General Safety & Health Standards |
|
|
Electrical
Chapter 296-24 WAC, Part L (Continued)
|
|
WAC 296-24-95611
Specific purpose equipment and installations.
(1) Electric signs and outline lighting.
(a) Disconnecting means. Signs operated by electronic or electromechanical
controllers located outside the sign shall have a disconnecting means
located inside the controller enclosure or within sight of the controller
location, and it shall be capable of being locked in the open position.
Such disconnecting means shall have no pole that can be operated independently,
and it shall open all ungrounded conductors that supply the controller
and sign. All other signs, except the portable type, and all outline
lighting installations shall have an externally operable disconnecting
means which can open all ungrounded conductors and is within the sight
of the sign or outline lighting it controls.
(b) Doors or covers giving access to uninsulated parts of indoor signs
or outline lighting exceeding 600 volts and accessible to other than
qualified persons shall either be provided with interlock switches to
disconnect the primary circuit or shall be so fastened that the use
of other than ordinary tools will be necessary to open them.
(2) Cranes and hoists. This subsection applies to the installation of
electric equipment and wiring used in connection with cranes, monorail
hoists, hoists, and all runways.
(a) Disconnecting means.
(i) A readily accessible disconnecting means shall be provided between
the runway contact conductors and the power supply.
(ii) Another disconnecting means, capable of being locked in the
open position, shall be provided in the leads from the runway contact
conductors or other power supply on any crane or monorail hoist.
(A) If this additional disconnection means is not readily accessible
from the crane or monorail hoist operating station means shall be
provided at the operating station, to open the power circuit to
all motors of the crane or monorail hoist.
(B) The additional disconnect may be omitted if a monorail hoist
or hand-propelled crane bridge installation meets all of the following:
(I) The unit is floor controlled;
(II) The unit is within view of the power supply disconnecting
means; and
(III) No fixed work platform has been provided for servicing
the unit.
(b) Control. A limit switch or other device shall be provided to prevent
the load block from passing the safe upper limit of travel of any hoisting
mechanism.
(c) Clearance. The dimension of the working space in the direction
of access to live parts which may require examination, adjustment, servicing,
or maintenance while alive shall be a minimum of 2 feet 6 inches. Where
controls are enclosed in cabinets, the door(s) shall either open at
least 90 degrees or be removable.
(3) Elevators, dumbwaiters, escalators, and moving walks.
(a) Disconnecting means. Elevators, dumbwaiters, escalators, and moving
walks shall have a single means for disconnecting all ungrounded main
power supply conductors for each unit.
(b) Warning signs. If interconnections between control panels are necessary
for operation of the system on a multicar installation that
remains energized from a source other than the disconnecting
means, a warning sign shall be mounted on or adjacent to the
disconnecting means. The sign shall be clearly legible and shall
read "Warning--Parts of the control panel are not de-energized
by this switch." (See WAC
296-24-95603 (2)(c).)
(c) Control panels. If control panels are not located in the same space
as the drive machine, they shall be located in cabinets with doors or
panels capable of being locked closed.
(4) Electric welders--disconnecting means.
(a) A disconnecting means shall be provided in the supply circuit for
each motor-generator arc welder, and for each AC transformer and DC
rectifier arc welder which is not equipped with a disconnect mounted
as an integral part of the welder.
(b) A switch or circuit breaker shall be provided by which each resistance
welder and its control equipment can be isolated from the supply circuit.
The ampere rating of this disconnecting means may not be less than the
supply conductor ampacity.
(5) Data processing systems--disconnecting means. A disconnecting means
shall be provided to disconnect the power to all electronic equipment
in data processing or computer rooms. This disconnecting means shall be
controlled from locations readily accessible to the operator at the principal
exit doors. There shall also be a similar disconnecting means to disconnect
the air conditioning system serving this area.
(6) X-ray equipment. This subsection applies to x-ray equipment for other
than medical or dental use.
(a) Disconnecting means.
