|
WAC
296-304-03007 Painting.
All respirators required by this section
must meet the requirements of chapter 296-842
WAC.
(1) Paints mixed with toxic vehicles or solvents.
(a) When employees spray paints mixed with toxic vehicles
or solvents, the employer must ensure that the following conditions
are met:
(i) In confined spaces, employees continuously exposed to
spraying are protected by air line respirators.
(ii) In tanks or compartments, employees continuously exposed
to spraying are protected by air line respirators. Where mechanical
ventilation is provided, employees are protected by respirators.
(iii) In large and well ventilated areas, employees exposed
to spraying are protected by respirators.
(b) The employer must ensure that where employees apply by
brush paints with toxic solvents in confined spaces or other
areas where lack of ventilation creates a hazard, the employees
are protected by filter respirators.
(c) When flammable paints or vehicles are used, precautions
shall be taken in accordance with the requirements of WAC 296-304-03009.
(d) The metallic parts of air moving devices, including fans,
blowers, and jet-type air movers, and all duct work shall be
electrically bonded to the vessel's structure.
(2) Paints and tank coatings dissolved in highly volatile, toxic
and flammable solvents. Several organic coatings, adhesives and
resins are dissolved in highly toxic, flammable and explosive
solvents with flash points below 80°F. Work involving such materials
shall be done only when all of the following special precautions
have been taken:
(a) Sufficient exhaust ventilation shall be provided to keep
the concentration of solvent vapors below ten percent of the
lower explosive limit. Frequent tests shall be made by a competent
person to ascertain the concentration.
(b) If the ventilation fails or if the concentration of solvent
vapors reaches or exceeds ten percent of the lower explosive
limit, painting shall be stopped and the compartment shall be
evacuated until the concentration again falls below ten percent
of the lower explosive limit. If the concentration does not
fall when painting is stopped, additional ventilation to bring
the concentration down to ten percent of the lower explosive
limit shall be provided.
(c) Ventilation shall be continued after the completion of
painting until the space or compartment is gas free. The final
determination as to whether the space or compartment is gas
free shall be made after the ventilating equipment has been
shut off for a least ten minutes.
(d) Exhaust ducts shall discharge clear of working areas and
away from sources of possible ignition. Periodic tests shall
be made to ensure that the exhausted vapors are not accumulating
in other areas within or around the vessel or dry dock.
(e) All motors and control equipment shall be of the explosion-proof
type. Fans shall have nonferrous blades. Portable air ducts
shall also be of nonferrous materials. All motors and associated
control equipment shall be properly maintained and grounded.
(f) Only nonsparking paint buckets, spray guns and tools shall
be used. Metal parts of paint brushes and rollers shall be insulated.
Staging shall be erected in a manner which ensures that it is
nonsparking.
(g) Only explosion proof lights, approved by the Underwriters'
Laboratories for use in Class I, Group D atmospheres, or approved
as permissible by the U.S. Bureau of Mines or the U.S. Coast
Guard, shall be used.
(h) A competent person shall inspect all power and lighting
cables to ensure that the insulation is in excellent condition,
free of all cracks and worn spots, that there are no connections
within fifty feet of the operation, that lines are not overloaded,
and that they are suspended with sufficient slack to prevent
undue stress or chafing.
(i) The face, eyes, head, hands and all other exposed parts
of the bodies of employees handling highly volatile paints must
be protected according to WAC 296-304-090.
All footwear must be nonsparking, such as rubbers, rubber boots
or rubber soled shoes without nails. Coveralls or other outer
clothing must be made of cotton. Rubber gloves, instead of plastic
gloves, must be used to protect against the danger of static
sparks.
(j) No matches, lighted cigarettes, cigars, or pipes, and
no cigarette lighters or ferrous articles shall be taken into
the area where work is being done.
(k) All solvent drums taken into the compartment shall be
placed on nonferrous surfaces and shall be grounded to the vessel.
Metallic contact shall be maintained between containers and
drums when materials are being transferred from one to another.
(l) Spray guns, paint pots, and metallic parts of connecting
tubing shall be electrically bonded, and the bonded assembly
shall be grounded to the vessel.
(m) The employer must ensure that all employees continuously
in a compartment in which such painting is performed, are protected
by air line respirators and by suitable protective clothing.
Employees entering such compartments for a limited time must
be protected by filter cartridge type respirators.
(n) The employer must ensure that all employees doing exterior
paint spraying with such paints are protected by suitable filter
cartridge type respirators and by suitable protective clothing.
[Statutory Authority: RCW 49.17.010,
.040, .050, and .060. 05-03-093 (Order 04-41), § 296-304-03007,
filed 01/18/05, effective 03/01/05. Statutory Authority: RCW 49.17.010,
49.17.040, 49.17.050, and 49.17.060. 03-04-099 (Order 02-31),
§ 296-304-03007, filed 02/04/03, effective 08/01/03. Statutory
Authority: RCW 49.17.040, 49.17.050, 49.17.060; 98-02-006 (Order
96-18), § 296-304-03007, filed 12/26/97, effective 3/1/98; Statutory
Authority: Chapter 49.17 RCW. 95-04-006, § 296-304-03007, filed
1/18/95, effective 3/10/95; 93-19-142 (Order 93-04), § 296-304-03007,
filed 9/22/93, effective 11/1/93; Order 76-7, § 296-304-03007,
filed 3/1/76; Order 74-25, § 296-304-03007, filed 5/7/74.]
WAC
296-304-03009 Flammable liquids.
(1) In all cases when liquid solvents, paint and preservative
removers, paints or vehicles, other than those covered by WAC
296-304-03007(2),
are capable of producing a flammable atmosphere under the conditions
of use the following precautions shall be taken:
(a) Smoking, open flames, arcs and spark-producing equipment
shall be prohibited in the area.
(b) Ventilation shall be provided in sufficient quantities
to keep the concentration of vapors below ten percent of their
lower explosive limit. Frequent tests shall be made by a competent
person to ascertain the concentration.
(c) Scrapings and rags soaked with these materials shall be
kept in a covered metal container.
(d) Only explosion proof lights, approved by the Underwriters'
Laboratories for use in Class I, Group D atmospheres, or approved
as permissible by the U.S. Bureau of Mines or the U.S. Coast
Guard, shall be used.
(e) A competent person shall inspect all power and lighting
cables to ensure that the insulation is in excellent condition,
free of all cracks and worn spots, that there are no connections
within fifty feet of the operation, that lines are not overloaded,
and that they are suspended with sufficient slack to prevent
undue stress or chafing.
Suitable fire extinguishing equipment shall be immediately
available in the work area and shall be maintained in a state
of readiness for instant use.
[Order 74-25, § 296-304-03009,
filed 5/7/74.]
WAC
296-304-040 Welding, cutting and heating-Scope and application.
All sections of this chapter which include WAC 296-304-040
in the section number apply to welding, cutting and heating.
You are also required to protect employees from exposure to
hexavalent chromium during the stainless steel welding process.
See WAC 296-62-08003, Hexavalent chromium for specific criteria.
[Statutory Authority: RCW 49.17.010,
.040, .050, and .060. 06-16-106 (Order 06-13), § 296-304-040,
filed 08/12/04, effective 09/01/06. Statutory Authority: Order
74-25, § 296-304-040, filed 5/7/74.]
WAC
296-304-04001 Ventilation and protection in welding, cutting
and heating.
(1) Mechanical ventilation requirements.
(a) For the purposes of this section, mechanical ventilation
shall meet the following requirements:
(i) Mechanical ventilation shall consist of either general
mechanical ventilation systems or local exhaust systems.
(ii) General mechanical ventilation shall be of sufficient
capacity and so arranged as to produce the number of air changes
necessary to maintain welding fumes and smoke within safe
limits.
(iii) Local exhaust ventilation shall consist of freely
movable hoods intended to be placed by the welder or burner
as close as practicable to the work. This system shall be
of sufficient capacity and so arranged as to remove fumes
and smoke at the source and keep the concentration of them
in the breathing zone within safe limits.
(iv) Contaminated air exhausted from a working space shall
be discharged into the open air or otherwise clear of the
source of intake air.
(v) All air replacing that withdrawn shall be clean and
respirable.
(vi) Oxygen shall not be used for ventilation purposes,
comfort cooling, blowing dust or dirt from clothing, or for
cleaning the work area.
(2) Welding, cutting and heating in confined spaces.
(a) Except as provided in WAC 296-304-04001
(2)(c) and (3)(b), either general mechanical or local exhaust
ventilation meeting the requirements of (1) of this section
shall be provided whenever welding, cutting or heating is performed
in a confined space.
(b) The means of access shall be provided to a confined space
and ventilation ducts to this space shall be arranged in accordance
with WAC 296-304-05011
(2)(a) and (b).
(c) When sufficient ventilation cannot be obtained without
blocking the means of access, employees in the confined space
shall be protected by air line respirators in accordance with
the requirements of chapter 296-842
WAC, and an employee on the outside of such a confined space
shall be assigned to maintain communication with those working
within it and to aid them in an emergency.
(3) Welding, cutting or heating of metals of toxic significance.
(a) Welding, cutting or heating in any enclosed spaces aboard
the vessel involving the metals specified in this subsection
shall be performed with either general mechanical or local exhaust
ventilation meeting the requirements of (1) of this section.
(i) Zinc-bearing base or filler metals or metals coated
with zinc-bearing materials.
(ii) Lead base metals.
(iii) Cadmium-bearing filler materials.
(iv) Chromium-bearing metals or metals coated with chromium-bearing
materials.
