a unit or assembly
of units or sections, and associated fittings, made of metal or other
noncombustible materials forming a rigid structural system used to support
cables. Cable tray systems include ladders, troughs, channels, solid bottom
trays, and other similar structures.
(20) Cablebus. Cablebus is an approved assembly of insulated conductors
with fittings and conductor terminations in a completely enclosed, ventilated,
protective metal housing.
(21) Center pivot irrigation machine. A center pivot irrigation
machine is a multimotored irrigation machine which revolves around a central
pivot and employs alignment switches or similar devices to control individual
motors.
(22) Certified. Equipment is "certified" if it (a) has been tested
and found by a nationally recognized testing laboratory to meet nationally
recognized standards or to be safe for use in a specified manner, or (b)
is of a kind whose production is periodically inspected by a nationally
recognized testing laboratory, and (c) it bears a label, tag, or other
record of certification.
(23) Circuit breaker.
(a) (600 volts nominal, or less.) A device designed to open and close
a circuit by nonautomatic means and to open the circuit automatically
on a predetermined overcurrent without injury to itself when properly
applied within its rating.
(b) (Over 600 volts, nominal.) A switching device capable of making,
carrying, and breaking currents under normal circuit conditions, and
also making, carrying for a specified time, and breaking currents under
specified abnormal circuit conditions, such as those of short circuit.
(24) Class I locations. Class I locations are those in which
flammable gases or vapors are or may be present in the air in quantities
sufficient to produce explosive or ignitible mixtures. Class I locations
include the following:
(a) Class I, Division 1. A Class I, Division 1 location is a location:
(i) In which hazardous concentrations of flammable gases or vapors
may exist under normal operating conditions; or
(ii) In which hazardous concentrations of such gases or vapors may
exist frequently because of repair or maintenance operations or because
of leakage; or
(iii) In which breakdown or faulty operation of equipment or processes
might release hazardous concentrations of flammable gases or vapors,
and might also cause simultaneous failure of electric equipment.
Note: This classification usually includes locations
where volatile flammable liquids or liquefied flammable gases are
transferred from one container to another; interiors of spray booths
and areas in the vicinity of spraying and painting operations where
volatile flammable solvents are used; locations containing open tanks
or vats of volatile flammable liquids; drying rooms or compartments
for the evaporation of flammable solvents; locations containing fat
and oil extraction equipment using volatile flammable solvents; portions
of cleaning and dyeing plants where flammable liquids are used; gas
generator rooms and other portions of gas manufacturing plants where
flammable gas may escape; inadequately ventilated pump rooms for flammable
gas or for volatile flammable liquids; the interiors of refrigerators
and freezers in which volatile flammable materials are stored in open,
lightly stoppered, or easily ruptured containers; and all other locations
where ignitible concentrations of flammable vapors or gases are likely
to occur in the course of normal operations.
(b) Class I, Division 2. A Class I, Division 2 location is a location:
(i) In which volatile flammable liquids or flammable gases are handled,
processed, or used, but in which the hazardous liquids, vapors, or
gases will normally be confined within closed containers or closed
systems from which they can escape only in case of accidental rupture
or breakdown of such containers or systems, or in case of abnormal
operation of equipment; or
(ii) In which hazardous concentrations of gases or vapors are normally
prevented by positive mechanical ventilation, and which might become
hazardous through failure or abnormal operations of the ventilating
equipment; or
(iii) That is adjacent to a Class I, Division 1 location, and to
which hazardous concentrations of gases or vapors might occasionally
be communicated unless such communication is prevented by adequate
positive-pressure ventilation from a source of clean air, and effective
safeguards against ventilation failure are provided.
Note: This classification usually includes locations
where volatile flammable liquids or flammable gases or vapors are
used, but which would become hazardous only in case of an accident
or of some unusual operating condition. The quantity of flammable
material that might escape in case of accident, the adequacy of ventilating
equipment, the total area involved, and the record of the industry
or business with respect to explosions or fires are all factors that
merit consideration in determining the classification and extent of
each location.
Piping without valves, checks, meters, and similar devices would
not ordinarily introduce a hazardous condition even though used for
flammable liquids or gases. Locations used for the storage of flammable
liquids or a liquefied or compressed gases in sealed containers would
not normally be considered hazardous unless also subject to other
hazardous conditions.
Electrical conduits and their associated enclosures separated from
process fluids by a single seal or barrier are classed as a Division
2 location if the outside of the conduit and enclosures is a nonhazardous
location.
(25) Class II locations. Class II locations are those that are
hazardous because of the presence of combustible dust. Class II locations
include the following:
(a) Class II, Division 1. A Class II, Division 1 location is a location:
(i) In which combustible dust is or may be in suspension in the air
under normal operating conditions, in quantities sufficient to produce
explosives or ignitible mixtures; or
(ii) Where mechanical failure or abnormal operation of machinery
or equipment might cause such explosive or ignitible mixtures to be
produced, and might also provide a source of ignition through simultaneous
failure of electric equipment, operation of protection devices, or
from other causes; or
(iii) In which combustible dusts of an electrically conductive nature
may be present.
Note: This classification may include areas
of grain handling and processing plants, starch plants, sugar-pulverizing
plants, malting plants, hay-grinding plants, coal pulverizing plants,
areas where metal dusts and powders are produced or processed, and
other similar locations which contain dust producing machinery and
equipment (except where the equipment is dust-tight or vented to the
outside). These areas would have combustible dust in the air, under
normal operating conditions, in quantities sufficient to produce explosive
or ignitible mixtures. Combustible dusts which are electrically nonconductive
include dusts produced in the handling and processing of grain and
grain products, pulverized sugar and cocoa, dried egg and milk powders,
pulverized spices, starch and pastes, potato and woodflour, oil meal
from beans and seed, dried hay, and other organic materials which
may produce combustible dusts when processed or handled. Dusts containing
magnesium or aluminum are particularly hazardous and the use of extreme
caution is necessary to avoid ignition and explosion.
(b) Class II, Division 2. A Class II, Division 2 location is a location
in which:
(i) Combustible dust will not normally be in suspension in the air
in quantities sufficient to produce explosive or ignitible mixtures;
and dust accumulations are normally insufficient to interfere with
the normal operation of electrical equipment or other apparatus; or
(ii) Dust may be in suspension in the air as a result of infrequent
malfunctioning of handling or processing equipment, and dust accumulations
resulting therefrom may be ignitible by abnormal operation or failure
of electrical equipment or other apparatus.
Note: This classification includes locations
where dangerous concentrations of suspended dust would not be likely
but where dust accumulations might form on or in the vicinity of electric
equipment. These areas may contain equipment from which appreciable
quantities of dust would escape under abnormal operating conditions
or be adjacent to a Class II Division 1 location, as described above,
into which an explosive or ignitible concentration of dust may be
put into suspension under abnormal operating conditions.
(26) Class III locations. Class III locations are those that
are hazardous because of the presence of easily ignitible fibers or flyings
but in which such fibers or flyings are not likely to be in suspension
in the air in quantities sufficient to produce ignitible mixtures. Class
III locations include the following:
(a) Class III, Division 1. A Class III, Division 1 location is a location
in which easily ignitible fibers or materials producing combustible
flyings are handled, manufactured, or used.
Note: Such locations usually include some parts
of rayon, cotton, and other textile mills; combustible fiber manufacturing
and processing plants; cotton gins and cottonseed mills; flax-processing
plants; clothing manufacturing plants; woodworking plants, and establishments;
and industries involving similar hazardous processes or conditions.
Easily ignitible fibers and flyings include rayon, cotton (including
cotton linters and cotton waste), sisal or henequen, istle, jute, hemp,
tow, cocoa fiber, oakum, baled waste kapok, Spanish moss, excelsior,
and other materials of similar nature.
(b) Class III, Division 2. A Class III, Division 2 location is a location
in which easily ignitible fibers are stored or handled, except in process
of manufacture.
(27) Collector ring. A collector ring is an assembly of slip
rings for transferring electrical energy from a stationary to a rotating
member.
(28) Concealed. Rendered inaccessible by the structure or finish
of the building. Wires in concealed raceways are considered concealed,
even though they may become accessible by withdrawing them. (See "accessible.
(As applied to wiring methods."))
(29) Conductor.
(a) Bare. A conductor having no covering or electrical insulation
whatsoever.
(b) Covered. A conductor encased within material of composition
or thickness that is not recognized as electrical insulation.
(c) Insulated. A conductor encased within material of composition
and thickness that is recognized as electrical insulation.
(30) Conduit body. A separate portion of a conduit or tubing
system that provides access through a removable cover(s) to the interior
of the system at a junction of two or more sections of the system or at
a terminal point of the system. Boxes such as FS and FD or larger cast
or sheet metal boxes are not classified as conduit bodies.
(31) Controller. A device or group of devices that serves to govern,
in some predetermined manner, the electric power delivered to the apparatus
to which it is connected.
(32) Cooking unit, counter-mounted. A cooking appliance designed
for mounting in or on a counter and consisting of one or more heating
elements, internal wiring, and built-in or separately mountable controls.
(See "oven, wall-mounted.")
(33) Covered conductor. See "conductor."
(34) Cutout. (Over 600 volts, nominal.) An assembly of a fuse
support with either a fuseholder, fuse carrier, or disconnecting blade.
The fuseholder or fuse carrier may include a conducting element (fuse
link), or may act as the disconnecting blade by the inclusion of an nonfusible
member.
(35) Cutout box. An enclosure designed for surface mounting and
having swinging doors or covers secured directly to and telescoping with
the walls of the box proper. (See "cabinet.")
(36) Damp location. See "location."
(37) Dead front. Without live parts exposed to a person on the
operating side of the equipment.
(38) Device. A unit of an electrical system which is intended
to carry but not utilize electric energy.
(39) Dielectric heating. Dielectric heating is the heating of
a nominally insulating material due to its own dielectric losses when
the materials is placed in a varying electric filed.
(40) Disconnecting means. A device, or group of devices, or other
means by which the conductors of a circuit can be disconnected from their
source of supply.
(41) Disconnecting (or isolating) switch. (Over 600 volts, nominal.)
A mechanical switching device used for isolating a circuit or equipment
from a source of power.