(i) A disconnecting means shall be provided in the supply circuit.
The disconnecting means shall be operable from a location readily
accessible from the x-ray control. For equipment connected to a 120-volt
branch circuit of 30 amperes or less, a grounding-type attachment
plug cap and receptacle of proper rating may serve as a disconnecting
means.
(ii) If more than one piece of equipment is operated from the same
high-voltage circuit, each piece or each group of equipment as a unit
shall be provided with a high-voltage switch or equivalent disconnecting
means. This disconnecting means shall be constructed, enclosed, or
located so as to avoid contact by employees with its live parts.
(b) Control.
(i) Radiographic and fluoroscopic types. Radiographic and fluoroscopic-type
equipment shall be effectively enclosed or shall have interlocks that
de-energize the equipment automatically to prevent ready access to
live current-carrying parts.
(ii) Diffraction and irradiation types. Diffraction-type and irradiation-type
equipment shall be provided with a means to indicate when it is energized
unless the equipment or installation is effectively enclosed or is
provided with interlocks to prevent access to live current-carrying
parts during operation.
(7) Induction and dielectric heating equipment.
(a) Scope. Subdivisions (b) and (c) of this subsection cover induction
and dielectric heating equipment and accessories for industrial and
scientific applications, but not for medical dental applications or
for appliances.
(b) Guarding and grounding.
(i) Enclosures. The converting apparatus (including the DC line)
and high-frequency electric circuits (excluding the output circuits
and remote-control circuits) shall be completely contained within
enclosures of noncombustible material.
(ii) Panel controls. All panel controls shall be of dead-front construction.
(iii) Access to internal equipment. Where doors are used for access
to voltages from 500 to 1000 volts AC or DC, either door locks or
interlocks shall be provided. Where doors are used for access to voltages
of over 1000 volts AC or DC, either mechanical lockouts with a disconnecting
means to prevent access until voltage is removed from the cubicle,
or both door interlocking and mechanical door locks, shall be provided.
(iv) Warning labels. "Danger" labels shall be attached on the equipment
and shall be plainly visible even when doors are open or panels are
removed from compartments containing voltages of over 250 volts AC
or DC.
(v) Work applicator shielding. Protective cages or adequate shielding
shall be used to guard work applicators other than induction heating
coils. Induction heating coils shall be protected by insulation and/or
refractory materials. Interlock switches shall be used on all hinged
access doors, sliding panels, or other such means of access to the
applicator. Interlock switches shall be connected in such a manner
as to remove all power from the applicator when any one of the access
doors or panels is open. Interlocks on access doors or panels are
not required if the applicator is an induction heating coil at DC
ground potential or operating at less than 150 volts AC.
(vi) Disconnecting means. A readily accessible disconnecting means
shall be provided by which each unit of heating equipment can be isolated
from its supply circuit.
(c) Remote control. If remote controls are used for applying power,
a selector switch shall be provided and interlocked to provide power
from only one control point at a time. Switches operated by foot pressure
shall be provided with a shield over the contact button to avoid accidental
closing the switch.
(8) Electrolytic cells.
(a) Scope. These provisions for electrolytic cells apply to the installation
of the electrical components and accessory equipment of electrolytic
cells, electrolytic cell lines, and process power supply for the production
of aluminum, cadmium, chlorine, copper, fluorine, hydrogen peroxide,
magnesium, sodium, sodium chlorate, and zinc. Cells used as a source
of electric energy and for electroplating processes and cells used for
production of hydrogen are not covered by these provisions.
(b) Definitions applicable to this subsection.
Cell line: An assembly of electrically interconnected electrolytic
cells supplied by a source of direct-current power.
Cell line attachments and auxiliary equipment: Cell line attachments
and auxiliary equipment include, but are not limited to: Auxiliary tanks;
process piping; duct work; structural supports; exposed cell line conductors;
conduits and other raceways; pumps; positioning equipment and cell cutout
or bypass electrical devices. Auxiliary equipment also includes tools,
welding machines, crucibles, and other portable equipment used for operation
and maintenance within the electrolytic cell line working zone. In the
cell line working zone, auxiliary equipment includes the exposed conductive
surfaces of ungrounded cranes and crane-mounted cell-servicing equipment.