(b) Welding, cutting, or heating in any enclosed spaces aboard
the vessel involving the metals specified in this subsection
shall be performed with local exhaust ventilation in accordance
with the requirements of (1) of this section or employees shall
be protected by air line respirators in accordance with the
requirements of chapter 296-842
WAC.
(i) Metals containing lead, other than as an impurity, or
metals coated with lead-bearing materials.
(ii) Cadmium-bearing or cadmium coated base metals.
(iii) Metals coated with mercury-bearing metals.
(iv) Beryllium-containing base or filler metals. Because
of its high toxicity, work involving beryllium shall be done
with both local exhaust ventilation and air line respirators.
(c) Employees performing such operations in the open air shall
be protected by filter type respirators in accordance with the
requirements of WAC
296-304-09003, except that employees performing such operations
on beryllium-containing base or filler metals shall be protected
by air line respirators in accordance with the requirements
of chapter 296-842
WAC.
(d) Other employees exposed to the same atmosphere as the
welders or burners shall be protected in the same manner as
the welder or burner.
(4) Inert-gas metal-arc welding.
(a) Since the inert-gas metal-arc welding process involves
the production of ultraviolet radiation of intensities of 5
to 30 times that produced during shielded metal-arc welding,
the decomposition of chlorinated solvents by ultraviolet rays,
and the liberation of toxic fumes and gases, employees shall
not be permitted to engage in, or be exposed to the process
until the following special precautions have been taken:
(i) The use of chlorinated solvents shall be kept at least
two hundred feet from the exposed arc, and surfaces prepared
with chlorinated solvents shall be thoroughly dry before welding
is permitted on such surfaces.
(ii) Helpers and other employees in the area not protected
from the arc by screening as provided in WAC 296-304-04011(5)
shall be protected by filter lenses meeting the requirements
of Tables I-1A and B (see below). When two or more welders
are exposed to each other's arc, filter lens goggles of a
suitable type meeting the requirements of WAC 296-304-09001
(1) and (3) shall be worn under welding helmets or hand shields
to protect the welder against flashes and radiant energy when
either the helmet is lifted or the shield is removed.
(iii) Welders and other employees who are exposed to radiation
shall be suitably protected so that the skin is covered completely
to prevent burns and other damage by ultraviolet rays. Welding
helmets and hand shields shall be free of leaks and openings,
and free of highly reflective surfaces.
(iv) When inert-gas metal-arc welding is being performed
on stainless steel, the requirements of (3)(b) of this section
shall be met to protect against dangerous concentrations of
nitrogen dioxide.
(5) General welding, cutting and heating.
(a) Welding, cutting and heating not involving conditions
or materials described in (2), (3) or (4) of this section may
normally be done without mechanical ventilation or respiratory
protective equipment, but where, because of unusual physical
or atmospheric conditions, an unsafe accumulation of contaminants
exists, suitable mechanical ventilation or respiratory protective
equipment shall be provided.
(b) Employees performing any type of welding, cutting or heating
shall be protected by suitable eye protective equipment in accordance
with the requirements of Tables I-1A and B (see below)..
(6) Residues and cargos of metallic ores. Residues and cargos
of metallic ores of toxic significance shall be removed from the
area or protected from the heat before welding, cutting or heating
is begun.
TABLE I-1A
FILTER
LENSES FOR PROTECTION AGAINST RADIANT ENERGY
| OPERATIONS |
ELECTRODE
SIZE
1/32 IN |
ARC
CURRENT |
MINIMUM
PROTECTIVE
SHADE |
| |
| Shielder
Metal arc welding |
Less
than 3
3-5
5-8
More
than 8 |
Less
than 60
60-160
160-250
250-550 |
7
8
10
11 |
| |
| Gas
metal arc welding and flux cored arc welding |
|
Less
than 60
60-160
160-250
250-550 |
7
10
10
10 |
| |
| Gas
Tungsten arc welding |
|
Less
than 50
50-150
150-500 |
8
8
10 |
| |
| Air
carbon arc cutting |
(Light)
(Heavy) |
Less
than 500 500-1000 |
10
11 |
| |
| Plasma
arc welding |
|
Less
than 20
20-100
100-400
400-800 |
6
8
10
11 |
| |
| Plasma
arc cutting |
(Light)** (Medium)**
(Heavy)** |
Less
than 300 300-400
400-800 |
8
9
10 |
| |
| Torch
brazing |
--
___ |
--
___ |
3 |
| |
| Torch
soldering |
--
___ |
--
___ |
2 |
| |
| Carbon
arc welding |
--
___ |
--
___ |
14 |
** These values apply where the actual arc is clearly seen.
Lighter filters may be used when the arc is hidden by the workplace.
TABLE
I-1B
FILTER
LENSES FOR PROTECTION AGAINST RADIANT ENERGY
| OPERATIONS |
PLATE
THICKNESS INCHES |
PLATE
THICKNESS
MM |
MINIMUM*
PROTECTIVE
SHADE |
| Gas
welding |
| Light
Medium
Heavy |
Under
1/8
1/8
- 1/2
Over
1/2 |
Under
3.2
3.2
- 12.7
Over
12.7 |
4
5
6 |
| Oxygen
cutting |
| Light
Medium
Heavy |
Under
1
1
- 6
Over
6 |
Under
25
25
- 100
Over
150 |
3
4
5 |
As a rule of thumb, start with a shade that is too dark to see
the weld zone. Then go to a lighter shade which gives sufficient
view of the weld zone without going below the minimum. In oxyfuel
gas welding or cutting where the torch produces a high yellow
light, it is desirable to use a filter lens that absorbs the yellow
or sodium line in the viable light of the (spectrum) operation.
[Statutory Authority: RCW 49.17.010,
.040, .050, and .060. 05-03-093 (Order 04-41), § 296-304-04001,
filed 01/18/05, effective 03/01/05. Statutory Authority: RCW 49.17.010,
49.17.040, 49.17.050, and 49.17.060. 03-04-099 (Order 02-31),
§ 296-304-04001, filed 02/04/03, effective 08/01/03. Statutory
Authority: Chapter 49.17 RCW. 95-04-006, § 296-304-04001, filed
1/18/95, effective 3/10/95; 93-19-142 (Order 93-04), § 296-304-04001,
filed 9/22/93, effective 11/1/93; Order 74-25, § 296-304-04001,
filed 5/7/74.]
WAC
296-304-04003 Fire prevention. (Note:
This section was repealed effective 12/01/05)
WAC
296-304-04005 Welding, cutting and heating in way of preservative
coatings.
(1) Before welding, cutting or heating is commenced on any surface
covered by a preservative coating whose flammability is not known,
a test shall be made by a competent person to determine its flammability.
Preservative coatings shall be considered to be highly flammable
when scrapings burn with extreme rapidity.
(2) Precautions shall be taken to prevent ignition of highly
flammable hardened preservative coatings. When coatings are determined
to be highly flammable they shall be stripped from the area to
be heated to prevent ignition. A 1 1/2-inch or larger fire hose
with fog nozzle, which has been uncoiled and placed under pressure,
shall be immediately available for instant use in the immediate
vicinity, consistent with avoiding freezing of the hose.
(3) Protection against toxic preservative coatings.
(a) In enclosed spaces all surfaces covered with toxic preservatives
shall be stripped of all toxic coatings for a distance of at
least 4 inches from the area of heat application or the employees
shall be protected by air line respirators meeting the requirements
of chapter 296-842
WAC, Respirators.
(b) In the open air employees shall be protected by a filter
type respirator in accordance with the requirements of chapter
296-842
WAC, Respirators.
(4) Before welding, cutting or heating is commenced in enclosed
spaces on metals covered by soft and greasy preservatives, the
following precautions shall be taken:
(a) A competent person shall test the atmosphere in the space
to ensure that it does not contain explosive vapors, since there
is a possibility that some soft and greasy preservatives may
have flash points below temperatures which may be expected to
occur naturally. If such vapors are determined to be present,
no hot work shall be commenced until such precautions have been
taken as will ensure that the welding, cutting or heating can
be performed in safety.
(b) The preservative coatings shall be removed for a sufficient
distance from the area to be heated to ensure that the temperature
of the unstripped metal will not be appreciably raised. Artificial
cooling of the metal surrounding the heated area may be used
to limit the size of the area required to be cleaned. The prohibition
contained in WAC 296-304-03005
(2)(b) shall apply.
(5) Immediately after welding, cutting or heating is commenced
in enclosed spaces on metal covered by soft and greasy preservatives,
and at frequent intervals thereafter, a competent person shall
make tests to ensure that no flammable vapors are being produced
by the coatings. If such vapors are determined to be present,
the operation shall be stopped immediately and shall not be resumed
until such additional precautions have been taken as are necessary
to ensure that the operation can be resumed safely.
[Statutory Authority: RCW 49.17.010,
.040, .050, and .060. 07-03-163 (Order 06-30), § 296-304-04005,
filed 01/24/07, effective 04/01/07. Statutory Authority: Chapter
49.17 RCW. 95-04-006, § 296-304-04005, filed 1/18/95, effective
3/10/95; 93-19-142 (Order 93-04), § 296-304-04005, filed 9/22/93,
effective 11/1/93; Order 74-25, § 296-304-04005, filed 5/7/74.]
WAC
296-304-04007 Welding, cutting and heating of hollow metal
containers and structures not covered by WAC 296-304-02003.
(1) Drums, containers, or hollow structures which have contained
toxic or flammable substances shall, before welding, cutting,
or heating is undertaken on them, either be filled with water
or thoroughly cleaned of such substances and ventilated and tested.
(2) Before heat is applied to a drum, container, or hollow structure,
a vent or opening shall be provided for the release of any built-up
pressure during the application of heat.