(42) Dry location. See "location."
(43) Electric sign. A fixed, stationary, or portable self-contained,
electrically illuminated utilization equipment with words or symbols designed
to convey information or attract attention.
(44) Enclosed. Surrounded by a case, housing, fence or walls which
will prevent persons from accidentally contacting energized parts.
(45) Enclosure. The case or housing of apparatus, or the fence
or walls surrounding an installation to prevent personnel from accidentally
contacting energized parts, or to protect the equipment from physical
damage.
(46) Equipment. A general term including material, fittings, devices,
appliances, fixtures, apparatus, and the like, used as a part of, or in
connection with, an electrical installation.
(47) Equipment grounding conductor. See "grounding conductor,
equipment."
(48) Explosion-proof apparatus. Apparatus enclosed in a case
that is capable of withstanding an explosion of a specified gas or vapor
which may occur within it and of preventing the ignition of a specified
gas or vapor surrounding the enclosure by sparks, flashes, or explosion
of the gas or vapor within, and which operates at such an external temperature
that it will not ignite a surrounding flammable atmosphere.
(49) Exposed. (As applied to live parts.) Capable of being inadvertently
touched or approached nearer than a safe distance by a person. It is applied
to parts not suitably guarded, isolated, or insulated. (See "accessible"
and "concealed.")
(50) Exposed. (As applied to wiring methods.) On or attached to
the surface or behind panels designed to allow access. (See "accessible.
(As applied to wiring methods."))
(51) Exposed. (For the purpose of WAC
296-24-95615(5), communications systems.) Where the circuit
is in such a position that in case of failure of supports or insulation,
contact with another circuit may result.
(52) Externally operable. Capable of being operated without exposing
the operator to contact with live parts.
(53) Feeder. All circuit conductors between the service equipment,
or the generator switchboard of an isolated plant, and the final branch-circuit
overcurrent device.
(54) Fitting. An accessory such as a locknut, bushing, or other
part of a wiring system that is intended primarily to perform a mechanical
rather than an electrical function.
(55) Fuse. (Over 600 volts, nominal.) An overcurrent protective
device with a circuit opening fusible part that is heated and severed
by the passage of overcurrent through it. A fuse comprises all the parts
that form a unit capable of performing the prescribed functions. It may
or may not be the complete device necessary to connect it into an electrical
circuit.
(56) Ground. A conducting connection, whether intentional or accidental,
between an electrical circuit or equipment and the earth, or to some conducting
body that serves in place of the earth.
(57) Grounded. Connected to earth or to some conducting body that
serves in place of the earth.
(58) Grounded, effectively. (Over 600 volts, nominal.) Permanently
connected to earth through a ground connection of sufficiently low impedance
and having sufficient ampacity that ground fault current which may occur
cannot build up to voltages dangerous to personnel.
(59) Grounded conductor. A system or circuit conductor that is
intentionally grounded.
(60) Grounding conductor. A conductor used to connect equipment
or the grounded circuit of a wiring system to a grounding electrode or
electrodes.
(61) Grounding conductor, equipment. The conductor used to connect
the noncurrent-carrying metal parts of equipment, raceways, and other
enclosures to the system grounded conductor and/or the grounding electrode
conductor at the service equipment or at the source of a separately derived
system.
(62) Grounding electrode conductor. The conductor used to connect
the grounding electrode to the equipment grounding conductor and/or to
the grounded conductor of the circuit at the service equipment or at the
source of a separately derived system.
(63) Ground-fault circuit-interrupter. A device whose function
is to interrupt the electric circuit to the load when a fault current
to ground exceeds some predetermined value that is less than that required
to operate the overcurrent protective device of the supply circuit.
(64) Guarded. Covered, shielded, fenced, enclosed, or otherwise
protected by means of suitable covers, casings, barriers, rails, screens,
mats, or platforms to remove the likelihood of approach to a point of
danger or contact by persons or objects.
(65) Health care facilities. Buildings or portions of buildings
and mobile homes that contain, but are not limited to, hospitals, nursing
homes, extended care facilities, clinics, and medical and dental offices,
whether fixed or mobile.
(66) Heating equipment. For the purposes of WAC
296-24-95611(7), the term "heating equipment" includes any
equipment used for heating purposes if heat is generated by induction
or dielectric methods.
(67) Hoistway. Any shaftway, hatchway, well hole, or other vertical
opening or space in which an elevator or dumbwaiter is designed to operate.
(68) Identified. Identified, as used in reference to a conductor
or its terminal, means that such conductor or terminal can be readily
recognized as grounded.
(69) Induction heating. Induction heating is the heating of a
nominally conductive material due to its own I2R losses when the material
is placed in a varying electromagnetic field.
(70) Insulated conductor. See "conductor."
(71) Interrupter switch. (Over 600 volts, nominal.) A switch
capable of making, carrying, and interrupting specified currents.
(72) Irrigation machine. An irrigation machine is an electrically
driven or controlled machine, with one or more motors, not hand portable,
and used primarily to transport and distribute water for agricultural
purposes.
(73) Isolated. Not readily accessible to persons unless special
means for access are used.
(74) Isolated power system. A system comprising an isolating
transformer or its equivalent, a line isolation monitor, and its ungrounded
circuit conductors.
(75) Labeled. Equipment is "labeled" if there is attached to it
a label, symbol, or other identifying mark of a nationally recognized
testing laboratory which, (a) makes periodic inspections of the production
of such equipment, and (b) whose labeling indicates compliance with nationally
recognized standards or tests to determine safe use in a specified manner.
(76) Lighting outlet. An outlet intended for the direct connection
of a lampholder, a lighting fixture, or a pendant cord terminating in
a lampholder.
(77) Line-clearance tree trimming. The pruning, trimming, repairing,
maintaining, removing, or clearing of trees or cutting of brush that is
within 10 feet of electric supply lines and equipment.
(78) Listed. Equipment is "listed" if it is of a kind mentioned
in a list which, (a) is published by a nationally recognized laboratory
which makes periodic inspection of the production of such equipment, and
(b) states such equipment meets nationally recognized standards or has
been tested and found safe for use in a specified manner.
(79) Location.
(a) Damp location. Partially protected locations under canopies,
marquees, roofed open porches, and like locations, and interior locations
subject to moderate degrees of moisture, such as some basements, some
barns, and some cold-storage warehouses.
(b) Dry location. A location not normally subject to dampness
or wetness. A location classified as dry may be temporarily subject
to dampness or wetness, as in the case of a building under construction.
(c) Wet location. Installations underground or in concrete
slabs or masonry in direct contact with the earth, and locations subject
to saturation with water or other liquids, such as vehicle-washing areas,
and locations exposed to weather and unprotected.
(80) Medium voltage cable. Type MV medium voltage cable is a
single or multiconductor solid dielectric insulated cable rated 2000 volts
or higher.
(81) Metal-clad cable. Type MC cable is a factory assembly of
one or more conductors, each individually insulated and enclosed in a
metallic sheath of interlocking tape, or a smooth or corrugated tube.
(82) Mineral-insulated metal-sheathed cable. Type MI mineral-insulated
metal-sheathed cable is a factory assembly of one or more conductors insulated
with a highly compressed refractory mineral insulation and enclosed in
a liquidtight and gastight continuous copper sheath.
(83) Mobile x-ray. X-ray equipment mounted on a permanent base
with wheels and/or casters for moving while completely assembled.
(84) Nonmetallic-sheathed cable. Nonmetallic-sheathed cable is
a factory assembly of two or more insulated conductors having an outer
sheath of moisture resistant, flame-retardant, nonmetallic material. Nonmetallic
sheathed cable is manufactured in the following types:
(a) Type NM. The overall covering has a flame-retardant and
moisture-resistant finish.
(b) Type NMC. The overall covering is flame-retardant, moisture-resistant,
fungus-resistant, and corrosion-resistant.
(85) Oil (filled) cutout. (Over 600 volts, nominal.) A cutout
in which all or part of the fuse support and its fuse link or disconnecting
blade are mounted in oil with complete immersion of the contacts and the
fusible portion of the conducting element (fuse link), so that arc interruption
by severing of the fuse link or by opening of the contacts will occur
under oil.
(86) Open wiring on insulators. Open wiring on insulators is
an exposed wiring method using cleats, knobs, tubes, and flexible tubing
for the protection and support of single insulated conductors run in or
on buildings, and not concealed by the building structure.
(87) Outlet. A point on the wiring system at which current is
taken to supply utilization equipment.
(88) Outline lighting. An arrangement of incandescent lamps or
electric discharge tubing to outline or call attention to certain features
such as the shape of a building or the decoration of a window.
(89) Oven, wall-mounted. An oven for cooking purposes designed
for mounting in or on a wall or other surface and consisting of one or
more heating elements, internal wiring, and built-in or separately mountable
controls. (See "cooking unit, counter-mounted.")
(90) Overcurrent. Any current in excess of the rated current of
equipment or the ampacity of a conductor. It may result from overload
(see definition), short circuit, or ground fault. A current in excess
of rating may be accommodated by certain equipment and conductors for
a given set of conditions. Hence the rules for overcurrent protection
are specific for particular situations.
(91) Overload. Operation of equipment in excess of normal, full
load rating, or of a conductor in excess of rated ampacity which, when
it persists for a sufficient length of time, would cause damage or dangerous
overheating. A fault, such as a short circuit or ground fault, is not
an overload. (See "overcurrent.")
(92) Panelboard. A single panel or group of panel units designed
for assembly in the form of a single panel; including buses, automatic
overcurrent devices, and with or without switches for the control of light,
heat, or power circuits; designed to be placed in a cabinet or cutout
box placed in or against a wall or partition and accessible only from
the front. (See "switchboard.")
(93) Permanently installed decorative fountains and reflection pools.
Those that are constructed in the ground, on the ground, or in a building
in such a manner that the pool cannot be readily disassembled for storage
and are served by electrical circuits of any nature. These units are primarily
constructed for their aesthetic value and not intended for swimming or
wading.
(94) Permanently installed swimming pools, wading and therapeutic
pools. Those that are constructed in the ground, on the ground, or
in a building in such a manner that the pool cannot be readily disassembled
for storage whether or not served by electrical circuits of any nature.