Cell line working zone: The cell line working zone is the space
envelope wherein operation or maintenance is normally performed on or
in the vicinity of exposed energized surfaces of cell lines or their
attachments.
Electrolytic cells: A receptacle or vessel in which electrochemical
reactions are caused by applying energy for the purpose of refining
or producing usable materials.
(c) Application. Installations covered by subsection (8) of this section
shall comply with all applicable provisions of this section except as
follows:
(i) Overcurrent protection of electrolytic cell DC process power
circuits need not comply with the requirements of WAC
296-24-95607(5).
(ii) Equipment located or used within the cell line working zone
or associated with the cell line DC power circuits need not
comply with the provisions of WAC
296-24-95607(6).
(iii) Electrolytic cells, cell line conductors, cell line
attachments, and the wiring of auxiliary equipment and devices
within the cell line working zone need not comply with the
provisions of WAC
296-24-95605 and 296-24-95607
(2) and (3).
(d) Disconnecting means.
(i) If more than one DC cell line process power supply serves the
same cell line, a disconnecting means shall be provided on the cell
line circuit side of each power supply to disconnect it from the cell
line circuit.
(ii) Removable links or removable conductors may be used as the disconnecting
means.
(e) Portable electric equipment.
(i) The frames and enclosures of portable electric equipment used
within the cell line working zone may not be grounded. However, these
frames and enclosures may be grounded if the cell line circuit voltage
does not exceed 200 volts DC or if the frames are guarded.
(ii) Ungrounded portable electric equipment shall be distinctively
marked and may not be interchangeable with grounded portable electric
equipment.
(f) Power supply circuits and receptacles for portable electric equipment.
(i) Circuits supplying power to ungrounded receptacles for hand-held,
cord- and plug-connected equipment shall be electrically isolated
from any distribution system supplying areas other than the cell line
working zone and shall be ungrounded. Power for these circuits shall
be supplied through isolating transformers.
(ii) Receptacles and their mating plugs for ungrounded equipment
may not have provision for a grounding conductor and shall be of a
configuration which prevents their use for equipment required to be
grounded.
(iii) Receptacles on circuits supplied by an isolating transformer
with an ungrounded secondary shall have a distinctive configuration,
shall be distinctively marked, and may not be used in any other location
in the plant.
(g) Fixed and portable electric equipment.
(i) AC systems supplying fixed and portable electric equipment within
the cell line working zone need not be grounded.
(ii) Exposed conductive surfaces, such as electric equipment housings,
cabinets, boxes, motors, raceways and the like that are within the
cell line working zone need not be grounded.
(iii) Auxiliary electrical devices, such as motors, transducers,
sensors, control devices, and alarms, mounted on an electrolytic cell
or other energized surface, shall be connected by any of the following
means:
(A) Multiconductor hard usage or extra hard usage flexible cord;
(B) Wire or cable in suitable raceways; or
(C) Exposed metal conduit, cable tray, armored cable, or similar
metallic systems installed with insulating breaks such that they
will not cause a potentially hazardous electrical condition.
(iv) Fixed electric equipment may be bonded to the energized conductive
surfaces of the cell line, its attachments, or auxiliaries. If fixed
electric equipment is mounted on an energized conductive surface,
it shall be bonded to that surface.
(h) Auxiliary nonelectric connections. Auxiliary nonelectric connections,
such as air hoses, water hoses, and the like, to an electrolytic cell,
its attachments, or auxiliary equipment may not have continuous conductive
reinforcing wire, armor, braids, and the like. Hoses shall be of a nonconductive
material.
(i) Cranes and hoists.