(3) Before welding, cutting, heating or brazing is begun on
structural voids such as skegs, bilge keels, fair waters, masts,
booms, support stanchions, pipe stanchions or railings, a competent
person shall inspect the object and, if necessary, test it for
the presence of flammable liquids or vapors. If flammable liquids
or vapors are present, the object shall be made safe.
(4) Objects such as those listed in (3) of this section shall
also be inspected to determine whether water or other nonflammable
liquids are present which, when heated, would build up excessive
pressure. If such liquids are determined to be present, the object
shall be vented, cooled, or otherwise made safe during the application
of heat.
(5) Jacketed vessels shall be vented before and during welding,
cutting or heating operations in order to release any pressure
which may build up during the application of heat.
[Order 76-7, § 296-304-04007,
filed 3/1/76; Order 74-25, § 296-304-04007, filed 5/7/74.]
WAC
296-304-04009 Gas welding and cutting.
(1) Transporting, moving and storing compressed gas cylinders.
(a) Valve protection caps shall be in place and secure. Oil
shall not be used to lubricate protection caps.
(b) When cylinders are hoisted, they shall be secured on a
cradle, slingboard or pallet. They shall not be hoisted by means
of magnets or choker slings.
(c) Cylinders shall be moved by tilting and rolling them on
their bottom edges. They shall not be intentionally dropped,
struck, or permitted to strike each other violently.
(d) When cylinders are transported by vehicle, they shall
be secured in position.
(e) Valve protection caps shall not be used for lifting cylinders
from one vertical position to another. Bars shall not be used
under valves or valve protection caps to pry cylinders loose
when frozen. Warm, not boiling, water shall be used to thaw
cylinders loose.
(f) Unless cylinders are firmly secured on a special carrier
intended for this purpose, regulators shall be removed and valve
protection caps put in place before cylinders are moved.
(g) A suitable cylinder truck, chain, or other steadying device
shall be used to keep cylinders from being knocked over while
in use.
(h) When work is finished, when cylinders are empty or when
cylinders are moved at any time, the cylinder valves shall be
closed.
(i) Acetylene cylinders shall be secured in an upright position
at all times except, if necessary, for short periods of time
while cylinders are actually being hoisted or carried.
(2) Placing cylinders.
(a) Cylinders shall be kept far enough away from the actual
welding or cutting operation so that sparks, hot slag or flame
will not reach them. When this is impractical, fire resistant
shields shall be provided.
(b) Cylinders shall be placed where they cannot become part
of an electrical circuit. Electrodes shall not be struck against
a cylinder to strike an arc.
(c) Fuel gas cylinders shall be placed with valve end up whenever
they are in use. They shall not be placed in a location where
they would be subject to open flame, hot metal, or other sources
of artificial heat.
(d) Cylinders containing oxygen or acetylene or other fuel
gas shall not be taken into confined spaces.
(3) Treatment of cylinders.
(a) Cylinders, whether full or empty, shall not be used as
rollers or supports.
(b) No person other than the gas supplier shall attempt to
mix gases in a cylinder. No one except the owner of the cylinder
or person authorized by him shall refill a cylinder. No one
shall use a cylinder's contents for purposes other than those
intended by the supplier. Only cylinders bearing Interstate
Commerce Commission identification and inspection markings shall
be used.
(c) No damaged or defective cylinder shall be used.
(4) Use of fuel gas. The employer shall thoroughly instruct
employees in the safe use of fuel gas, as follows:
(a) Before connecting a regulator to a cylinder valve, the
valve shall be opened slightly and closed immediately. (This
action is generally termed “cracking” and is intended
to clear the valve of dust or dirt that might otherwise enter
the regulator.) The person cracking the valve shall stand to
one side of the outlet, not in front of it. The valve of a fuel
gas cylinder shall not be cracked where the gas would reach
welding work, sparks, flame or other possible sources of ignition.
(b) The cylinder valve shall always be opened slowly to prevent
damage to the regulator. To permit quick closing, valves on
fuel gas cylinders shall not be opened more than 1 1/2 turns.
When a special wrench is required, it shall be left in position
on the stem of the valve while the cylinder is in use so that
the fuel gas flow can be shut off quickly in case of emergency.
In the case of a manifolded or coupled cylinders, at least one
such wrench shall always be available for immediate use. Nothing
shall be placed on top of a fuel gas cylinder, when in use,
which may damage the safety device or interfere with the quick
closing of the valve.
(c) Fuel gas shall not be used from cylinders through torches
or other devices which are equipped with shut-off valves without
reducing the pressure through a suitable regulator attached
to the cylinder valve or manifold.
(d) Before a regulator is removed from a cylinder valve, the
cylinder valve shall always be closed and the gas released from
the regulator.
(e) If, when the valve on a fuel gas cylinder is opened, there
is found to be a leak around the valve stem, the valve shall
be closed and the gland nut tightened. If this action does not
stop the leak, the use of the cylinder shall be discontinued,
and it shall be properly tagged and removed from the vessel.
In the event that fuel gas should leak from the cylinder valve
rather than from the valve stem and the gas cannot be shut off,
the cylinder shall be properly tagged and removed from the vessel.
If a regulator attached to a cylinder valve will effectively
stop a leak through the valve seat the cylinder need not be
removed from the vessel.
(f) If a leak should develop at a fuse plug or other safety
device, the cylinder shall be removed from the vessel.
(5) Fuel gas and oxygen manifolds.
(a) Fuel gas and oxygen manifolds shall bear the name of the
substance they contain in letters at least one (1) inch high
which shall be either painted on the manifold or on a sign permanently
attached to it.
(b) Fuel gas and oxygen manifolds shall be placed in safe
and accessible locations in the open air. They shall not be
located within enclosed spaces.
(c) Manifold hose connections, including both ends of the
supply hose that lead to the manifold, shall be such that the
hose cannot be interchanged between fuel gas and oxygen manifolds
and supply header connections. Adapters shall not be used to
permit the interchange of hose. Hose connections shall be kept
free of grease and oil.
(d) When not in use, manifold and header hose connections
shall be capped.
(e) Nothing shall be placed on top of a manifold, when in
use, which will damage the manifold or interfere with the quick
closing of the valves.
(6) Hose.
(a) Fuel gas hose and oxygen hose shall be easily distinguishable
from each other. The contrast may be made by different colors
or by surface characteristics readily distinguishable by the
sense of touch. Oxygen and fuel gas hoses shall not be interchangeable.
A single hose having more than one gas passage, a wall failure
of which would permit the flow of one gas into the other gas
passage, shall not be used.
(b) When parallel sections of oxygen and fuel gas hose are
taped together, not more than 4 inches out of 8 inches shall
be covered by tape.
(c) All hose carrying acetylene, oxygen, natural or manufactured
fuel gas, or any gas or substance which may ignite or enter
into combustion or be in any way harmful to employees, shall
be inspected at the beginning of each shift. Defective hose
shall be removed from service.
(d) Hose which has been subjected to flashback or which shows
evidence of severe wear or damage shall be tested to twice the
normal pressure to which it is subject, but in no case less
than two hundred psi. Defective hose or hose in doubtful condition
shall not be used.
(e) Hose couplings shall be of the type that cannot be unlocked
or disconnected by means of a straight pull without rotary motion.
(f) Boxes used for the stowage of gas hose shall be ventilated.
(7) Torches.
(a) Clogged torch tip openings shall be cleaned with suitable
cleaning wires, drills or other devices designed for such purpose.
(b) Torches shall be inspected at the beginning of each shift
for leaking shutoff valves, hose couplings, and tip connections.
Defective torches shall not be used.
(c) Torches shall be lighted by friction lighters or other
approved devices, and not by matches or from hot work.
(8) Pressure regulators. Oxygen and fuel gas pressure regulators
including their related gauges shall be in proper working order
while in use.
[Order 74-25, § 296-304-04009,
filed 5/7/74.]
WAC
296-304-04011 Arc welding and cutting.
(1) Manual electrode holders.
(a) Only manual electrode holders which are specifically designed
for arc welding and cutting and are of a capacity capable of
safely handling the maximum rated current required by the electrodes
shall be used.
(b) Any current carrying parts passing through the portion
of the holder which the arc welder or cutter grips in his hand,
and the outer surfaces of the jaws of the holder, shall be fully
insulated against the maximum voltage encountered to ground.
(2) Welding cables and connectors.
(a) All arc welding and cutting cables shall be of the completely
insulated, flexible type, capable of handling the maximum current
requirements of the work in progress, taking into account the
duty cycle under which the arc welder or cutter is working.
(b) Only cable free from repair or splices for a minimum distance
of ten feet from the cable end to which the electrode holder
is connected shall be used, except that cables with standard
insulated connectors or with splices whose insulating quality
is equal to that of the cable are permitted.
(c) When it becomes necessary to connect or splice lengths
of cable one to another, substantial insulated connectors of
a capacity at least equivalent to that of the cable shall be
used. If connections are effected by means of cable lugs, they
shall be securely fastened together to give good electrical
contact, and the exposed metal parts of the lugs shall be completely
insulated.
(d) Cables in poor repair shall not be used. When a cable,
other than the cable lead referred to in (b), becomes worn to
the extent of exposing bare conductors, the portion thus exposed
shall be protected by means of rubber and friction tapes or
other equivalent insulation.
(3) Ground returns and machine grounding.
(a) A ground return cable shall have a safe current carrying
capacity equal to or exceeding the specified maximum output
capacity of the arc welding or cutting unit which it services.
When a single ground return cable services more than one unit,
its safe current carrying capacity shall equal or exceed the
total specified maximum output capacities of all the units which
it services.