(95) Portable x-ray. X-ray equipment designed to be hand-carried.
(96) Power and control tray cable. Type TC power and control
tray cable is a factory assembly of two or more insulated conductors,
with or without associated bare or covered grounding conductors under
a nonmetallic sheath, approved for installation in cable trays, in raceways,
or where supported by a messenger wire.
(97) Power fuse. (Over 600 volts, nominal.) See "fuse."
(98) Power-limited tray cable. Type PLTC nonmetallic-sheathed
power limited tray cable is a factory assembly of two or more insulated
conductors under a nonmetallic jacket.
(99) Power outlet. An enclosed assembly which may include receptacles,
circuit breakers, fuseholders, fused switches, buses and watt-hour meter
mounting means; intended to supply and control power to mobile homes,
recreational vehicles or boats, or to serve as a means for distributing
power required to operate mobile or temporarily installed equipment.
(100) Premises wiring system. That interior and exterior wiring,
including power, lighting, control, and signal circuit wiring together
with all of its associated hardware, fittings, and wiring devices, both
permanently and temporarily installed, which extends from the load end
of the service drop, or load end of the service lateral conductors to
the outlet(s). Such wiring does not include wiring internal to appliances,
fixtures, motors, controllers, motor control centers, and similar equipment.
(101) Qualified person. One familiar with the construction and
operation of the equipment and the hazards involved.
Note 1: Whether an employee is considered to be
a "qualified person" will depend upon various circumstances in
the workplace. It is possible and, in fact, likely for an individual
to be considered "qualified" with regard to certain equipment
in the workplace, but "unqualified" as to other equipment. (See
WAC
296-24-970 for training requirements that specifically apply
to qualified persons.)
Note 2: An employee who is undergoing on-the-job
training and who, in the course of such training, has demonstrated an
ability to perform duties safely at his or her level of training and who
is under the direct supervision of a qualified person is considered to
be a qualified person for the performance of those duties.
(102) Raceway. A channel designed expressly for holding wires,
cables, or busbars, with additional functions as permitted in this part.
Raceways may be of metal or insulating material, and the term includes
rigid metal conduit, rigid nonmetallic conduit, intermediate metal conduit,
liquidtight flexible metal conduit, flexible metallic tubing, flexible
metal conduit, electrical metallic tubing, underfloor raceways, cellular
concrete floor raceways, cellular metal floor raceways, surface raceways,
wireways, and busways.
(103) Readily accessible. Capable of being reached quickly for
operation, renewal, or inspections, without requiring those to whom ready
access is requisite to climb over or remove obstacles or to resort to
portable ladders, chairs, etc. (See "accessible.")
(104) Receptacle. A receptacle is a contact device installed at
the outlet for the connection of a single attachment plug. A single receptacle
is a single contact device with no other contact device on the same yoke.
A multiple receptacle is a single device containing two or more receptacles.
(105) Receptacle outlet. An outlet where one or more receptacles
are installed.
(106) Remote-control circuit. Any electric circuit that controls
any other circuit through a relay or an equivalent device.
(107) Sealable equipment. Equipment enclosed in a case or cabinet
that is provided with a means of sealing or locking so that live parts
cannot be made accessible without opening the enclosure. The equipment
may or may not be operable without opening the enclosure.
(108) Separately derived system. A premises wiring system whose
power is derived from generator, transformer, or converter winding and
has no direct electrical connection, including a solidly connected grounded
circuit conductor, to supply conductors originating in another system.
(109) Service. The conductors and equipment for delivering energy
from the electricity supply system to the wiring system of the premises
served.
(110) Service cable. Service conductors made up in the form of
a cable.
(111) Service conductors. The supply conductors that extend from
the street main or from transformers to the service equipment of the premises
supplied.
(112) Service drop. The overhead service conductors from the
last pole or other aerial support to and including the splices, if any,
connecting to the service-entrance conductors at the building or other
structure.
(113) Service-entrance cable. Service-entrance cable is a single
conductor or multiconductor assembly provided with or without an overall
covering, primarily used for services and of the following types:
(a) Type SE, having a flame-retardant, moisture-resistant covering,
but not required to have inherent protection against mechanical abuse.
(b) Type use, recognized for underground use, having a moisture-resistant
covering, but not required to have a flame-retardant covering or inherent
protection against mechanical abuse. Single-conductor cables having
an insulation specifically approved for the purpose do not require an
outer covering.
(114) Service-entrance conductors, overhead system. The service
conductors between the terminals of the service equipment and a point
usually outside the building, clear of building walls, where joined by
tap or splice to the service drop.
(115) Service entrance conductors, underground system. The service
conductors between the terminals of the service equipment and the point
of connection to the service lateral. Where service equipment is located
outside the building walls, there may be no service-entrance conductors,
or they may be entirely outside the building.
(116) Service equipment. The necessary equipment, usually consisting
of a circuit breaker or switch and fuses, and their accessories, located
near the point of entrance of supply conductors to a building or other
structure, or an otherwise defined area, and intended to constitute the
main control and means of cutoff of the supply.
(117) Service raceway. The raceway that encloses the service-entrance
conductors.
(118) Shielded nonmetallic-sheathed cable. Type SNM, shielded
nonmetallic-sheathed cable is a factory assembly of two or more insulated
conductors in an extruded core of moisture-resistant, flame-resistant
nonmetallic material, covered with an overlapping spiral metal tape and
wire shield and jacketed with an extruded moisture-resistant, flame-resistant,
oil-resistant, corrosion-resistant, fungus-resistant, and sunlight-resistant
nonmetallic material.
(119) Show window. Any window used or designed to be used for
the display of goods or advertising material, whether it is fully or partly
enclosed or entirely open at the rear and whether or not it has a platform
raised higher than the street floor level.
(120) Sign. See "electric sign."
(121) Signaling circuit. Any electric circuit that energizes
signaling equipment.
(122) Special permission. The written consent of the authority
having jurisdiction.
(123) Storable swimming or wading pool. A pool with a maximum
dimension of fifteen feet and a maximum wall height of three feet and
is so constructed that it may be readily disassembled for storage and
reassembled to its original integrity.
(124) Switchboard. A large single panel, frame, or assembly of
panels which have switches, buses, instruments, overcurrent and other
protective devices mounted on the face or back or both. Switchboards are
generally accessible from the rear as well as from the front and are not
intended to be installed in cabinets. (See "panelboard.")
(125) Switches.
(a) General-use switch. A switch intended for use in general distribution
and branch circuits. It is rated in amperes, and it is capable of interrupting
its rated current at its rated voltage.
(b) General-use snap switch. A form of general-use switch so constructed
that it can be installed in flush device boxes or on outlet box covers,
or otherwise used in conjunction with wiring systems recognized by this
part.
(c) Isolating switch. A switch intended for isolating an electric circuit
from the source of power. It has no interrupting rating, and it is intended
to be operated only after the circuit has been opened by some other
means.
(d) Motor-circuit switch. A switch, rated in horsepower, capable of
interrupting the maximum operating overload current of a motor of the
same horsepower rating as the switch at the rated voltage.
(126) Switching devices. (Over 600 volts, nominal.) Devices designed
to close and/or open one or more electric circuits. Included in this category
are circuit breakers, cutouts, disconnecting (or isolating) switches,
disconnecting means, interrupter switches, and oil (filled) cutouts.
(127) Transportable x-ray. X-ray equipment installed in a vehicle
or that may readily be disassembled for transport in a vehicle.
(128) Utilization equipment. Utilization equipment means equipment
which utilizes electric energy for mechanical, chemical, heating, lighting,
or similar useful purpose.
(129) Utilization system. A utilization system is a system which
provides electric power and light for employee workplaces, and includes
the premises wiring system and utilization equipment.
(130) Ventilated. Provided with a means to permit circulation
of air sufficient to remove an excess of heat, fumes, or vapors.
(131) Volatile flammable liquid. A flammable liquid having a
flash point below 38 degrees C (100 degrees F) or whose temperature is
above its flash point.
(132) Voltage (of a circuit). The greatest root-mean-square (effective)
difference of potential between any two conductors of the circuit concerned.
(133) Voltage, nominal. A nominal value assigned to a circuit
or system for the purpose of conveniently designating its voltage class
(as 120/240, 480Y/277, 600, etc.). The actual voltage at which a circuit
operates can vary from the nominal within a range that permits satisfactory
operation of equipment.
(134) Voltage to ground. For grounded circuits, the voltage between
the given conductor and that point or conductor of the circuit that is
grounded; for undergrounded circuits, the greatest voltage between the
given conductor and any other conductor of the circuit.
(135) Watertight. So constructed that moisture will not enter
the enclosure.
(136) Weatherproof. So constructed or protected that exposure
to the weather will not interfere with successful operation. Rainproof,
raintight, or watertight equipment can fulfill the requirements for weatherproof
where varying weather conditions other than wetness, such as snow, ice,
dust, or temperature extremes, are not a factor.
(137) Wet location. See "location."
(138) Wireways. Wireways are sheet-metal troughs with hinged or
removable covers for housing and protecting electric wires and cable and
in which conductors are laid in place after the wireway has been installed
as a complete system.
[Statutory Authority: Chapter 49.17 RCW.
94-15-096 (Order 94-07), 296-24-95601, filed 7/20/94, effective 9/20/94;
91-24-017 (Order 91-07), 296-24-95601, filed 11/22/91, effective 12/24/91;
88-23-054 (Order 88-25), 296-24-95601, filed 11/14/88; 87-24-051 (Order
87-24), 296-24-95601, filed 11/30/87. Statutory Authority: RCW 49.17.040
and 49.17.050. 82-08-026 (Order 82-10), 296-24-95601, filed 3/30/82.]
WAC 296-24-95603
Electric utilization systems.
(1) Scope.
(a) Covered. The provisions of WAC
296-24-95603 through 296-24-985
cover electrical installations and utilization equipment installed
or used within or on buildings, structures, and other premises
including:
(i) Yards;
(ii) Carnivals;
(iii) Parking and other lots;
(iv) Mobile homes;
(v) Recreational vehicles;
(vi) Industrial substations under 750 volts. Chapter
296-45 WAC, Safety standards for electrical workers, shall
apply to industrial substations of 750 volts or more;
(vii) Conductors that connect the installations to a supply of electricity;
and
(viii) Other outside conductors on the premises.