(i) The conductive surfaces of cranes and hoists that enter the cell
line working zone need not be grounded. The portion of an overhead
crane or hoist which contacts an energized electrolytic cell or energized
attachments shall be insulated from ground.
(ii) Remote crane or hoist controls which may introduce hazardous
electrical conditions into the cell line working zone shall employ
one or more of the following systems:
(A) Insulated and ungrounded control circuit;
(B) Nonconductive rope operator;
(C) Pendent pushbutton with nonconductive supporting means and
having nonconductive surfaces or ungrounded exposed conductive surfaces;
or
(D) Radio.
(9) Electrically driven or controlled irrigation machines. (See
WAC
296-24-95603 (2)(c).)
(a) Lightning protection. If an electrically driven or controlled irrigation
machines has a stationary point, a driven ground rod shall be connected
to the machine at the stationary point for lightning protection.
(b) Disconnecting means. The main disconnecting means for a center
pivot irrigation machine shall be located at the point of connection
of electrical power to the machine and shall be readily accessible and
capable of being locked in the open position. A disconnecting means
shall be provided for each motor and controller.
(10) Swimming pools, fountains, and similar installations.
(a) Scope. Subdivisions (b) through (e) of this subsection apply to
electric wiring for and equipment in or adjacent to all swimming, wading,
therapeutic, and decorative pools and fountains, whether permanently
installed or storable, and to metallic auxiliary equipment, such as
pumps, filters, and similar equipment. Therapeutic pools in health care
facilities are exempt from these provisions.
(b) Lighting and receptacles.
(i) Receptacles. A single receptacle of the locking and grounding
type that provides power for a permanently installed swimming pool
recirculating pump motor may be located not less than 5 feet from
the inside walls of a pool. All other receptacles on the property
shall be located at least 10 feet from the inside walls of a pool.
Receptacles which are located within 15 feet of the inside walls of
the pool shall be protected by ground-fault circuit interrupters.
Note: In determining these dimensions, the distance
to be measured is the shortest path the supply cord of an appliance
connected to the receptacle would follow without piercing a floor,
wall, or ceiling of a building or other effective permanent barrier.
(ii) Lighting fixtures and lighting outlets.
(A) Unless they are 12 feet above the maximum water level, lighting
fixtures and lighting outlets may not be installed over a pool or
over the area extending 5 feet horizontally from the inside walls
of a pool. However, a lighting fixture or lighting outlet which
has been installed before April 16, 1981, may be located less than
5 feet measured horizontally from the inside walls of a pool if
it is at least 5 feet above the surface of the maximum water level
and shall be rigidly attached to the existing structure. It shall
also be protected by a ground-fault circuit interrupter installed
in the branch circuit supplying the fixture.
(B) Unless installed 5 feet above the maximum water level and rigidly
attached to the structure adjacent to or enclosing the pool, lighting
fixtures and lighting outlets installed in the area extending between
5 feet and 10 feet horizontally from the inside walls of a pool
shall be protected by a ground-fault circuit interrupter.
(c) Cord-connected and plug-connected equipment. Flexible cords used
with the following equipment may not exceed 3 feet in length and shall
have a copper equipment grounding conductor with a grounding-type attachment
plug.
(i) Cord-connected and plug-connected lighting fixtures installed
within 16 feet of the water surface of permanently installed pools.
(ii) Other cord-connected and plug-connected, fixed or stationary
equipment used with permanently installed pools.
(d) Underwater equipment.
(i) A ground-fault circuit interrupter shall be installed in the
branch circuit supplying underwater fixtures operating at more than
15 volts. Equipment installed underwater shall be approved for the
purpose.
(ii) No underwater lighting fixtures may be installed for operation
at over 150 volts between conductors.
(e) Fountains. All electric equipment operating at more than 15 volts,
including power supply cords, used with fountains shall be protected
by ground-fault circuit interrupters. (See WAC
296-24-95603 (2)(c).)