(b) Structures or pipe lines, except pipelines containing
gases or flammable liquids or conduits containing electrical
circuits, may be used as part of the ground return circuit,
provided that the pipe or structure has a current carrying capacity
equal to that required by (2).
(c) When a structure or pipe line is employed as a ground
return circuit, it shall be determined that the required electrical
contact exists at all joints. The generation of an arc, sparks
or heat at any point shall cause rejection of the structure
as a ground circuit.
(d) When a structure or pipe line is continuously employed
as a ground return circuit, all joints shall be bonded, and
periodic inspections shall be conducted to ensure that no condition
of electrolysis or fire hazard exists by virtue of such use.
(e) The frames of all arc welding and cutting machines shall
be grounded either through a third wire in the cable containing
the circuit conductor or through a separate wire which is grounded
at the source of the current. Grounding circuits, other than
by means of the vessel's structure, shall be checked to ensure
that the circuit between the ground and the grounded power conductor
has resistance low enough to permit sufficient current to flow
to cause the fuse or circuit breaker to interrupt the current.
(f) All ground connections shall be inspected to ensure that
they are mechanically strong and electrically adequate for the
required current.
(4) Operating instructions. Employers shall instruct employees
in the safe means of arc welding and cutting as follows:
(a) When electrode holders are to be left unattended, the
electrodes shall be removed and the holders shall be so placed
or protected that they cannot make electrical contact with employees
or conducting objects.
(b) Hot electrode holders shall not be dipped in water, since
to do so may expose the arc welder or cutter to electric shock.
(c) When the arc welder or cutter has occasion to leave his
work or to stop work for any appreciable length of time, or
when the arc welding or cutting machine is to be moved, the
power supply switch to the equipment shall be opened.
(d) Any faulty or defective equipment shall be reported to
the supervisor.
(5) Shielding. Whenever practicable, all arc welding and cutting
operations shall be shielded by noncombustible or flame-proof
screens which will protect employees and other persons working
in the vicinity from the direct rays of the arc.
[Order 74-25, § 296-304-04011,
filed 5/7/74.]
WAC
296-304-04013 Uses of fissionable material in ship-breaking,
shipbuilding and ship repairing.
(1) In ship-breaking, shipbuilding and ship repairing and related
activities involving the use of and exposure to sources of ionizing
radiation not only on conventionally powered but also on nuclear
powered vessels, the applicable provisions of the Atomic Energy
Commission's Standards for Protection Against Radiation (10 CFR
Part 20), relating to protection against occupational radiation
exposure, shall apply.
(2) Any activity which involves the use of radioactive material,
whether or not under license from the Atomic Energy Commission,
shall be performed by competent persons specially trained in the
proper and safe operation of such equipment. In the case of materials
used under commission license, only persons actually licensed,
or competent persons under direction and supervision of the licensee,
shall perform such work.
[Order 76-7, § 296-304-04013,
filed 3/1/76; Order 74-25, § 296-304-04013, filed 5/7/74.]
WAC
296-304-050 Scaffolds, ladders and other working surfaces-Scope
and application.
All sections of this chapter which include WAC 296-304-050
in the section number apply to scaffolds, ladders and other working
surfaces.
[Order 74-25, § 296-304-050,
filed 5/7/74.]
WAC
296-304-05001 Scaffolds or staging.
(1) General requirements.
(a) All scaffolds and their supports whether of lumber, steel
or other material, shall be capable of supporting the load they
are designed to carry with a safety factor of not less than
four.
(b) All lumber used in the construction of scaffolds shall
be spruce, fir, long leaf yellow pine, Oregon pine or wood of
equal strength. The use of hemlock, short leaf yellow pine,
or short fiber lumber is prohibited.
(c) Lumber dimensions as given are nominal except where given
in fractions of an inch.
(d) All lumber used in the construction of scaffolds shall
be sound, straight-grained, free from cross grain, shakes and
large, loose or dead knots. It shall also be free from dry rot,
large checks, worm holes or other defects which impair its strength
or durability.
(e) Scaffolds shall be maintained in a safe and secure condition.
Any component of the scaffold which is broken, burned or otherwise
defective shall be replaced.
(f) Barrels, boxes, cans, loose bricks, or other unstable
objects shall not be used as working platforms or for the support
of planking intended as scaffolds or working platforms.
(g) No scaffold shall be erected, moved, dismantled or altered
except under the supervision of competent persons.
(h) No welding, burning, riveting or open flame work shall
be performed on any staging suspended by means of fiber rope.
(i) Lifting bridles on working platforms suspended from cranes
shall consist of four legs so attached that the stability of
the platform is assured.
(j) Unless the crane hook has a safety latch or is moused,
the lifting bridles on working platforms suspended from cranes
shall be attached by shackles to the lower lifting block or
other positive means shall be taken to prevent them from becoming
accidentally disengaged from the crane hook.
(2) Independent pole wood scaffolds.
(a) All pole uprights shall be set plumb. Poles shall rest
on a foundation of sufficient size and strength to distribute
the load and to prevent displacement.
(b) In light-duty scaffolds not more than 24 feet in height,
poles may be spliced by overlapping the ends not less than 4
feet and securely nailing them together. A substantial cleat
shall be nailed to the lower section to form a support for the
upper section except when bolted connections are used.
(c) All other poles to be spliced shall be squared at the
ends of each splice, abutted, and rigidly fastened together
by not less than two cleats securely nailed or bolted thereto.
Each cleat shall overlap each pole end by at least 24 inches
and shall have a width equal to the face of the pole to which
it is attached. The combined cross sectional area of the cleats
shall be not less than the cross sectional area of the pole.
(d) Ledgers shall extend over two consecutive pole spaces
and shall overlap the poles at each end by not less than 4 inches.
They shall be left in position to brace the poles as the platform
is raised with the progress of the work. Ledgers shall be level
and shall be securely nailed or bolted to each pole and shall
be placed against the inside face of each pole.
(e) All bearers shall be set with their greater dimension
vertical and shall extend beyond the ledgers upon which they
rest.
(f) Diagonal bracing shall be provided between the parallel
poles, and cross bracing shall be provided between the inner
and outer poles or from the outer poles to the ground.
(g) Minimum dimensions and spacing of members shall be in
accordance with Table E-1 in WAC 296-304-07011.
(h) Platform planking shall be in accordance with the requirements
of (8) of this section.
(i) Backrails and toeboards shall be in accordance with the
requirements of (9) of this section.
(3) Independent pole metal scaffolds.
(a) Metal scaffold members shall be maintained in good repair
and free of corrosion.
(b) All vertical and horizontal members shall be fastened
together with a coupler or locking device which will form a
positive connection. The locking device shall be of a type which
has no loose parts.
(c) Posts shall be kept plumb during erection and the scaffold
shall be subsequently kept plumb and rigid by means of adequate
bracing.
(d) Posts shall be fitted with bases supported on a firm foundation
to distribute the load. When wooden sills are used, the bases
shall be fastened thereto.
(e) Bearers shall be located at each set of posts, at each
level, and at each intermediate level where working platforms
are installed.
(f) Tubular bracing shall be applied both lengthwise and crosswise
as required.
(g) Platform planking shall be in accordance with the requirements
of (8) of this section.
(h) Backrails and toeboards shall be in accordance with the
requirements of (9) of this section.
(4) Wood trestle and extension trestle ladders.
(a) The use of trestle ladders, or extension sections or base
sections of extension trestle ladders longer than 20 feet is
prohibited. The total height of base and extension may, however,
be more than 20 feet.
(b) The minimum dimensions of the side rails of the trestle
ladder, or the base sections of the extension trestle ladder,
shall be as follows:
(i) Ladders up to and including those 16 feet long shall
have side rails of not less than 1 5/16 x 2 3/4 inch lumber.
(ii) Ladders over 16 feet long and up to and including those
20 feet long shall have side rails of not less than 1 5/16
x 3 inch lumber.
(c) The side rails of the extension section of the extension
trestle ladder shall be parallel and shall have minimum dimensions
as follows:
(i) Ladders up to and including 12 feet long shall have
side rails of not less than 1 5/16 x 2 1/4 inch lumber.
(ii) Ladders over 12 feet long and up to and including those
16 feet long shall have side rails of not less than 1 5/16
x 2 1/2 inch lumber.
(iii) Ladders over 16 feet long and up to and including
those 20 feet long shall have side rails of not less than
1 5/16 x 3 inch lumber. (Rev. 2-17-76)
(d) Trestle ladders and base sections of extension trestle
ladders shall be so spread that when in an open position the
spread of the trestle at the bottom, inside to inside, shall
be not less than 5 1/2 inches per foot of the length of the
ladder.
(e) The width between the side rails at the bottom of the
trestle ladder or of the base section of the extension trestle
ladder shall be not less than 21 inches for all ladders and
sections 6 feet or less in length. For longer lengths of ladder
the width shall be increased at least 1 inch for each additional
foot of length. The width between the side rails of the extension
section of the trestle ladder shall be not less than 12 inches.
(f) In order to limit spreading, the top ends of the side
rails of both the trestle ladder and of the base section of
the extension trestle ladder shall be beveled, or of equivalent
construction, and shall be provided with a metal hinge.
(g) A metal spreader or locking device to hold the front and
back sections in an open position, and to hold the extension
section securely in the elevated position, shall be a component
of each trestle ladder or extension trestle ladder.
(h) Rungs shall be parallel and level. On the trestle ladder,
or on the base section of the extension trestle ladder, rungs
shall be spaced not less than 8 inches nor more than 18 inches
apart; on the extension section of the extension trestle ladder,
rungs shall be spaced not less than 6 inches nor more than 12
inches apart.