(b) Not covered. The provisions of WAC
296-24-95603 through 296-24-985
do not cover:
(i) Installations in ships, watercraft, railway rolling stock, aircraft,
or automotive vehicles other than mobile homes and recreational vehicles.
(ii) Installations underground in mines.
(iii) Installations of railways for generation, transformation, transmission,
or distribution of power used exclusively for operation of rolling
stock or installations used exclusively for signaling and communication
purposes.
(iv) Installations of communication equipment under the exclusive
control of communication utilities, located outdoors or in building
spaces used exclusively for such installations.
(v) Installations under the exclusive control of electric utilities
for the purpose of communication or metering; or for the generation,
control, transformation, transmission, and distribution of electric
energy located in buildings used exclusively by utilities for such
purposes or located outdoors on property owned or leased by the utility
or on public highways, streets, roads, etc., or outdoors by established
rights on private property.
(2) Extent of application.
(a) The requirements contained in the sections listed below shall apply
to all electrical installations and utilization equipment, regardless
of when they were designed or installed:
Sections:
| WAC
296-24-95605 |
(2) |
Examination, installation,
and use of equipment. |
| " |
" |
(3) |
Splices. |
| " |
" |
(4) |
Arcing parts. |
| " |
" |
(5) |
Marking. |
| " |
" |
(6) |
Identification of
disconnection means. |
| " |
" |
(7)(b) |
Guarding of live
parts. |
| WAC
296-24-95607 |
(5)(a)(i) |
Protection of conductors
and equipment |
| " |
" |
(5)(a)(iv) |
Location in or on
premises. |
| " |
" |
(5)(a)(v) |
Arcing or suddenly
moving parts. |
| " |
" |
(6)(a)(ii) |
2-Wire DC systems
to be grounded. |
| " |
" |
(6)(a)(iii) and
(iv) |
AC systems to be
grounded. |
| " |
" |
(6)(a)(v) |
AC systems 50 to
1000 volts not required to be grounded. |
| " |
" |
(6)(c) |
Grounding connections. |
| " |
" |
(6)(d) |
Grounding path. |
|
WAC
296-24-95607 |
(6)(e)(iv) (A)through(D) |
Fixed equipment
required to be grounded. |
| " |
" |
(6)(e)(v) |
Grounding of equipment
connected by cord and plug. |
| " |
" |
(6)(e)(vi) |
Grounding or nonelectrical
equipment. |
| " |
" |
(6)(f)(i) |
Methods of grounding
fixed equipment. |
| WAC
296-24-95609 |
(7)(a)(i) and (ii) |
Flexible cords and
cables, uses. |
| " |
" |
(7)(a)(iii) |
Flexible cords and
cables prohibited. |
| " |
" |
(7)(b)(ii) |
Flexible cords and
cables, splices. |
| " |
" |
(7)(b)(iii) |
Pull at joints and
terminals of flexible cords and cables. |
| WAC
296-24-95613 |
|
Hazardous (classified)
locations. |
(b) Every electric utilization system and all utilization equipment
installed after March 15, 1972, and every major replacement,
modification, repair, or rehabilitation, after March 15, 1972,
of any part of any electric utilization system or utilization
equipment installed before March 15, 1972, shall comply with
the provisions of WAC
296-24-956 through 296-24-985.
Note: "Major replacements, modifications,
repairs, or rehabilitations" include work similar to that involved
when a new building or facility is built, a new wing is added, or an
entire floor is renovated.
(c) The following provisions apply to electric utilization systems
and utilization equipment installed after April 16, 1981:
| WAC
296-24-95605 |
(8)(d)(i) and (ii) |
Entrance and access
to work space (over 600 volts) |
| WAC
296-24-95607 |
(5)(a)(vi)(b) |
Circuit breakers
operated vertically. |
| " |
" |
(5)(a)(vi)(C) |
Circuit breakers
used as switches. |
| " |
" |
(6)(g)(ii) |
Grounding of systems
of 1000 volts or more supplying portable or mobile equipment. |
| WAC
296-24-95609 |
(10)(f)(ii)(B) |
Switching series
capacitors over 600 volts. |
| WAC
296-24-95611 |
(3)(b) |
Warning signs for
elevators and escalators. |
| " |
" |
(9) |
Electrically controlled
irrigation machines. |
| " |
" |
(10)(e) |
Ground-fault circuit
interrupters for fountains. |
| WAC
296-24-95615 |
(1)(a)(ii) |
Physical protection
of conductors over 600 volts. |
| " |
" |
(3)(b) |
Marking of Class
2 and Class 3 power supplies. |
| " |
" |
(4) |
Fire protective
signaling circuits. |
[Statutory Authority: Chapter
49.17 RCW. 91-24-017 (Order 91-07), 296-24-95603, filed 11/22/91, effective
12/24/91; 87-24-051 (Order 87-24), 296-24-95603, filed 11/30/87. Statutory
Authority: RCW 49.17.040 and 49.17.050. 82-08-026 (Order 82-10), 296-24-95603,
filed 3/30/82.]
WAC 296-24-95605
General requirements.
(1) Approval. The conductors and equipment required or permitted by this
section shall be acceptable only if approved.
(2) Examination, installation, and use of equipment.
(a) Examination. Electrical equipment shall be free from recognized
hazards that are likely to cause death or serious physical harm to employees.
Safety of equipment shall be determined using the following considerations:
(i) Suitability for installation and use in conformity with the provisions
of this part. Suitability of equipment for an identified purpose may
be evidenced by listing or labeling for that identified purpose.
(ii) Mechanical strength and durability, including, for parts designed
to enclose and protect other equipment, the adequacy of the protection
thus provided.
(iii) Electrical insulation.
(iv) Heating effects under conditions of use.
(v) Arcing effects.
(vi) Classification by type, size, voltage, current capacity, specific
use.
(vii) Other factors which contribute to the practical safeguarding
of employees using or likely to come in contact with the equipment.
(b) Installation and use. Listed or labeled equipment shall be used
or installed in accordance with any instructions included in the listing
or labeling.
(3) Splices. Conductors shall be spliced or joined with splicing devices
suitable for the use or by brazing, welding, or soldering with a fusible
metal or alloy. Soldered splices shall first be so spliced or joined as
to be mechanically and electrically secure without solder and then soldered.
All splices and joints and the free ends of conductors shall be covered
with an insulation equivalent to that of the conductors or with an insulating
device suitable for the purpose.
(4) Arcing parts. Parts of electric equipment which in ordinary operation
produce arcs, sparks, flames, or molten metal shall be enclosed or separated
and isolated from all combustible material.
(5) Marking. Electrical equipment may not be used unless the manufacturer's
name, trademark, or other descriptive marking by which the organization
responsible for the product may be identified is placed on the equipment.
Other markings shall be provided giving voltage, current, wattage, or
other ratings as necessary. The marking shall be of sufficient durability
to withstand the environment involved.
(6) Identification of disconnecting means and circuits. Each disconnecting
means required by this part for motors and appliances shall be legibly
marked to indicate its purpose, unless located and arranged so the purpose
is evident. Each service, feeder, and branch circuit, at its disconnecting
means or overcurrent device, shall be legibly marked to indicate its purpose,
unless located and arranged so the purpose is evident. These markings
shall be of sufficient durability to withstand the environment involved.
(7) 600 volts, nominal, or less.
(a) Working space about electric equipment. Sufficient access and working
space shall be provided and maintained about all electric equipment
to permit ready and safe operation and maintenance of such equipment.
(i) Working clearances. Except as required or permitted elsewhere
in this chapter, the dimension of the working space in the direction
of access to live parts operating at 600 volts or less and likely
to require examination, adjustment, servicing, or maintenance while
alive may not be less than indicated in Table S-1. In addition to
the dimensions shown in Table S-1, workspace may not be less than
30 inches wide in front of the electric equipment. Distances shall
be measured from the live parts if they are exposed, or from the enclosure
front or opening if the live parts are enclosed. Concrete, brick,
or tile walls are considered to be grounded. Working space is not
required in back of assemblies such as dead-front switchboards or
motor control centers where there are no renewable or adjustable parts
such as fuses or switches on the back and where all connections are
accessible from locations other than the back.
TABLE S-1--Working Clearances
| Minimum clear
distance for condition2 (ft) |
| Nominal voltage
to ground |
| |
(a) |
(b) |
(c) |
| 0-150 |
13 |
13 |
3 |
| 151-600 |
13 |
3 1/2 |
4 |
1Minimum clear distances may be 2 feet 6 inches for installations
built prior to effective date of this section.
2Conditions (a), (b), (c), are as follows: (a) Exposed live
parts on one side and no live or grounded parts on the other side of the
working space, or exposed live parts on both sides effectively guarded
by suitable wood or other insulating material. Insulated wire or insulated
busbars operating at not over 300 volts are not considered live parts.
(b) Exposed live parts on one side and grounded parts on the other side
(c) Exposed live parts on both sides of the workspace (not guarded as
provided in condition (a)) with the operator between.
(ii) Clear spaces. Working space required by this part may not be
used for storage. When normally enclosed live parts are exposed for
inspection or servicing, the working space, if in a passageway or
general open space, shall be suitably guarded.
(iii) Access and entrance to working space. At least one entrance
of sufficient area shall be provided to give access to the working
space about electric equipment.
(iv) Front working space. Where there are live parts normally exposed
on the front of switchboards or motor control centers, the working
space in front of such equipment may not be less than 3 feet.
(v) Illumination. Illumination shall be provided for all working
spaces about service equipment, switchboards, panelboards, and motor
control centers installed indoors.
(vi) Headroom. The minimum headroom of working spaces about service
equipment, switchboards, panelboards, or motor control centers shall
be 6 feet 3 inches.
Note: As used in this section, a motor control
center is an assembly of one or more enclosed sections having a common
power bus and principally containing motor control units.
(b) Guarding of live parts.