(11) Safety procedure and protective equipment required for exposure
to movie theater Xenon bulbs. Exposure also includes opening of the lamphouse
where the bulb is installed. The following are minimum requirements for
theater personnel or others who install, change, or dispose of Xenon bulbs
and are exposed to potential explosion hazard:
(a) All bulbs, new, used or subject to future disposal, must be stored
in the protective jacket provided until time of use.
(b) Protective equipment shall be furnished at no cost to the employee
and the use shall be strictly enforced for any exposed employee. Basic
safety equipment required is:
(i) Full protective face shield with crown protector.
(ii) Safety glasses for use under face shield. (To meet required
impact resistance test of ANSI Z87.1.)
(iii) Impact resistant, long-sleeved jacket of a length adequate
to protect vital organs.
(iv) Impact resistant gloves.
(c) A bulb subject to disposal should be removed with the regular,
proper precautions, carefully placed in its protective jacket or cover
and deliberately broken by dropping from a sufficient height. An unbroken
bulb must never be disposed of as regular garbage or trash.
Bulbs must be handled only at room temperature. If they have been in
operation, adequate time (at least 10 minutes) must be allowed for the
bulb to cool to room temperature before handling.
[Statutory Authority: Chapter 49.17 RCW.
91-03-044 (Order 90-18), 296-24-95611, filed 1/10/91, effective 2/12/91;
87-24-051 (Order 87-24), 296-24-95611, filed 11/30/87. Statutory Authority:
RCW 49.17.040 and 49.17.050. 82-08-026 (Order 82-10), 296-24-95611, filed
3/30/82.]
WAC 296-24-95613
Hazardous (classified) locations.
(1) Scope. This section covers the requirements for electric equipment
and wiring in locations which are classified depending on the properties
of the flammable vapors, liquids or gases, or combustible dusts or fibers
which may be present therein and the likelihood that a flammable combustible
concentration or quantity is present. Hazardous (classified) locations
may be found in occupancies such as, but not limited to, the following:
Aircraft hangars, gasoline dispensing and service stations, bulk storage
plants for gasoline or other volatile flammable liquids, paint-finishing
process plants, health care facilities, agricultural or other facilities
where excessive combustible dusts may be present, marinas, boat yards,
and petroleum and chemical processing plants. Each room, section or area
shall be considered individually in determining its classification. These
hazardous (classified) locations are assigned six designations as follows:
Class I, Division 1
Class I, Division 2
Class II, Division 1
Class II, Division 2
Class III, Division 1
Class III, Division 2
For definitions of these locations see WAC
296-24-95601(1). All applicable requirements in this part
shall apply to hazardous (classified) locations, unless modified
by provisions of this section.
(2) Electrical installations. Equipment, wiring methods, and installations
of equipment in hazardous (classified) locations shall be intrinsically
safe, or approved for the hazardous (classified) location, or safe for
the hazardous (classified) location. Requirements for each of these options
are as follows:
(a) Intrinsically safe. Equipment and associated wiring approved as
intrinsically safe shall be permitted in any hazardous (classified)
location for which it is approved.
(b) Approved for the hazardous (classified) location.
(i) Equipment shall be approved not only for the class of location
but also for the ignitible or combustible properties of the specific
gas, vapor, dust, or fiber that will be present.
Note: NFPA 70, the National Electrical Code,
lists or defines hazardous gases, vapors, and dusts by "groups" characterized
by their ignitible or combustible properties.
(ii) Equipment shall be marked to show the class, group, and operating
temperature or temperature range, based on operation in a 40 degrees
C ambient, for which it is approved. The temperature marking may not
exceed the ignition temperature of the specific gas or vapor to be
encountered. However, the following provisions modify this marking
requirement for specific equipment:
(A) Equipment of the nonheat-producing type, such as junction boxes,
conduit, and fittings, and equipment of the heat-producing type
having a maximum temperature not more than 100 degrees C (212 degrees
F) need not have a marked operating temperature or temperature range.