(i) Platform planking shall be in accordance with the requirements
of (8) of this section, except that the width of the platform
planking shall not exceed the distance between the side rails.
(j) Backrails and toeboards shall be in accordance with the
requirements of (9) of this section.
(5) Painters' suspended scaffolds.
(a) The supporting hooks of swinging scaffolds shall be constructed
to be equivalent in strength to mild steel or wrought iron,
shall be forged with care, shall be not less than 7/8 inch in
diameter, and shall be secured to a safe anchorage at all times.
(b) The ropes supporting a swinging scaffold shall be equivalent
in strength to first-grade 3/4 inch diameter manila rope properly
rigged into a set of standard 6 inch blocks consisting of at
least one double and one single block.
(c) Manila and wire ropes shall be carefully examined before
each operation and thereafter as frequently as may be necessary
to ensure their safe condition.
(d) Each end of the scaffold platform shall be supported by
a wrought iron or mild steel stirrup or hanger, which in turn
is supported by the suspension ropes.
(e) Stirrups shall be constructed so as to be equivalent in
strength to wrought iron 3/4 inch in diameter.
(f) The stirrups shall be formed with a horizontal bottom
member to support the platform, shall be provided with means
to support the guardrail and midrail and shall have a loop or
eye at the top for securing the supporting hook on the block.
(g) Two or more swinging scaffolds shall not at any time be
combined into one by bridging the distance between them with
planks or any other form of platform.
(h) No more than two persons shall be permitted to work at
one time on a swinging scaffold built to the minimum specifications
contained in this section. Where heavier construction is used,
the number of persons permitted to work on the scaffold shall
be determined by the size and the safe working load of the scaffold.
(i) Backrails and toeboards shall be in accordance with the
requirements of (9) of this section.
(j) The swinging scaffold platform shall be one of the three
types described in (k), (l), and (m) of this section.
(k) The ladder-type platform consists of boards upon a horizontal
ladder-like structure, referred to herein as the ladder, the
side rails of which are parallel. If this type of platform is
used the following requirements shall be met:
(i) The width between the side rails shall be no more than
20 inches.
(ii) The side rails of ladders in ladder-type platforms
shall be equivalent in strength to a beam of clear straight-grained
spruce of the dimensions contained in Table E-2 in WAC 296-304-07011.
(iii) The side rails shall be tied together with tie rods.
The tie rods shall be not less than 5/16 inch in diameter,
located no more than 5 feet apart, pass through the rails,
and be riveted up tight against washers at both ends.
(iv) The rungs shall be of straight-grained oak, ash, or
hickory, not less than 1 1/8 inches diameter, with 7/8 inch
tenons mortised into the side rails not less than 7/8 inch
and shall be spaced no more than 18 inches on centers.
(v) Flooring strips shall be spaced no more than 5/8 inch
apart except at the side rails, where 1 inch spacing is permissible.
(vi) Flooring strips shall be cleated on their undersides.
(l) The plank-type platform consists of planks supported on
the stirrups or hangers. If this type of platform is used, the
following requirements shall be met:
(i) The planks of plank-type platforms shall be not less
than 2 x 10 inch lumber.
(ii) The platform shall be no more than 24 inches in width.
(iii) The planks shall be tied together by cleats of not
less than 1 x 6 inch lumber, nailed on their undersides at
intervals of not more than 4 feet.
(iv) The planks shall extend not less than 6 inches nor
more than 18 inches beyond the supporting stirrups.
(v) A cleat shall be nailed across the platform on the underside
at each end outside the stirrup to prevent the platform from
slipping off the stirrup.
(vi) Stirrup supports shall be not more than 10 feet apart.
(m) The beam-type platform consists of longitudinal side stringers
with cross beams set on edge and spaced not more than 4 feet
apart on which longitudinal platform planks are laid. If this
type platform is used the following requirements shall be met:
(i) The side stringers shall be of sound, straight-grained
lumber, free from knots, and of not less than 2 x 6 inch lumber,
set on edge.
(ii) The stringers shall be supported on the stirrups with
a clear span between stirrups of not more than 16 feet.
(iii) The stringers shall be bolted to the stirrups by U-bolts
passing around the stirrups and bolted through the stringers
with nuts drawn up tight on the inside face.
(iv) The ends of the stringers shall extend beyond the stirrups
not less than 6 inches nor more than 12 inches at each end
of the platform.
(v) The platform shall be supported on cross beams of 2
x 6 inch lumber between the side stringers securely nailed
thereto and spaced not more than 4 feet on centers.
(vi) The platform shall be not more than 24 inches wide.
(vii) The platform shall be formed of boards 7/8 inch in
thickness by not less than 6 inches in width, nailed tightly
together, and extending to the outside face of the stringers.
(viii) The ends of all platform boards shall rest on the
top of the cross beams, shall be securely nailed, and at no
intermediate points in the length of the platform shall there
by any cantilever ends.
(6) Horse scaffolds.
(a) The minimum dimensions of lumber used in the construction
of horses shall be in accordance with Table E-3 in WAC 296-304-07011.
(b) Horses constructed of materials other than lumber shall
provide the strength, rigidity and security required of horses
constructed of lumber.
(c) The lateral spread of the legs shall be equal to not less
than one-third of the height of the horse.
(d) All horses shall be kept in good repair, and shall be
properly secured when used in staging or in locations where
they may be insecure.
(e) Platform planking shall be in accordance with the requirements
of (8) of this section.
(f) Backrails and toeboards shall be in accordance with (9)
of this section.
(7) Other types of scaffolds.
(a) Scaffolds of a type for which specifications are not contained
in this section shall meet the general requirements of (1),
(8) and (9) of this section, shall be in accordance with recognized
principles of design and shall be constructed in accordance
with accepted standards covering such equipment.
(8) Scaffold or platform planking.
(a) Except as otherwise provided in (5)(k) and (m), platform
planking shall be of not less than 2 x 10 inch lumber. Platform
planking shall be straight-grained and free from large or loose
knots and may be either rough or dressed.
(b) Platforms of staging shall be not less than two 10 inch
planks in width except in such cases as the structure of the
vessel or the width of the trestle ladders make it impossible
to provide such a width.
(c) Platform planking shall project beyond the supporting
members at either end by at least 6 inches but in no case shall
project more than 12 inches unless the planks are fastened to
the supporting members.
(d) Table E-4 in WAC 296-304-07011
shall be used as a guide in determining safe loads for scaffold
planks.
(9) Backrails and toeboards.
(a) Scaffolding, staging, runways, or working platforms which
are supported or suspended more than 5 feet above a solid surface,
or at any distance above the water, shall be provided with a
railing which has a top rail whose upper surface is from 42
to 45 inches above the upper surface of the staging, platform,
or runway and a midrail located half way between the upper rail
and the staging, platform, or runway.
(b) Rails shall be of 2 x 4 inch lumber, flat bar or pipe.
When used with rigid supports, taut wire or fiber rope of adequate
strength may be used. If the distance between supports is more
than 8 feet, rails shall be equivalent in strength to 2 x 4
inch lumber. Rails shall be firmly secured. Where exposed to
hot work or chemicals, fiber rope rails shall not be used.
(c) Rails may be omitted where the structure of the vessel
prevents their use. When rails are omitted employees working
more than 5 feet above solid surfaces shall be protected by
safety belts and life lines meeting the requirements of WAC
296-304-09021(2),
and employees working over water shall be protected by personal
flotation devices meeting the requirements of WAC 296-304-09017(1).
(d) Employees working from swinging scaffolds which are triced
out of a vertical line below their supports or from scaffolds
on paint floats subject to surging, shall be protected against
falling toward the vessel by a railing or a safety belt and
line attached to the backrail.
(e) When necessary, to prevent tools and materials from falling
on men below, toeboards of not less than 1 x 4 inch lumber shall
be provided.
(10) Access to staging.
(a) Access from below to staging more than 5 feet above a
floor, deck or the ground shall consist of well secured stairways,
cleated ramps, fixed or portable ladders meeting the applicable
requirements of WAC 296-304-05003
or rigid type noncollapsible trestles with parallel and level
rungs.
(b) Ramps and stairways shall be provided with 36-inch handrails
with midrails.
(c) Ladders shall be so located or other means shall be taken
so that it is not necessary for employees to step more than
one foot from the ladder to any intermediate landing or platform.
(d) Ladders forming integral parts of prefabricated staging
are deemed to meet the requirements of these regulations.
(e) Access from above to staging more than 3 feet below the
point of access shall consist of a straight, portable ladder
meeting the applicable requirements of WAC
296-304-05003 or a Jacob's ladder properly secured, meeting
the requirements of WAC 296-304-05007(4).
[Statutory Authority: RCW 49.17.010,
49.17.040, 49.17.050, and 49.17.060. 03-04-099 (Order 02-31),
§ 296-304-05001, filed 02/04/03, effective 08/01/03. Order
76-7, § 296-304-05001, filed 3/1/76; Order 74-25, § 296-304-05001,
filed 5/7/74.]
WAC
296-304-05003 Ladders.
(1) General requirements.
(a) The use of ladders with broken or missing rungs or steps,
broken or split side rails, or other faulty or defective construction
is prohibited. When ladders with such defects are discovered,
they shall be immediately withdrawn from service. Inspection
of metal ladders shall include checking for corrosion of interiors
of open end, hollow rungs.
(b) When sections of ladders are spliced, the ends shall be
abutted, and not fewer than 2 cleats shall be securely nailed
or bolted to each rail. The combined cross sectional area of
the cleats shall be not less than the cross sectional area of
the side rail. The dimensions of side rails for their total
length shall be those specified in (2) or (3) of this section.