(i) Except as required or permitted elsewhere in this section, live
parts of electric equipment operating at 50 volts or more shall be
guarded against accidental contact by approved cabinets or other forms
of approved enclosures, or by any of the following means:
(A) By location in a room, vault, or similar enclosure that is
accessible only to qualified persons.
(B) By suitable permanent, substantial partitions or screens so
arranged that only qualified persons will have access to the space
within reach of the live parts. Any openings in such partitions
or screens shall be so sized and located that persons are not likely
to come into accidental contact with live parts or to bring conducting
objects into contact with them.
(C) By location on a suitable balcony, gallery, or platform so
elevated and arranged as to exclude unqualified persons.
(D) By elevation of 8 feet or more above the floor or other working
surface.
(ii) In locations where electric equipment would be exposed to physical
damage, enclosures or guards shall be so arranged and of such strength
as to prevent such damage.
(iii) Entrances to rooms and other guarded locations containing exposed
live parts shall be marked with conspicuous warning signs forbidding
unqualified persons to enter.
(8) Over 600 volts, nominal.
(a) General. Conductors and equipment used on circuits exceeding 600
volts, nominal, shall comply with all applicable provisions of subsections
(1) through (7) of this section and with the following provisions which
supplement or modify those requirements. The provisions of (b), (c)
and (d) of this subsection do not apply to equipment on the supply side
of the service conductors.
(b) Enclosure for electrical installations. Electrical installations
in a vault, room, closet or in an area surrounded by a wall, screen,
or fence, access to which is controlled by lock and key or other approved
means, are considered to be accessible to qualified persons only. A
wall, screen, or fence less than 8 feet in height is not considered
to prevent access unless it has other features that provide a degree
of isolation equivalent to an 8 foot fence. The entrances to all buildings,
rooms, or enclosures containing exposed live parts or exposed conductors
operating at over 600 volts, nominal, shall be kept locked or shall
be under the observation of a qualified person at all times.
(i) Installations accessible to qualified persons only. Electrical
installations having exposed live parts shall be accessible to qualified
persons only and shall comply with the applicable provisions of (c)
of this subsection.
(ii) Installations accessible to unqualified persons. Electrical
installations that are open to unqualified persons shall be made with
metal-enclosed equipment or shall be enclosed in a vault or in an
area, access to which is controlled by a lock. If metal-enclosed equipment
is installed so that the bottom of the enclosure is less than 8 feet
above the floor, the door or cover shall be kept locked. Metal-enclosed
switchgear, unit substations, transformers, pull boxes, connection
boxes, and other similar associated equipment shall be marked with
appropriate caution signs. If equipment is exposed to physical damage
from vehicular traffic, suitable guards shall be provided to prevent
such damage. Ventilating or similar openings in metal-enclosed equipment
shall be designed so that foreign objects inserted through these openings
will be deflected from energized parts.
(c) Workspace about equipment. Sufficient space shall be provided and
maintained about electric equipment to permit ready and safe operation
and maintenance of such equipment. Where energized parts are exposed,
the minimum clear workspace may not be less than 6 feet 6 inches high
(measured vertically from the floor or platform), or less than 3 feet
wide (measured parallel to the equipment). The depth shall be as required
in Table S-2. The workspace shall be adequate to permit at least a 90-degree
opening of doors or hinged panels.
(i) Working space. The minimum clear working space in front of electric
equipment such as switchboards, control panels, switches, circuit
breakers, motor controllers, relays, and similar equipment may not
be less than specified in Table S-2 unless otherwise specified in
this part. Distances shall be measured from the live parts if they
are exposed, or from the enclosure front or opening if the live parts
are enclosed. However, working space is not required in back of equipment
such as deadfront switchboards or control assemblies where there are
no renewable or adjustable parts (such as fuses or switches) on the
back and where all connections are accessible from locations other
than the back. Where rear access is required to work on deenergized
parts on the back of enclosed equipment, a minimum working space of
30 inches horizontally shall be provided.
TABLE S-2--Minimum Depth of Clear Working Space in
Front of Electric Equipment
| Nominal voltage
to ground |
Conditions2
(ft) |
| |
(a) |
(b) |
(c) |
| 601 to 2,500 |
3 |
4 |
5 |
| 2,501 to 9,000 |
4 |
5 |
6 |
| 9,001 to 25,000 |
5 |
6 |
9 |
| 25,001 to 75kV1 |
6 |
8 |
10 |
| Above 75 kV1 |
8 |
10 |
12 |
1Minimum depth of clear working space in front of electric
equipment with a nominal voltage to ground above 25,000 volts may be the
same as for 25,000 volts under conditions (a), (b) and (c) for installations
built prior to April 16, 1981.
2Conditions (a), (b) and (c) are as follows: (a) Exposed live
parts on one side and no live or grounded parts on the other side of the
working space, or exposed live parts on both sides effectively guarded
by suitable wood or other insulating materials. Insulated wire or insulated
busbars operating at not over 300 volts are not considered live parts.
(b) Exposed live parts on one side and grounded parts on the other side.
Concrete, brick, or tile walls will be considered as grounded surfaces.
(c) Exposed live parts on both sides of the workspace not guarded as provided
in condition (a) with the operator between.
(ii) Illumination. Adequate illumination shall be provided for all
working spaces about electric equipment. The lighting outlets shall
be so arranged that persons changing lamps or making repairs on the
lighting system will not be endangered by live parts or other equipment.
The points of control shall be so located that persons are not likely
to come in contact with any live part or moving part of the equipment
while turning on the lights.
(iii) Elevation of unguarded live parts. Unguarded live parts above
working space shall be maintained at elevations not less than specified
in Table S-3.
TABLE S-3--Elevation of Unguarded Energized Parts Above
Working Space
| Nominal voltage
between phases |
Minimum elevation |
| 601 to 7,500 |
8 feet 6 inches |
| 7,501 to 35,000 |
9 feet |
| Over 35kV |
9 feet + 0.37
inches per kV above 35kV |
Note: Minimum elevation may be 8 feet 0 inches for
installations built prior to April 16, 1981, if the nominal voltage between
phases is in the range of 601-6600 volts.
(d) Entrance and access to workspace. (See WAC
296-24-95603 (2)(c).)
(i) At least one entrance not less than 24 inches wide and 6 feet
6 inches high shall be provided to give access to the working space
about electric equipment. On switchboard and control panels exceeding
48 inches in width, there shall be one entrance at each end of such
board where practicable. Where bare energized parts at any voltage
or insulated energized parts above 600 volts are located adjacent
to such entrance, they shall be suitably guarded.
Permanent ladders or stairways shall be provided to give safe access
to the working space around electric equipment installed on platforms,
balconies, mezzanine floors, or in attic or roof rooms or spaces.
[Statutory Authority: Chapter 49.17 RCW.
94-15-096 (Order 94-07), 296-24-95605, filed 7/20/94, effective 9/20/94;
87-24-051 (Order 87-24), 296-24-95605, filed 11/30/87. Statutory Authority:
RCW 49.17.040 and 49.17.050. 82-08-026 (Order 82-10), 296-24-95605, filed
3/30/82.]
WAC 296-24-95607
Wiring design and protection.
(1) Use and identification of grounded and grounding conductors.
(a) Identification of conductors. A conductor used as a grounded conductor
shall be identifiable and distinguishable from all other conductors.
A conductor used as an equipment grounding conductor shall be identifiable
and distinguishable from all other conductors.
(b) Polarity of connections. No grounded conductor may be attached
to any terminal or lead so as to reverse designated polarity.
(c) Use of grounding terminals and devices. A grounding terminal or
grounding-type device on a receptacle, cord connector, or attachment
plug may not be used for purposes other than grounding.
(2) Outlet devices. Outlet devices shall have an ampere rating not less
than the load to be served.
(3) Outside conductors, 600 volts, nominal, or less. Subdivisions (a),
(b), (c) and (d) of this subsection apply to branch circuit, feeder, and
service conductors rated 600 volts, nominal, or less and run outdoors
as open conductors. Subdivision (e) of this subsection applies to lamps
installed under such conductors.
(a) Conductors on poles. Conductors supported on poles shall provide
a horizontal climbing space not less than the following:
(i) Power conductors below communication conductors--30 inches.
(ii) Power conductors alone or above communication conductors: 300
volts or less--24 inches; more than 300 volts--30 inches.
(iii) Communication conductors below power conductors with power
conductors 300 volts or less--24 inches; more than 300 volts--30 inches.
(b) Clearance from ground. Open conductors shall conform to the following
minimum clearances:
(i) 10 feet--above finished grade, sidewalks, or from any platform
or projection from which they might be reached.
(ii) 12 feet--over areas subject to vehicular traffic other than
truck traffic.
(iii) 15 feet--over areas other than those specified in item (b)(iv)
of this subsection that are subject to truck traffic.
(iv) 18 feet--over public streets, alleys, roads, and driveways.
(c) Clearance from building openings. Conductors shall have a clearance
of at least 3 feet from windows, doors, porches, fire escapes, or similar
locations. Conductors run above the top level of a window are considered
to be out of reach from that window and, therefore, do not have to be
3 feet away.
(d) Clearance over roofs. Conductors shall have a clearance of not
less than 8 feet from the highest point of roofs over which they pass,
except that:
(i) Where the voltage between conductors is 300 volts or less and
the roof has a slope of not less than 4 inches in 12, the clearance
from the roofs shall be at least 3 feet; or
(ii) Where the voltage between conductors is 300 volts or less and
the conductors do not pass over more than 4 feet of the overhang portion
of the roof and they are terminated at a through-the-roof raceway
or approved support, the clearance from the roofs shall be at least
18 inches.
(e) Location of outdoor lamps. Lamps for outdoor lighting shall be
located below all live conductors, transformers, or other electric equipment,
unless such equipment is controlled by a disconnecting means that can
be locked in the open position or unless adequate clearances or other
safeguards are provided for relamping operations.
(4) Services.
(a) Disconnecting means.
(i) General. Means shall be provided to disconnect all conductors
in a building or other structure from the service-entrance conductors.
The disconnecting means shall plainly indicate whether it is in the
open or closed position and shall be installed at a readily accessible
location nearest the point of entrance of the service-entrance conductors.