(B) Fixed lighting fixtures marked for use in Class I, Division
2 locations only, need not be marked to indicate the group.
(C) Fixed general-purpose equipment in Class I locations, other
than lighting fixtures, which is acceptable for use in Class I,
Division 2 locations need not be marked with the class, group, division,
or operating temperature.
(D) Fixed dust-tight equipment, other than lighting fixtures, which
is acceptable for use in Class II, Division 2 and Class III locations
need not be marked with the class, group, division, or operating
temperature.
(c) Safe for the hazardous (classified) location. Equipment which is
safe for the location shall be of a type and design which the employer
demonstrates will provide protection from the hazards arising from the
combustibility and flammability of vapors, liquids, gases, dusts, or
fibers.
Note: The National Electrical Code, NFPA 70, contains
guidelines for determining the type and design of equipment and installations
which will meet this requirement. The guidelines of this document address
electric wiring, equipment, and systems installed in hazardous (classified)
locations and contain specific provisions for the following: Wiring
methods, wiring connections; conductor insulation, flexible cords, sealing
and drainage, transformers, capacitors, switches, circuit breakers,
fuses, motor controllers, receptacles, attachment plugs, meters, relays,
instruments, resistors, generators, motors, lighting fixtures, storage
battery charging equipment, electric cranes, electric hoists and similar
equipment, utilization equipment, signaling systems, alarm systems,
remote control systems, local loud speaker and communication systems,
ventilation piping, live parts, lighting surge protection, and grounding.
Compliance with these guidelines will constitute one means, but not
the only means, of compliance with this subsection.
(3) Conduits. All conduits shall be threaded and shall be made wrench-tight.
Where it is impractical to make a threaded joint tight, a bonding jumper
shall be utilized.
(4) Equipment in Division 2 locations. Equipment that has been approved
for a Division 1 location may be installed in a Division 2 location of
the same class and group. General-purpose equipment or equipment in general-purpose
enclosures may be installed in Division 2 locations if the equipment does
not constitute a source of ignition under normal operating conditions.
Motors and generators. Motors and generators shall conform to the following:
Class I, Division 1. In Class I, Division 1 locations, motors, generators
and other rotating electric machinery shall be: (a) Approved for Class
I, Division 1 locations (explosion-proof); or (b) of the totally enclosed
type supplied with positive-pressure ventilation from a source of clean
air with discharge to a safe area, so arranged to prevent energizing of
the machine until ventilation has been established and the enclosure has
been purged with at least 10 volumes of air, and also arranged to automatically
deenergize the equipment when the air supply fails; or (c) of the totally
enclosed inert-gas-filled type supplied with a suitable reliable source
of inert gas for pressuring the enclosure, with devices provided to ensure
a positive pressure in the enclosure and arranged to automatically deenergize
the equipment when the gas supply fails; or (d) of a type designed to
be submerged in a liquid which is flammable only when vaporized and mixed
with air, or in a gas or vapor at a pressure greater than atmospheric
and which is flammable only when mixed with air; and the machine is so
arranged to prevent energizing it until it has been purged with the liquid
or gas to exclude air, and also arranged to automatically deenergize the
equipment when the supply of liquid, or gas or vapor fails or the pressure
is reduced to atmospheric. Totally enclosed motors of types (b) and (c)
shall have no external surface with an operating temperature in degrees
Celsius in excess of eighty percent of the ignition temperature of the
gas or vapor involved, as determined by ASTM test procedure (Designation:
D-2155-69). Appropriate devices shall be provided to detect any increase
in temperature of the motor beyond design limits and automatically deenergize
the equipment or provide an adequate alarm. Auxiliary equipment shall
be of a type approved for the location in which it is installed.
[Statutory Authority: Chapter 49.17 RCW.
94-15-096 (Order 94-07), 296-24-95613, filed 7/20/94, effective 9/20/94;
87-24-051 (Order 87-24), 296-24-95613, filed 11/30/87. Statutory Authority:
RCW 49.17.040 and 49.17.050. 82-08-026 (Order 82-10), 296-24-95613, filed
3/30/82.]