(c) Portable ladders shall be lashed, blocked or otherwise
secured to prevent their being displaced. The side rails of
ladders used for access to any level shall extend not less than
36 inches above that level. When this is not practical, grab
rails which will provide a secure grip for an employee moving
to or from the point of access shall be installed.
(d) Portable metal ladders shall be of strength equivalent
to that of wood ladders. Manufactured portable metal ladders
provided by the employer shall be in accordance with the provisions
of the United States of America Standard Safety Code for Portable
Metal Ladders, A14.2-1972.
(e) Portable metal ladders shall not be used near electrical
conductors nor for electric arc welding operations.
(f) Manufactured portable wood ladders provided by the employer
shall be in accordance with the provisions of the United States
of America Standard Safety Code for Portable Wood Ladders, A-14-1-1968.
(2) Construction of portable wood cleated ladders up to 30 feet
in length.
(a) Wood side rails shall be made from west coast hemlock,
eastern spruce, Sitka spruce, or wood of equivalent strength.
Material shall be seasoned, straight-grained wood, and free
from shakes, checks, decay or other defects which will impair
its strength. The use of low density woods is prohibited.
(b) Side rails shall be dressed on all sides, and kept free
of splinters.
(c) All knots shall be sound and hard. The use of material
containing loose knots is prohibited. Knots shall not appear
on the narrow face of the rail and, when in the side face, shall
be not more than 1/2 inch in diameter or within 1/2 inch of
the edge of the rail or nearer than 3 inches to a tread or rung.
(d) Pitch pockets not exceeding 1/8 inch in width, 2 inches
in length and 1/2 inch in depth are permissible in wood side
rails, provided that not more than one such pocket appears in
each 4 feet of length.
(e) The width between side rails at the base shall be not
less than 11 1/2 inches for ladders 10 feet or less in length.
For longer ladders this width shall be increased at least 1/4
inch for each additional 2 feet in length.
(f) Side rails shall be at least 1 5/8 x 3 5/8 inches in cross
section.
(g) Cleats (meaning rungs rectangular in cross section with
the wide dimension parallel to the rails) shall be of the material
used for side rails, straight-grained and free from knots. Cleats
shall be mortised into the edges of the side rails 1/2 inch,
or filler blocks shall be used on the rails between the cleats.
The cleats shall be secured to each rail with three 10d common
wire nails or fastened with through bolts or other fasteners
of equivalent strength. Cleats shall be uniformly spaced not
more than 12 inches apart.
(h) Cleats 20 inches or less in length shall be at least 25/32
x 3 inches in cross section. Cleats over 20 inches but not more
than 30 inches in length shall be at least 25/32 x 3 3/4 inches
in cross section.
(3) Construction of portable wood cleated ladders from 30 to
60 feet in length.
(a) Ladders from 30 to 60 feet in length shall be in accordance
with the specifications of (2) of this section with the following
exceptions:
(i) Rails shall be of not less than 2 x 6 inch lumber.
(ii) Cleats shall be of not less than 1 x 4 inch lumber.
(iii) Cleats shall be nailed to each rail with five 10d
common wire nails or fastened with through bolts or other
fastenings of equivalent strength.
[Statutory Authority: RCW 49.17.010,
.040, .050, and .060. 07-03-163 (Order 06-30), § 296-304-05003,
filed 01/24/07, effective 04/01/07. Statutory Authority: RCW 49.17.010,
49.17.040, 49.17.050, and 49.17.060. 03-04-099 (Order 02-31),
§ 296-304-05003, filed 02/04/03, effective 08/01/03. Order
74-25, § 296-304-05003, filed 5/7/74.]
WAC
296-304-05005 Guarding of deck openings and edges.
(1) When employees are working in the vicinity of flush manholes
and other small openings of comparable size in the deck and other
working surfaces, such openings shall be suitably covered or guarded
to a height of not less than 30 inches, except where the use of
such guards is made impracticable by the work actually in progress.
(2) When employees are working around open hatches not protected
by coamings to a height of 24 inches or around other large openings,
the edge of the opening shall be guarded in the working area to
a height of 36 to 42 inches, except where the use of such guards
is made impracticable by the work actually in progress.
(3) When employees are exposed to unguarded edges of decks,
platforms, flats, and similar flat surfaces, more than 5 feet
above a solid surface, the edges shall be guarded by adequate
guardrails meeting the requirements of WAC 296-304-05001
(9)(a) and (b), unless the nature of the work in progress or the
physical conditions prohibit the use or installation of such guardrails.
(4) When employees are working near the unguarded edges of decks
of vessels afloat, they shall be protected by buoyant personal
flotation devices, meeting the requirements of WAC 296-304-09017(1).
(5) Sections of bilges from which floor plates or gratings have
been removed shall be guarded by guardrails except where they
would interfere with work in progress. If these open sections
are in a walkway at least two 10-inch planks placed side by side,
or equivalent, shall be laid across the opening to provide a safe
walking surface.
(6) Gratings, walkways, and catwalks, from which sections or
ladders have been removed, shall be barricaded with adequate guardrails.
[Statutory Authority: RCW 49.17.010,
.040, .050, and .060. 07-03-163 (Order 06-30), § 296-304-05005,
filed 01/24/07, effective 04/01/07. Statutory Authority: RCW 49.17.010,
49.17.040, 49.17.050, and 49.17.060. 03-04-099 (Order 02-31),
§ 296-304-05005, filed 02/04/03, effective 08/01/03. Order
74-25, § 296-304-05005, filed 5/7/74.]
WAC
296-304-05007 Access to vessels.
“Barge” - An unpowered, flat bottom, shallow
draft vessel including scows, carfloats and lighters, but not
ship-shaped or deep-draft barges.
“River towboat” - A shallow draft, low free
board, self-propelled vessel designed to tow river barges by pushing
ahead.
(1) Access to vessels afloat. The employer shall not permit
employees to board or leave any vessel, except a barge or river
towboat, until the following requirements have been met:
(a) Whenever practicable, a gangway of not less than 20 inches
walking surface, of adequate strength, maintained in safe repair
and safely secured shall be used. If a gangway is not practicable,
a substantial straight ladder, extending at least 36 inches
above the upper landing surface and adequately secured against
shifting or slipping shall be provided. When conditions are
such that neither a gangway nor a straight ladder can be used,
a Jacob's ladder meeting the requirements of (4)(a) and (b)
of this section may be used.
(b) Each side of such gangway, and the turntable if used,
shall have a railing with a minimum height of approximately
33 inches measured perpendicularly from rail to walking surface
at the stanchion, with a midrail. Rails shall be of wood, pipe,
chain, wire or rope and shall be kept taut at all times.
(c) Gangways on vessels inspected and certificated by the
U.S. Coast Guard are deemed to meet the foregoing requirements,
except in cases where the vessel's regular gangway is not being
used.
(d) The gangway shall be kept properly trimmed at all times.
(e) When a fixed tread accommodation ladder is used, and the
angle is low enough to require employees to walk on the edge
of the treads, cleated duckboards shall be laid over and secured
to the ladder.
(f) When the lower end of a gangway overhangs the water between
the ship and the dock in such a manner that there is danger
of employees falling between the ship and the dock, a net or
other suitable protection shall be rigged at the foot of the
gangway in such a manner as to prevent employees from falling
from the end of the gangway.
(g) If the foot of the gangway is more than one foot away
from the edge of the apron, the space between them shall be
bridged by a firm walkway equipped with railings, with a minimum
height of approximately 33 inches with midrails on both sides.
(h) Supporting bridles shall be kept clear so as to permit
unobstructed passage for employees using the gangway.
(i) When the upper end of the means of access rests on or
flush with the top of the bulwark, substantial steps properly
secured and equipped with at least one substantial handrail
approximately 33 inches in height shall be provided between
the top of the bulwark and the deck.
(j) Obstructions shall not be laid on or across the gangway.
(k) The means of access shall be adequately illuminated for
its full length.
(l) Unless the construction of the vessel makes it impossible,
the means of access shall be so located that drafts of cargo
do not pass over it. In any event loads shall not be passed
over the means of access while employees are on it.
(2) Access to vessels in drydock or between vessels. Gangways
meeting the requirements of (1)(a), (b), (i), (j) and (l) of this
section shall be provided for access from wing wall to vessel
or, when two or more vessels, other than barges or river towboats,
are lying abreast, from one vessel to another.
(3) Access to barges and river towboats.
(a) Ramps for access of vehicles to or between barges shall
be of adequate strength, provided with side boards, well maintained
and properly secured.
(b) Unless employees can step safely to or from the wharf,
float, barge, or river towboat, either a ramp in accordance
with the requirements of (a) of this section or a safe walkway
in accordance with the requirements of (1)(g) of this section
shall be provided. When a walkway is impracticable, a substantial
straight ladder, extending at least 36 inches above the upper
landing surface and adequately secured against shifting or slipping
shall be provided. When conditions are such that neither a walkway
nor a straight ladder can be used, a Jacob's ladder in accordance
with the requirements of (4) of this section may be used.
(c) The means of access shall be in accordance with the requirements
of (1)(i), (j) and (k) of this section.
(4) Jacob's ladders.
(a) Jacob's ladders shall be of the double rung or flat tread
type. They shall be well maintained and properly secured.
(b) A Jacob's ladder shall either hang without slack from
its lashings or be pulled up entirely.
[Statutory Authority: RCW 49.17.040,
49.17.050, 49.17.060; 98-02-006 (Order 96-18), § 296-304-05007,
filed 12/26/97, effective 3/1/98; Order 74-25, § 296-304-05007,
filed 5/7/74.]
WAC
296-304-05009 Access to and guarding of dry docks and marine
railways..