(ii) Simultaneous opening of poles. Each service disconnecting means
shall simultaneously disconnect all ungrounded conductors.
(b) Services over 600 volts, nominal. The following additional requirements
apply to services over 600 volts, nominal.
(i) Guarding. Service-entrance conductors installed as open wires
shall be guarded to make them accessible only to qualified persons.
(ii) Warning signs. Signs warning of high voltage shall be posted
where other than qualified employees might come in contact with live
parts.
(5) Overcurrent protection. Over 600 volts, nominal. Feeders and branch
circuits over 600 volts, nominal, shall have short-circuit protection.
(6) Grounding. Subdivisions (a) through (g) of this subsection contain
grounding requirements for systems, circuits, and equipment.
(a) Systems to be grounded. The following systems which supply premises
wiring shall be grounded:
(i) All 3-wire DC systems shall have their neutral conductor grounded.
(ii) Two-wire DC systems operating at over 50 volts through 300 volts
between conductors shall be grounded unless:
(A) They supply only industrial equipment in limited areas and
are equipped with a ground detector; or
(B) They are rectifier-derived from an AC system complying with
items (a)(iii), (a)(iv), and (a)(v) of this subsection; or
(C) They are fire-protective signaling circuits having a maximum
current of 0.030 amperes.
(iii) AC circuits of less than 50 volts shall be grounded if they
are installed as overhead conductors outside of buildings or if they
are supplied by transformers and the transformer primary supply system
is ungrounded or exceeds 150 volts to ground.
(iv) AC systems of 50 volts to 1000 volts shall be grounded under
any of the following conditions, unless exempted by item (a)(v) of
this subsection:
(A) If the system can be so grounded that the maximum voltage to
ground on the ungrounded conductors does not exceed 150 volts;
(B) If the system is nominally rated 480Y/277 volt, 3-phase, 4-wire
in which the neutral is used as a circuit conductor;
(C) If the system is nominally rated 240/120 volt, 3-phase, 4-wire
in which the midpoint of one phase is used as a circuit conductor;
or
(D) If a service conductor is uninsulated.
(v) AC systems of 50 volts to 1000 volts are not required to be grounded
under any of the following conditions:
(A) If the system is used exclusively to supply industrial electric
furnaces for melting, refining, tempering, and the like.
(B) If the system is separately derived and is used exclusively
for rectifiers supplying only adjustable speed industrial drives.
(C) If the system is separately derived and is supplied by a transformer
that has a primary voltage rating less than 1000 volts, provided
all of the following conditions are met:
(I) The system is used exclusively for control circuits;
(II) The conditions of maintenance and supervision assure that
only qualified persons will service the installation;
(III) Continuity of control power is required; and
(IV) Ground detectors are installed on the control system.
(D) If the system is an isolated power system that supplies circuits
in health care facilities.
(b) Conductors to be grounded. For AC premises wiring systems the identified
conductor shall be grounded.
(c) Grounding connections.
(i) For a grounded system, a grounding electrode conductor shall
be used to connect both the equipment grounding conductor and the
grounded circuit conductor to the grounding electrode. Both the equipment
grounding conductor and the grounding electrode conductor shall be
connected to the grounded circuit conductor on the supply side of
the service disconnecting means, or on the supply side of the system
disconnecting means or overcurrent devices if the system is separately
derived.
(ii) For an ungrounded service-supplied system, the equipment grounding
conductor shall be connected to the grounding electrode conductor
at the service equipment. For an ungrounded separately derived system,
the equipment grounding conductor shall be connected to the grounding
electrode conductor at, or ahead of, the system disconnecting means
or overcurrent devices.
(iii) On extensions of existing branch circuits which do not have
an equipment grounding conductor, grounding-type receptacles may be
grounded to a grounded cold water pipe near the equipment.
(d) Grounding path. The path to ground from circuits, equipment, and
enclosures shall be permanent and continuous.
(e) Supports, enclosures, and equipment to be grounded.
(i) Supports and enclosures for conductors. Metal cable trays, metal
raceways, and metal enclosures for conductors shall be grounded, except
that:
(A) Metal enclosures such as sleeves that are used to protect cable
assemblies from physical damage need not be grounded; or
(B) Metal enclosures for conductors added to existing installations
of open wire, knob-and-tube wiring, and nonmetallic-sheathed cable
need not be grounded if all of the following conditions are met:
(I) Runs are less than 25 feet;
(II) Enclosures are free from probable contact with ground, grounded
metal, metal laths, or other conductive materials; and
(III) Enclosures are guarded against employee contact.
(ii) Service equipment enclosures. Metal enclosures for service equipment
shall be grounded.
(iii) Frames of ranges and clothes dryers. Frames of electric ranges,
wall-mounted ovens, counter-mounted cooking units, clothes dryers,
and metal outlet or junction boxes which are part of the circuit for
these appliances shall be grounded.
(iv) Fixed equipment. Exposed noncurrent-carrying metal parts of
fixed equipment which may become energized shall be grounded under
any of the following conditions:
(A) If within 8 feet vertically or 5 feet horizontally of ground
or grounded metal objects and subject to employee contact.
(B) If located in a wet or damp location and not isolated.
(C) If in electrical contact with metal.
(D) If in a hazardous (classified) location.
(E) If supplied by a metal-clad, metal-sheathed, or grounded metal
raceway wiring method.
(F) If equipment operates with any terminal at over 150 volts to
the ground; however, the following need not be grounded:
(I) Enclosures for switches or circuit breakers used for other
than service equipment and accessible to qualified persons only;
(II) Metal frames of electrically heated appliances which are
permanently and effectively insulated from ground; and
(III) The cases of distribution apparatus such as transformers
and capacitors mounted on wooden poles at a height exceeding 8
feet above ground or grade level.
(v) Equipment connected by cord and plug. Under any of the conditions
described in subitems (e)(v)(A) through (e)(v)(C) of this subsection,
exposed noncurrent-carrying metal parts of cord-connected and plug-connected
equipment which may become energized shall be grounded.
(A) If in hazardous (classified) locations (see WAC
296-24-95613).
(B) If operated at over 150 volts to ground, except for guarded
motors and metal frames of electrically heated appliances if the
appliance frames are permanently and effectively insulated from
ground.
(C) If the equipment is of the following types:
(I) Refrigerators, freezers, and air conditioners;
(II) Clothes-washing, clothes-drying and dishwashing machines,
sump pumps, and electrical aquarium equipment;
(III) Hand-held motor-operated tools;
(IV) Motor-operated appliances of the following types: Hedge
clippers, lawn mowers, snow blowers, and wet scrubbers;
(V) Cord-connected and plug-connected appliances used in damp
or wet locations or by employees standing on the ground or on
metal floors or working inside of metal tanks or boilers;
(VI) Portable and mobile x-ray and associated equipment;
(VII) Tools likely to be used in wet and conductive locations;
and
(VIII) Portable hand lamps. Tools likely to be used in wet and
conductive locations need not be grounded if supplied through
an isolating transformer with an ungrounded secondary of not over
50 volts. Listed or labeled portable tools and appliances protected
by an approved system of double insulation, or its equivalent,
need not be grounded. If such a system is employed, the equipment
shall be distinctively marked to indicate that the tool or appliance
utilizes an approved system of double insulation.
(vi) Nonelectrical equipment. The metal parts of the following nonelectrical
equipment shall be grounded: Frames and tracks of electrically operated
cranes; frames of nonelectrically driven elevator cars to which electric
conductors are attached; hand operated metal shifting ropes or cables
of electric elevators, and metal partitions, grill work, and similar
metal enclosures around equipment of over 750 volts between conductors.
(f) Methods of grounding fixed equipment.
(i) Noncurrent-carrying metal parts of fixed equipment, if required
to be grounded by this section, shall be grounded by an equipment
grounding conductor which is contained within the same raceway, cable,
or cord, or runs with or encloses the circuit conductors. For DC circuits
only, the equipment grounding conductor may be run separately from
the circuit conductors.
(ii) Electric equipment is considered to be effectively grounded
if it is secured to, and in electrical contact with, a metal rack
or structure that is provided for its support and the metal rack or
structure is grounded by the method specified for the noncurrent-carrying
metal parts of fixed equipment in item (f)(i) of this subsection.
For installations made before May 30, 1982, only, electric equipment
is also considered to be effectively grounded if it is secured to,
and in metallic contact with, the grounded structural metal frame
of a building. Metal car frames supported by metal hoisting cables
attached to or running over metal sheaves or drums of grounded elevator
machines are also considered to be effectively grounded.
(g) Grounding of systems and circuits of 1000 volts and over (high
voltage).
(i) General. If high voltage systems are grounded, they shall comply
with all applicable provisions of subdivisions (a) through (f) of
this subsection as supplemented and modified by the subdivision (g)
of this subsection.
(ii) Grounding of systems supplying portable or mobile equipment.
(See WAC
296-24-95603 (2)(c) and 296-800-280.)
Systems supplying portable or mobile high voltage equipment,
other than substations installed on a temporary basis, shall
comply with the following:
(A) Portable and mobile high voltage equipment shall be supplied
from a system having its neutral grounded through an impedance.
If a delta-connected high voltage system is used to supply the equipment,
a system neutral shall be derived.
(B) Exposed noncurrent-carrying metal parts of portable and mobile
equipment shall be connected by an equipment grounding conductor
to the point at which the system neutral impedance is grounded.
(C) Ground-fault detection and relaying shall be provided to automatically
deenergize any high voltage system component which has developed
a ground fault. The continuity of the equipment grounding conductor
shall be continuously monitored so as to deenergize automatically
the high voltage feeder to the portable equipment upon loss of continuity
of the equipment grounding conductor.
(D) The grounding electrode to which the portable or mobile equipment
system neutral impedance is connected shall be isolated from and
separated in the ground by at least 20 feet from any other system
or equipment grounding electrode, and there shall be no direct connection
between the grounding electrodes, such as buried pipe, fence, etc.
Grounding of equipment. All noncurrent-carrying metal parts of
portable equipment and fixed equipment including their associated
fences, housings, enclosures, and supporting structures shall be
grounded. However, equipment which is guarded by location and isolated
from ground need not be grounded. Additionally, pole-mounted distribution
apparatus at a height exceeding 8 feet above ground or grade level
need not be grounded.