WAC 296-24-95615
Special systems.
(1) Systems over 600 volts, nominal. Subdivisions (a) through (d) of
this subsection cover the general requirements for all circuits and equipment
operated at over 600 volts.
(a) Wiring methods for fixed installations.
(i) Above-ground conductors shall be installed in rigid metal conduit,
in intermediate metal conduit, in cable trays, in cablebus, in other
suitable raceways, or as open runs of metal-clad cable suitable for
the use and purpose. However, open runs of nonmetallic-sheathed cable
or of bare conductors or busbars may be installed in locations accessible
only to qualified persons. Metallic shielding components, such as
tapes, wires, or braids for conductors, shall be grounded. Open runs
of insulated wires and cables having a bare lead sheath or a braided
outer covering shall be supported in a manner designed to prevent
physical damage to the braid or sheath.
(ii) Conductors emerging from the ground shall be enclosed in approved
raceways. (See WAC
296-24-95603 (2)(c).)
(b) Interrupting and isolating devices.
(i) Circuit breaker installations located indoors shall consist of
metal-enclosed units or fire-resistant cell-mounted units. In locations
accessible only to qualified personnel, open mounting of circuit breakers
is permitted. A means of indicating the open and closed position of
circuit breakers shall be provided.
(ii) Fused cutouts installed in buildings or transformer vaults shall
be of a type approved for the purpose. They shall be readily accessible
for fuse replacement.
(iii) A means shall be provided to completely isolate equipment for
inspection and repairs. Isolating means which are not designed to
interrupt the load current of the circuit shall be either interlocked
with an approved circuit interrupter or provided with a sign warning
against opening them under load.
(c) Mobile and portable equipment.
(i) Power cable connections to mobile machines. A metallic enclosure
shall be provided on the mobile machine for enclosing the terminals
of the power cable. The enclosure shall include provisions for a solid
connection for the ground wire(s) terminal to effectively ground the
machine frame. The method of cable termination used shall prevent
any strain or pull on the cable from stressing the electrical connections.
The enclosure shall have provision for locking so only authorized
qualified persons may open it and shall be marked with a sign warning
of the presence of energized parts.
(ii) Guarding live parts. All energized switching and control parts
shall be enclosed in effectively grounded metal cabinets or enclosures.
Circuit breakers and protective equipment shall have the operating
means projecting through the metal cabinet or enclosure so these units
can be reset without locked doors being opened. Enclosures and metal
cabinets shall be locked so that only authorized qualified persons
have access and shall be marked with a sign warning of the presence
of energized parts. Collector ring assemblies on revolving-type machines
(shovels, draglines, etc.) shall be guarded.
(d) Tunnel installations.
(i) Application. The provisions of this subsection apply to installation
and use of high-voltage power distribution and utilization equipment
which is portable and/or mobile, such as substations, trailers, cars,
mobile shovels, draglines, hoists, drills, dredges, compressors, pumps,
conveyors, and underground excavators.
(ii) Conductors. Conductors in tunnels shall be installed in one
or more of the following:
(A) Metal conduit or other metal raceway,
(B) Type MC cable, or
(C) Other approved multiconductor cable.
Conductors shall also be so located or guarded as to protect them
from physical damage. Multiconductor portable cable may supply mobile
equipment. An equipment grounding conductor shall be run with circuit
conductors inside the metal raceway or inside the multiconductor
cable jacket. The equipment grounding conductor may be insulated
or bare.
(iii) Guarding live parts. Bare terminals of transformers, switches,
motor controllers, and other equipment shall be enclosed to prevent
accidental contact with energized parts. Enclosures for use in tunnels
shall be drip-proof, weatherproof, or submersible as required by the
environmental conditions.
(iv) Disconnecting means. A disconnecting means that simultaneously
opens all ungrounded conductors shall be installed at each transformer
or motor location.