(1) A gangway, ramp or permanent stairway of not less than 20
inches walking surface, of adequate strength, maintained in safe
repair and securely fastened, shall be provided between a floating
dry dock and the pier or bulkhead.
(2) Each side of such gangway, ramp or permanent stairway, including
those which are used for access to wing walls from dry dock floors,
shall have a railing with a midrail. Such railings on gangways
or ramps shall be approximately 42 inches in height; and railings
on permanent stairways shall be not less than approximately 30
or more than approximately 34 inches in height. Rails shall be
of wood, pipe, chain, wire, or rope and shall be kept taut at
all times.
(3) Railings meeting the requirements of (2) of this section
shall be provided on the means of access to and from the floors
of graving docks.
(4) Railings approximately 42 inches in height, with a midrail,
shall be provided on the edges of wing walls of floating dry docks
and on the edges of graving docks. Sections of the railings may
be temporarily removed where necessary to permit line handling
while a vessel is entering or leaving the dock.
(5) When employees are working on the floor of a floating dry
dock where they are exposed to the hazard of falling into the
water, the end of the dry dock shall be equipped with portable
stanchions and 42 inch railings with a midrail. When such a railing
would be impracticable or ineffective, other effective means shall
be provided to prevent employees from falling into the water.
(6) Access to wingwalls from floors of dry docks shall be by
ramps, permanent stairways or ladders meeting the applicable requirements
of WAC 296-304-05003.
(7) Catwalks on stiles of marine railways shall be no less than
20 inches wide and shall have on at least one side a guardrail
and midrail meeting the requirements of WAC 296-304-05001
(9)(a) and (b).
[Statutory Authority: RCW 49.17.010,
49.17.040, 49.17.050, and 49.17.060. 03-04-099 (Order 02-31),
§ 296-304-05009, filed 02/04/03, effective 08/01/03. Order
74-25, § 296-304-05009, filed 5/7/74.]
WAC
296-304-05011 Access to cargo spaces and confined spaces.
(1) Cargo spaces.
(a) There shall be at least one safe and accessible ladder
in any cargo space which employees must enter.
(b) When any fixed ladder is visibly unsafe, the employer
shall prohibit its use by employees.
(c) Straight ladders of adequate strength and suitably secured
against shifting or slipping shall be provided as necessary
when fixed ladders in cargo spaces do not meet the requirements
of (a) of this section. When conditions are such that a straight
ladder cannot be used, a Jacob's ladder meeting the requirements
of WAC 296-304-05007(4)
may be used.
(d) When cargo is stowed within 4 inches of the back of ladder
rungs, the ladder shall be deemed “unsafe” for the
purpose of this section.
(e) Fixed ladders or straight ladders provided for access
to cargo spaces shall not be used at the same time that cargo
drafts or other loads are entering or leaving the hold. Before
using these ladders to enter or leave the hold, the employee
shall be required to inform the winchman or crane signalman
of his intention.
(2) Confined spaces.
(a) More than one means of access shall be provided to a confined
space in which employees are working and in which the work may
generate a hazardous atmosphere in the space except where the
structure or arrangement of the vessel makes this provision
impractical.
(b) When the ventilation ducts required by these regulations
must pass through these means of access, the ducts shall be
of such a type and so arranged as to permit free passage of
an employee through at least two of these means of access.
[Order 74-25, § 296-304-05011,
filed 5/7/74.]
WAC
296-304-05013 Working surfaces.
(1) When firebox floors present tripping hazards of exposed
tubing or of missing or removed refractory, sufficient planking
to afford safe footing shall be laid while work is being carried
on within the boiler.
(2) The employer must provide and ensure the use of fall protection
when employees work aloft or elsewhere at elevations more than
5 feet above a solid surface.
(a) Employees must be protected by the use of scaffolds, ladders,
or personal protection equipment according to WAC
296-304-09021, or 296-304-09023.
(b) Employees must work from scaffolds when visually restricted
by:
-
Blasting hoods;
-
Welding helmets;
and
-
Burning goggles;
except
-
For the initial and final welding or burning operation to
start or complete a job such as the erection and dismantling
of hung scaffolding; or
-
Other similar, nonrepetitive jobs
of brief duration.
(3) For work performed in restricted quarters, such as behind
boilers and in between congested machinery units and piping, work
platforms at least 20 inches wide meeting the requirements of
WAC 296-304-05001
(8)(b) shall be used. Backrails may be omitted if bulkheading,
boilers, machinery units, or piping afford proper protection against
falling.
(4) When employees are boarding, leaving, or working from small
boats or floats, they shall be protected by personal flotation
devices meeting the requirements of WAC
296-304-09017(1).
[Statutory Authority: RCW 49.17.010,
49.17.040, 49.17.050, and 49.17.060. 03-04-099 (Order 02-31),
§ 296-304-05013, filed 02/04/03, effective 08/01/03. Statutory
Authority: RCW 49.17.040, 49.17.050, 49.17.060; 98-02-006 (Order
96-18) § 296-304-05013, filed 12/26/97, effective 3/1/98; Order
76-7, § 296-304-05013, filed 3/1/76; Order 74-25, § 296-304-05013,
filed 5/7/74.]
WAC
296-304-060 General working conditions-Scope and application.
All sections of this chapter which include WAC 296-304-060
in the section number apply to general working conditions.
[Order 74-25, § 296-304-060,
filed 5/7/74.]
WAC
296-304-06001 Housekeeping.
(1) Good housekeeping conditions shall be maintained at all
times. Adequate aisles and passageways shall be maintained in
all work areas. All staging platforms, ramps, stairways, walkways,
aisles, and passageways on vessels or dry docks shall be kept
clear of all tools, materials, and equipment except that which
is in use, and all debris such as welding rod tips, bolts, nuts,
and similar material. Hose and electric conductors shall be elevated
over or placed under the walkway or working surfaces or covered
by adequate crossover planks.
(2) All working areas on vessels and dry docks shall be kept
reasonably free of debris, and construction material shall be
so piled as not to present a hazard to employees.
(3) Slippery conditions on walkways or working surfaces shall
be eliminated as they occur.
(4) Free access shall be maintained at all times to all exits
and to all fire-alarm boxes or fire-extinguishing equipment.
(5) All oils, paints, thinners, solvents waste, rags, or other
flammable substances shall be kept in fire resistant covered containers
when not in use.
[Order 74-25, § 296-304-06001,
filed 5/7/74.]
WAC
296-304-06003 Illumination.
(1) All means of access and walkways leading to working areas
as well as the working areas themselves shall be adequately illuminated.
(2) Temporary lights shall meet the following requirements:
(a) Temporary lights shall be equipped with guards to prevent
accidental contact with the bulb, except that guards are not
required when the construction of the reflector is such that
the bulb is deeply recessed.
(b) Temporary lights shall be equipped with heavy duty electric
cords with connections and insulation maintained in safe condition.
Temporary lights shall not be suspended by their electric cords
unless cords and lights are designed for this means of suspension.
Splices which have insulation equal to that of the cable are
permitted.
(c) Cords shall be kept clear of working spaces and walkways
or other locations in which they are readily exposed to damage.
(3) Exposed noncurrent-carrying metal parts of temporary lights
furnished by the employer shall be grounded either through a third
wire in the cable containing the circuit conductors or through
a separate wire which is grounded at the source of the current.
Grounding shall be in accordance with the requirements of WAC
296-304-08003(2).
(4) Where temporary lighting from sources outside the vessel
is the only means of illumination, portable emergency lighting
equipment shall be available to provide illumination for safe
movement of employees.
(5) Employees shall not be permitted to enter dark spaces without
a suitable portable light. The use of matches and open flame lights
is prohibited. In nongas free spaces, portable lights shall meet
the requirements of WAC 296-304-02005(2)(i).
(6) Temporary lighting stringers or streamers shall be so arranged
as to avoid overloading of branch circuits. Each branch circuit
shall be equipped with overcurrent protection of capacity not
exceeding the rated current carrying capacity of the cord used.
[Statutory Authority: RCW 49.17.010,
49.17.040, 49.17.050, and 49.17.060. 03-04-099 (Order 02-31),
§ 296-304-06003, filed 02/04/03, effective 08/01/03. Order
74-25, § 296-304-06003, filed 5/7/74.]
WAC
296-304-06005 Utilities.
(1) Steam supply and hoses.
(a) Prior to supplying a vessel with steam from a source outside
the vessel, the employer shall ascertain from responsible vessel's
representatives, having knowledge of the condition of the plant,
the safe working pressure of the vessel's steam system. The
employer shall install a pressure gauge and a relief valve of
proper size and capacity at the point where the temporary steam
hose joins the vessel's steam piping system or systems. The
relief valve shall be set and capable of relieving at a pressure
not exceeding the safe working pressure of the vessel's system
in its present condition, and there shall be no means of isolating
the relief valve from the system which it protects. The pressure
gauge and relief valve shall be located so as to be visible
and readily accessible.
(b) Steam hose and fittings shall have a safety factor of
not less than five.
(c) When steam hose is hung in a bight or bights, the weight
shall be relieved by appropriate lines. The hose shall be protected
against chafing.
(d) Steam hose shall be protected from damage and hose and
temporary piping shall be so shielded where passing through
normal work areas as to prevent accidental contact by employees.
(2) Electric power.
(a) When the vessel is supplied with electric power from a
source outside the vessel, the following precautions shall be
taken prior to energizing the vessel's circuits:
(i) If in dry dock, the vessel shall be adequately grounded.
(ii) The employer shall ascertain from responsible vessel's
representatives, having a knowledge of the condition of the
vessel's electrical system, that all circuits to be energized
are in a safe condition.