[Statutory Authority: RCW 49.17.010, .040,
.050. 01-11-038 (Order 99-36), § 296-24-95607, filed 05/09/01, effective
09/01/01. Statutory Authority: Chapter 49.17 RCW. 91-24-017 (Order 91-07),
296-24-95607, filed 11/22/91, effective 12/24/91; 87-24-051 (Order 87-24),
296-24-95607, filed 11/30/87. Statutory Authority: RCW 49.17.040 and 49.17.050.
82-08-026 (Order 82-10), 296-24-95607, filed 3/30/82.]
WAC 296-24-95609
Wiring methods, components, and equipment for general use.
(1) Wiring methods. The provisions of this section do not apply to the
conductors that are an integral part of factory-assembled equipment.
(a) General requirements.
(i) Electrical continuity of metal raceways and enclosures. Metal
raceways, cable armor, and other metal enclosures for conductors shall
be metallically joined together into a continuous electric conductor
and shall be so connected to all boxes, fittings, and cabinets as
to provide effective electrical continuity.
(ii) Wiring in ducts. No wiring systems of any type shall be installed
in ducts used to transport dust, loose stock or flammable vapors.
No wiring system of any type may be installed in any duct used for
vapor removal or for ventilation of commercial-type cooking equipment,
or in any shaft containing only such ducts.
(b) Temporary wiring. Temporary electrical power and lighting wiring
methods may be of a class less than would be required for a permanent
installation. Except as specifically modified in this section, all other
requirements of this part for permanent wiring shall apply to temporary
wiring installations.
(i) Uses permitted, 600 volts, nominal or less. Temporary electrical
power and lighting installations 600 volts, nominal, or less may be
used only:
(A) During and for remodeling, maintenance, repair, or demolition
of buildings, structures, or equipment, and similar activities;
(B) For experimental or development work; and
(C) For a period not to exceed 90 days for Christmas decorative
lighting, carnivals, and similar purposes.
(ii) Uses permitted, over 600 volts, nominal. Temporary wiring over
600 volts, nominal, may be used only during periods of tests, experiments,
or emergencies.
(iii) General requirements for temporary wiring.
(A) Feeders shall originate in an approved distribution center.
The conductors shall be run as multiconductor cord or cable assemblies,
or, where not subject to physical damage, they may be run as open
conductors on insulators not more than 10 feet apart.
(B) Branch circuits shall originate in an approved power outlet
or panelboard. Conductors shall be multiconductor cord or cable
assemblies or open conductors. If run as open conductors they shall
be fastened at ceiling height every 10 feet. No branch-circuit conductor
may be laid on the floor. Each branch circuit that supplies receptacles
or fixed equipment shall contain a separate equipment grounding
conductor if run as open conductors.
(C) Receptacles shall be of the grounding type. Unless installed
in a complete metallic raceway, each branch circuit shall contain
a separate equipment grounding conductor and all receptacles shall
be electrically connected to the grounding conductor.
(D) No bare conductors nor earth returns may be used for the wiring
of any temporary circuit.
(E) Suitable disconnecting switches or plug connectors shall be
installed to permit the disconnection of all ungrounded conductors
of each temporary circuit.
(F) Lamps for general illumination shall be protected from accidental
contact or breakage. Protection shall be provided by elevation of
at least 7 feet from normal working surface or by a suitable fixture
or lampholder with a guard.
(G) Flexible cords and cables shall be protected from accidental
damage. Sharp corners and projections shall be avoided. Where passing
through doorways or other pinch points, flexible cords and cables
shall be provided with protection to avoid damage.
(c) Cable trays.
(i) Uses permitted.
(A) Only the following may be installed in cable tray systems:
(I) Mineral-insulated metal-sheathed cable (Type MI);
(II) Armored cable (Type AC);
(III) Metal-clad cable (Type MC);
(IV) Power-limited tray cable (Type PLTC);
(V) Nonmetallic-sheathed cable (Type NM or NMC);
(VI) Shielded nonmetallic-sheathed cable (Type SNM);
(VII) Multiconductor service-entrance cable (Type SE or USE);
(VIII) Multiconductor underground feeder and branch-circuit cable
(Type UF);
(IX) Power and control tray cable (Type TC);
(X) Other factory-assembled, multiconductor control, signal,
or power cables which are specifically approved for installation
in cable trays; or
(XI) Any approved conduit or raceway with its contained conductors.
(B) In industrial establishments only, where conditions of maintenance
and supervision assure that only qualified persons will service
the installed cable tray system, the following cables may also be
installed in ladder, ventilated trough, or 4 inch ventilated channel-type
cable trays:
(I) Single conductor cables which are 250 MCM or larger and are
Types RHH, RHW, MV, USE, or THW, and other 250 MCM or larger single
conductor cables if specifically approved for installation in
cable trays. Where exposed to direct rays of the sun, cables shall
be sunlight-resistant.
(II) Type MV cables, where exposed to direct rays of the sun,
shall be sunlight-resistant.
(C) Cable trays in hazardous (classified) locations shall contain
only the cable types permitted in such locations.
(ii) Uses not permitted. Cable tray systems may not be used in hoistways
or where subjected to severe physical damage.
(d) Open wiring on insulators.
(i) Uses permitted. Open wiring on insulators is only permitted on
systems of 600 volts, nominal, or less for industrial or agricultural
establishments and for services.
(ii) Conductor supports. Conductors shall be rigidly supported on
noncombustible, nonabsorbent insulating materials and may not contact
any other objects.
(iii) Flexible nonmetallic tubing. In dry locations where not exposed
to severe physical damage, conductors may be separately enclosed in
flexible nonmetallic tubing. The tubing shall be in continuous lengths
not exceeding 15 feet and secured to the surface by straps at intervals
not exceeding 4 feet 6 inches.
(iv) Through walls, floors, wood cross members, etc. Open conductors
shall be separated from contact with walls, floors, and wood cross
members, or partitions through which they pass by tubes or bushings
of noncombustible, nonabsorbent insulating material. If the bushing
is shorter than the hole, a waterproof sleeve of nonconductive material
shall be inserted in the hole and an insulating bushing slipped into
the sleeve at each end in such a manner as to keep the conductors
absolutely out of contact with the sleeve. Each conductor shall be
carried through a separate tube or sleeve.
(v) Protection from physical damage. Conductors within 7 feet from
the floor are considered exposed to physical damage. Where open conductors
cross ceiling joints and wall studs and are exposed to physical damage,
they shall be protected.
(2) Cabinets, boxes, and fittings.
(a) Conductors entering boxes, cabinets, or fittings. Conductors entering
boxes, cabinets, or fittings shall be protected from abrasion, and openings
through which conductors enter shall be effectively closed. Unused openings
in cabinets, boxes, and fittings shall also be effectively closed.
(b) Covers and canopies. All pull boxes, junction boxes, and fittings
shall be provided with covers approved for the purpose. If metal covers
are used they shall be grounded. In completed installations each outlet
box shall have a cover, faceplate, or fixture canopy. Covers of outlet
boxes having holes through which flexible cord pendants pass shall be
provided with bushings designed for the purpose or shall have smooth,
well-rounded surfaces on which the cords may bear.
(c) Pull and junction boxes for systems over 600 volts, nominal. In
addition to other requirements in this section for pull and junction
boxes, the following shall apply to these boxes for systems over 600
volts, nominal:
(i) Boxes shall provide a complete enclosure for the contained conductors
or cables.
(ii) Boxes shall be closed by suitable covers securely fastened in
place. Underground box covers that weight over 100 pounds meet this
requirement. Covers for boxes shall be permanently marked "high voltage."
The marking shall be on the outside of the box cover and shall be
readily visible and legible.
(3) Switches.
(a) Knife switches. Single-throw knife switches shall be so connected
that the blades are dead when the switch is in the open position. Single-throw
knife switches shall be so placed that gravity will not tend to close
them. Single-throw knife switches approved for use in the inverted position
shall be provided with a locking device that will ensure that the blades
remain in the open position when so set. Double-throw knife switches
may be mounted so that the throw will be either vertical or horizontal.
However, if the throw is vertical a locking device shall be provided
to ensure that the blades remain in the open position when so set.
(b) Faceplates for flush-mounted snap switches. Flush snap switches
that are mounted in ungrounded metal boxes and located within reach
of conducting floors or other conducting surfaces shall be provided
with faceplates of nonconducting, noncombustible material.
(4) Switchboards and panelboards. Switchboards that have any exposed
live parts shall be located in permanently dry locations and accessible
only to qualified persons. Panelboards shall be mounted in cabinets, cutout
boxes, or enclosures approved for the purpose and shall be dead front.
However, panelboards other than the dead front externally-operable type
are permitted where accessible only to qualified persons. Exposed blades
of knife switches shall be dead when open.
(5) Enclosures for damp or wet locations.
(a) Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures
in damp or wet locations shall be installed so as to prevent moisture
or water from entering and accumulating within the enclosures. In wet
locations the enclosures shall be weatherproof.
(b) Switches, circuit breakers, and switchboards installed in wet locations
shall be enclosed in weatherproof enclosures.
(6) Conductors for general wiring. All conductors used for general wiring
shall be insulated unless otherwise permitted in this section. The conductor
insulation shall be of a type that is approved for the voltage, operating
temperature, and location of use. Insulated conductors shall be distinguishable
by appropriate color or other suitable means as being grounded conductors,
ungrounded conductors, or equipment grounding conductors.
(7) Flexible cords and cables.
(a) Use of flexible cords and cables.
(i) Flexible cords and cables shall be approved and suitable for
conditions of use and location. Flexible cords and cables shall be
used only for:
(A) Pendants;
(B) Wiring of fixtures;
(C) Connection of portable lamps or appliances;
(D) Elevator cables;
(E) Wiring of cranes and hoists;
(F) Connection of stationary equipment to facilitate their frequent
interchange;
(G) Prevention of the transmission of noise or vibration;
(H) Appliances where the fastening means and mechanical connections
are designed to permit removal for maintenance and repair; or
(I) Data processing cables approved as a part of the data processing
system.