(iii) All circuits to be energized shall be equipped with
overcurrent protection of capacity not exceeding the rated
current carrying capacity of the cord used.
(3) Infrared electrical heat lamps.
(a) All infrared electrical heat lamps shall be equipped with
guards that surround the lamps with the exception of the face,
to minimize accidental contact with the lamps.
[Order 74-25, § 296-304-06005,
filed 5/7/74.]
WAC
296-304-06007 Work in confined or isolated spaces.
When any work is performed in a confined space, except as provided
in WAC 296-304-04001
(2)(c), or when an employee is working alone in an isolated location,
frequent checks shall be made to ensure the safety of the employees.
[Order 74-25, § 296-304-06007,
filed 5/7/74.]
WAC
296-304-06009 Work on or in the vicinity of radar and radio.
(1) No employees other than radar or radio repairmen shall be
permitted to work on masts, king posts or other aloft areas unless
the radar and radio are secured or otherwise made incapable of
radiation. In either event, the radio and radar shall be appropriately
tagged.
(2) Testing of radar or radio shall not be done until the employer
can schedule such tests at a time when no work is in progress
aloft or personnel can be cleared from the danger area according
to minimum safe distances established for and based on the type,
model, and power of the equipment.
[Order 74-25, § 296-304-06009,
filed 5/7/74.]
WAC
296-304-06011 Work in or on lifeboats.
(1) Before employees are permitted to work in or on a lifeboat,
either stowed or in a suspended position, the employer shall ensure
that the boat is secured independently of the releasing gear to
prevent the boat from falling due to accidental tripping of the
releasing gear and movement of the davits or capsizing of a boat
in chocks.
(2) Employees shall not be permitted to remain in boats while
the boats are being hoisted into final stowed position.
(3) Employees shall not be permitted to work on the outboard
side of lifeboats stowed on their chocks unless the boats are
secured by gripes or otherwise secured to prevent them from swinging
outboard.
[Order 74-25, § 296-304-06011,
filed 5/7/74.]
WAC
296-304-06013 Health and sanitation.
“Hazardous material” - A material with one
or more of the following characteristics:
-
Has a flash point
below 140°F, closed cup, or is subject to spontaneous heating;
-
Has a threshold
limit value below 500 p.p.m. in the case of a gas or vapor,
below 500 mg./m.3 for fumes, and below 25 m.p.p.c.f. in case
of a dust;
-
Has a single dose
oral LD50 below 500 mg./kg.;
-
Is subject to polymerization
with the release of large amounts of energy;
-
Is a strong oxidizing
or reducing agent;
-
Causes first degree
burns to skin in short time exposure, or is systematically
toxic by skin contact; or
-
In the course of
normal operations, may produce dusts, gases, fumes, vapors,
mists, or smokes that have one or more of the above characteristics.
(1) No chemical product, such as a solvent or preservative;
no structural material, such as cadmium or zinc coated steel,
or plastic material; and no process material, such as welding
filler metal; which is a hazardous material may be used until
the employer has ascertained the potential fire, toxic, or reactivity
hazards which are likely to be encountered in the handling, application,
or utilization of such a material.
(2) In order to ascertain the hazards, as required by subsection
(1) of this section, the employer shall obtain the following items
of information which are applicable to a specific product or material
to be used:
(a) The name, address, and telephone number of the source
of the information specified in this section preferably those
of the manufacturer of the product or material.
(b) The trade name and synonyms for a mixture of chemicals,
a basic structural material, or for a process material; and
the chemical name and synonyms, chemical family, and formula
for a single chemical.
(c) Chemical names of hazardous ingredients, including, but
not limited to, those in mixtures, such as those in: (i) Paints,
preservatives, and solvents; (ii) alloys, metallic coatings,
filler metals and their coatings or core fluxes; and (iii) other
liquids, solids, or gases (e.g., abrasive materials).
(d) An indication of the percentage, by weight or volume,
which each ingredient of a mixture bears to the whole mixture,
and of the threshold limit value of each ingredient, in appropriate
units.
(e) Physical data about a single chemical or a mixture of
chemicals, including boiling point, in degrees Fahrenheit; vapor
pressure, in millimeters of mercury; vapor density of gas or
vapor (air=1); solubility in water, in percent by weight; specific
gravity of material (water=1); percentage volatile, by volume,
at 70°F.; evaporation rate for liquids (either butyl acetate
or ether may be taken as 1); and appearance and odor.
(f) Fire and explosion hazard data about a single chemical
or a mixture of chemicals, including flashpoint, in degrees
Fahrenheit; flammable limits, in percent by volume in air; suitable
extinguishing media or agents; special fire fighting procedures;
and unusual fire and explosion hazard information.
(g) Health hazard data, including threshold limit value, in
appropriate units, for a single hazardous chemical or for the
individual hazardous ingredients of a mixture as appropriate,
effects of overexposure; and emergency and first aid procedures.
(h) Reactivity data, including stability, incompatibility,
hazardous decomposition products, and hazardous polymerization.
(i) Procedures to be followed and precautions to be taken
in cleaning up and disposing of materials leaked or spilled.
(j) Special protection information, including use of personal
protective equipment, such as respirators, eye protection, and
protective clothing, and of ventilation, such as local exhaust,
general, special, or other types.
(k) Special precautionary information about handling and storing.
(l) Any other general precautionary information.
(3) The pertinent information required by subsection (2) of
this section shall be recorded either on United States Department
of Labor Form LSB 00S-4, Material Safety Data Sheet, or on an
essentially similar form which has been approved by the department
of labor and industries. Copies of Form LSB 00S-4 may be obtained
at any of the following regional offices of the occupational safety
and health administration:
(a) Pacific region. (Arizona, California, Hawaii, and Nevada.)
10353 Federal Building, 450 Golden Gate Avenue, Box 36017, San
Francisco, Calif. 94102.
(b) Region X, OSHA, (Alaska, Washington, Idaho, and Oregon),
1111 3rd Ave., Suite 715, Seattle,Washington 98101.
A completed MSDS form shall be preserved and available for
inspection for each hazardous chemical on the worksite.
(4) The employer shall instruct employees who will be exposed
to the hazardous materials as to the nature of the hazards and
the means of avoiding them.
(5) The employer shall provide all necessary controls, and the
employees shall be protected by suitable personal protective equipment
against the hazards identified under subsection (1) of this section
and those hazards for which specific precautions are required
in WAC 296-304-020
through 296-304-04013.
(6) The employer shall provide adequate washing facilities for
employees engaged in the application of paints or coatings or
in other operations where contaminants can, by ingestion or absorption,
be detrimental to the health of the employees. The employer shall
encourage good personal hygiene practices by informing the employees
of the need for removing surface contaminants by thorough washing
of hands and face prior to eating or smoking.
(7) The employer shall not permit eating or smoking in areas
undergoing surface preparation or preservation or where shiprepairing,
shipbuilding, or shipbreaking operations produce atmospheric contamination.
(8) The employer shall not permit employees to work in the immediate
vicinity of uncovered garbage and shall ensure that employees
working beneath or on the outboard side of a vessel are not subject
to contamination by drainage or waste from overboard discharges.
(9) Requirements of WAC 296-800-170,
chemical hazard communication program, will apply to shiprepairing,
shipbuilding, and shipbreaking when potential hazards of chemicals
and communicating information concerning hazards and appropriate
protective equipment is applicable to an operation.
[Statutory Authority: RCW 49.17.010,
.040, .050, and .060. 07-03-163 (Order 06-30), § 296-304-06013,
filed 01/24/07, effective 04/01/07. Statutory Authority: Statutory
Authority: Chapter 49.17.040, 49.17.050, 49.17.060; 98-02-006
(Order 96-18), § 296-304-06013, filed 12/26/97, effective 3/1/98;
RCW 49.17; 95-04-006, § 296-304-06013, filed 1/18/95, effective
3/10/95; 88-14-108 (Order 88-11), § 296-304-06013, filed 7/6/88;
Order 76-7, § 296-304-06013, filed 3/1/76; Order 74-25, § 296-304-06013,
filed 5/7/74.
WAC
296-304-06015 First aid.
(1) Unless a first-aid room and a qualified attendant are close
at hand and prepared to render first aid to employees on behalf
of the employer, the employer shall furnish a first-aid kit for
each vessel on which work is being performed, except that when
work is being performed on more than one small vessel at one pier,
only one kit shall be required. The kit, when required, shall
be kept close to the vessel and at least one employee, close,
at hand, shall be qualified to administer first aid to the injured.
(2) The first-aid kit shall consist of a weatherproof container
with individual sealed packages for each type of item. The contents
of such kit shall contain a sufficient quantity of at least the
following types of items:
Gauze roller bandages,
1 inch and 2 inch.
Gauze compress bandages,
4 inch.
Adhesive bandages,
1 inch.
Triangular bandage,
40 inch.
Ammonia inhalants
and ampules.
Antiseptic applicators
or swabs.
Burn dressing.
Eye dressing.
Wire or thin board
splints.
Forceps and tourniquet.
(3) The contents of the first-aid kit shall be checked before
being sent out on each job and at least weekly on each job to
ensure that the expended items are replaced.
(4) There shall be available for each vessel on which ten or
more employees are working one Stokes basket stretcher, or equivalent,
permanently equipped with bridles for attaching to the hoisting
gear, except that no more than two stretchers are required on
each job location. A blanket or other liner suitable for transferring
the patient to and from the stretcher shall be provided. Stretchers
shall be kept close to the vessels. This section does not apply
where ambulance services which are available are known to carry
such stretchers.
[Order 74-25, § 296-304-06015,
filed 5/7/74.]
WAC
296-304 Continued
|