(ii) If used as permitted in subitem (a)(i)(C), (a)(i)(F) or (a)(i)(H)
of this subsection, the flexible cord shall be equipped with an attachment
plug and shall be energized from an approved receptacle outlet.
(iii) Unless specifically permitted in item (a)(i) of this subsection,
flexible cords and cables may not be used:
(A) As a substitute for the fixed wiring of a structure;
(B) Where run through holes in walls, ceilings, or floors;
(C) Where run through doorways, windows, or similar openings;
(D) Where attached to building surfaces; or
(E) Where concealed behind building walls, ceilings, or floors.
(iv) Flexible cords used in show windows and showcases shall be Type
S, SO, SJ, SJO, ST, STO, SJT, SJTO, or AFS except for the wiring of
chain-supported lighting fixtures and supply cords for portable lamps
and other merchandise being displayed or exhibited.
(b) Identification, splices, and terminations.
(i) A conductor of a flexible cord or cable that is used as a grounded
conductor or an equipment grounding conductor shall be distinguishable
from other conductors. Types SJ, SJO, SJT, SJTO, S, SO, ST, and STO
shall be durably marked on the surface with the type designation,
size, and number of conductors.
(ii) Flexible cords shall be used only in continuous lengths without
splice or tap. Hard service flexible cords No. 12 or larger may be
repaired if spliced so that the splice retains the insulation, outer
sheath properties, and usage characteristics of the cord being spliced.
(iii) Flexible cords shall be connected to devices and fittings so
that strain relief is provided which will prevent pull from being
directly transmitted to joints or terminal screws.
(8) Portable cables over 600 volts, nominal. Multiconductor portable
cable for use in supplying power to portable or mobile equipment at over
600 volts, nominal, shall consist of No. 8 or larger conductors employing
flexible stranding. Cables operated at over 2,000 volts shall be shielded
for the purpose of confining the voltage stresses to the insulation. Grounding
conductors shall be provided. Connectors for these cables shall be of
a locking type with provisions to prevent their opening or closing while
energized.
Strain relief shall be provided at connections and terminations. Portable
cables may not be operated with splices unless the splices are of the
permanent molded, vulcanized, or other approved type. Termination enclosures
shall be suitably marked with a high voltage hazard warning, and terminations
shall be accessible only to authorized and qualified personnel.
(9) Fixture wires.
(a) General. Fixture wires shall be approved for the voltage, temperature,
and location of use. A fixture wire which is used as a grounded conductor
shall be identified.
(b) Uses permitted. Fixture wires may be used:
(i) For installation in lighting fixtures and in similar equipment
where enclosed or protected and not subject to bending or twisting
in use; or
(ii) For connecting lighting fixtures to the branch-circuit conductors
supplying the fixtures.
(c) Uses not permitted. Fixture wires may not be used as branch-circuit
conductors except as permitted for Class 1 power limited circuits.
(10) Equipment for general use.
(a) Lighting fixtures, lampholders, lamps, and receptacles.
(i) Fixtures, lampholders, lamps, rosettes, and receptacles may have
no live parts normally exposed to employee contact. However, rosettes
and cleat-type lampholders and receptacles located at least 8 feet
above the floor may have exposed parts.
(ii) Handlamps of the portable type supplied through flexible cords
shall be equipped with a handle of molded composition or other material
approved for the purpose, and a substantial guard shall be attached
to the lampholder or the handle.
(iii) Lampholders of the screw-shell type shall be installed for
use as lampholders only. Lampholders installed in wet or damp locations
shall be of the weatherproof type.
(iv) Fixtures installed in wet or damp locations shall be approved
for the purpose and shall be so constructed or installed that water
cannot enter or accumulate in wireways, lampholders, or other electrical
parts.
(b) Receptacles, cord connectors, and attachment plugs (caps).
(i) Receptacles, cord connectors, and attachment plugs shall be constructed
so that no receptacle or cord connector will accept an attachment
plug with a different voltage or current rating than that for which
the device is intended. However, a 20-ampere T-slot receptacle or
cord connector may accept a 15-ampere attachment plug of the same
voltage rating.
(ii) A receptacle installed in a wet or damp location shall be suitable
for the location.
(c) Appliances.
(i) Appliances, other than those in which the current-carrying parts
at high temperatures are necessarily exposed, may have no live parts
normally exposed to employee contact.
(ii) A means shall be provided to disconnect each appliance.
(iii) Each appliance shall be marked with its rating in volts and
amperes or volts and watts.
(d) Motors. This subdivision applies to motors, motor circuits, and
controllers.
(i) In sight from. If specified that one piece of equipment shall
be "in sight from" another piece of equipment, one shall be visible
and not more than 50 feet from the other.
(ii) Disconnecting means.
(A) A disconnecting means shall be located in sight from the controller
location. However, a single disconnecting means may be located adjacent
to a group of coordinated controllers mounted adjacent to each other
or a multimotor continuous process machine. The controller disconnecting
means for motor branch circuits over 600 volts, nominal, may be
out of sight of the controller, if the controller is marked with
a warning label giving the location and identification of the disconnecting
means which is to be locked in the open position.
(B) The disconnecting means shall disconnect the motor and the
controller from all ungrounded supply conductors and shall be so
designed that no pole can be operated independently.
(C) If a motor and the driven machinery are not in sight from the
controller location, the installation shall comply with one of the
following conditions:
(I) The controller disconnecting means shall be capable of being
locked in the open position.
(II) A manually operable switch that will disconnect the motor
from its source of supply shall be placed in sight from the motor
location.
(D) The disconnecting means shall plainly indicate whether it is
in the open (off) or closed (on) position.
(E) The disconnecting means shall be readily accessible. If more
than one disconnect is provided for the same equipment, only one
need be readily accessible.
(F) An individual disconnecting means shall be provided for each
motor, but a single disconnecting means may be used for a group
of motors under any one of the following conditions:
(I) If a number of motors drive special parts of a single machine
or piece of apparatus, such as a metal or woodworking machine,
crane, or hoist;
(II) If a group of motors is under the protection of one set
of branch-circuit protective devices; or
(III) If a group of motors is in a single room in sight from
the location of the disconnecting means.
(iii) Motor overload, short-circuit, and ground-fault protection.
Motors, motor-control apparatus, and motor branch-circuit conductors
shall be protected against overheating due to motor overloads or failure
to start, and against short-circuits or ground faults. These provisions
shall not require overload protection that will stop a motor where
a shutdown is likely to introduce additional or increased hazards,
as in the case of fire pumps, or where continued operation of a motor
is necessary for a safe shutdown of equipment or process and motor
overload sensing devices are connected to a supervised alarm.
(iv) Protection of live parts--all voltages.
(A) Stationary motors having commutators, collectors, and brush
rigging located inside of motor end brackets and not conductively
connected to supply circuits operating at more than 150 volts to
ground need not have such parts guarded. Exposed live parts of motors
and controllers operating at 50 volts or more between terminals
shall be guarded against accidental contact by any of the following:
(I) By installation in a room or enclosure that is accessible
only to qualified persons;
(II) By installation on a suitable balcony, gallery, or platform,
so elevated and arranged as to exclude unqualified persons; or
(III) By elevation 8 feet or more above the floor.
(B) Where live parts of motors or controllers operating at over
150 volts to ground are guarded against accidental contact only
by location, and where adjustment or other attendance may be necessary
during the operation of the apparatus, suitable insulating mats
or platforms shall be provided so that the attendant cannot readily
touch live parts unless standing on the mats or platforms.
(e) Transformers.
(i) The following items cover the installation of all transformers
except the following:
(A) Current transformers;
(B) Dry-type transformers installed as a component part of other
apparatus;
(C) Transformers which are an integral part of an x-ray, high frequency,
or electrostatic-coating apparatus;
(D) Transformers used with Class 2 and Class 3 circuits, sign and
outline lighting, electric discharge lighting, and power-limited
fire-protective signaling circuits; and
(E) Liquid-filled or dry-type transformers used for research, development,
or testing, where effective safeguard arrangements are provided.
(ii) The operating voltage of exposed live parts of transformer installations
shall be indicated by warning signs or visible markings on the equipment
or structure.
(iii) Dry-type, high fire point liquid-insulated, and askarel-insulated
transformers installed indoors and rated over 35kV shall be in a vault.
(iv) If they present a fire hazard to employees, oil-insulated transformers
installed indoors shall be in a vault.
(v) Combustible material, combustible buildings and parts of buildings,
fire escapes, and door and window openings shall be safeguarded from
fires which may originate in oil-insulated transformers attached to
or adjacent to a building or combustible material.
(vi) Transformer vaults shall be constructed so as to contain fire
and combustible liquids within the vault and to prevent unauthorized
access. Locks and latches shall be so arranged that a vault door can
be readily opened from the inside.
(vii) Any pipe or duct system foreign to the vault installation may
not enter or pass through a transformer vault.
(viii) Materials may not be stored in transformer vaults.
(f) Capacitors.
(i) All capacitors, except surge capacitors or capacitors included
as a component part of other apparatus, shall be provided with an
automatic means of draining the stored charge after the capacitor
is disconnected from its source of supply.
(ii) Capacitors rated over 600 volts, nominal, shall comply with
the following additional requirements:
(A) Isolating or disconnecting switches (with no interrupting rating)
shall be interlocked with the load interrupting device or shall
be provided with prominently displayed caution signs to prevent
switching load current.
(B) For series capacitors (see WAC
296-24-95603 (2)(c)), the proper switching shall be
assured by use of at least one of the following:
(I) Mechanically sequenced isolating and bypass switches;
(II) Interlocks; or
(III) Switching procedure prominently displayed at the switching
location.
Storage batteries. Provisions shall be made for sufficient diffusion
and ventilation of gases from storage batteries to prevent the
accumulation of explosive mixtures.
[Statutory Authority: Chapter 49.17 RCW.
94-15-096 (Order 94-07), 296-24-95609, filed 7/20/94, effective 9/20/94;
87-24-051 (Order 87-24), 296-24-95609, filed 11/30/87. Statutory Authority:
RCW 49.17.040 and 49.17.050. 82-08-026 (Order 82-10), 296-24-95609, filed
3/30/82.]
WAC
296-24 Part L Continued
|