(v) Grounding and bonding. All nonenergized metal parts of electric
equipment and metal raceways and cable sheaths shall be effectively
grounded and bonded to all metal pipes and rails at the portal and
at intervals not exceeding 1000 feet throughout the tunnel.
(2) Emergency power systems.
(a) Scope. The provisions for emergency systems apply to circuits,
systems, and equipment intended to supply power for illumination and
special loads, in the event of failure of the normal supply.
(b) Wiring methods. Emergency circuit wiring shall be kept entirely
independent of all other wiring and equipment and may not enter the
same raceway, cable, box, or cabinet as other wiring except either where
common circuit elements suitable for the purpose are required, or for
transferring power from the normal to the emergency source.
(c) Emergency illumination. Where emergency lighting is necessary,
the system shall be so arranged that the failure of any individual lighting
element, such as the burning out of a light bulb, cannot leave any space
in total darkness.
(3) Class 1, Class 2, and Class 3 remote control, signaling, and power-limited
circuits.
(a) Classification. Class 1, Class 2, or Class 3 remote control, signaling,
or power-limited circuits are characterized by their usage and electrical
power limitation which differentiates them from light and power circuits.
These circuits are classified in accordance with their respective voltage
and power limitations as summarized in items (a)(i) through (a)(iii)
of this subsection.
(i) Class 1 circuits.
(A) A Class 1 power-limited circuit is supplied from a source having
a rated output of not more than 30 volts and 1000 volt-amperes.
(B) A Class 1 remote control circuit or a Class 1 signaling circuit
has a voltage which does not exceed 600 volts; however, the power
output of the source need not be limited.
(ii) Class 2 and Class 3 circuits.
(A) Power for Class 2 and Class 3 circuits is limited either inherently
(in which no overcurrent protection is required) or by a combination
of a power source and overcurrent protection.
(B) The maximum circuit voltage is 150 volts AC or DC for a Class
2 inherently limited power source, and 100 volts AC or DC for a
Class 3 inherently limited power source.
(C) The maximum circuit voltage is 30 volts AC and 60 volts DC
for a Class 2 power source limited by overcurrent protection, and
150 volts AC or DC for a Class 3 power source limited by overcurrent
protection.
(iii) The maximum circuit voltages in items (a)(i) and (a)(ii) of
this subsection apply to sinusoidal AC or continuous DC power sources,
and where wet contact occurrence is not likely.
(b) Marking. A Class 2 or Class 3 power supply unit shall be durably
marked where plainly visible to indicate the class of supply
and its electrical rating. (See WAC
296-24-95603 (2)(c).)
(4) Fire protective signaling systems. (See WAC
296-24-95603 (2)(c).)
(a) Classifications. Fire protective signaling circuits shall be classified
either as nonpower limited or power limited.
(b) Power sources. The power sources for use with fire protective signaling
circuits shall be either power limited or nonlimited as follows:
(i) The power supply of nonpower-limited fire protective signaling
circuits shall have an output voltage not in excess of 600 volts.
(ii) The power for power-limited fire protective signaling circuits
shall be either inherently limited, in which no overcurrent protection
is required, or limited by a combination of power source and overcurrent
protection.
(c) Nonpower-limited conductor location. Nonpower-limited fire protective
signaling circuits and Class 1 circuits may occupy the same enclosure,
cable, or raceway provided all conductors are insulated for maximum
voltage of any conductor within the enclosure, cable or raceway. Power
supply and fire protective signaling circuit conductors are permitted
in the same enclosure, cable, or raceway only if connected to the same
equipment.
(d) Power-limited conductor location. Where open conductors are installed,
power-limited fire protective signaling circuits shall be separated
at least 2 inches from conductors of any light, power, Class 1, and
nonpower-limited fire protective signaling circuits unless a special
and equally protective method of conductor separation is employed. Cables
and conductors of two or more power-limited fire protective signaling
circuits or Class 3 circuits are permitted in the same cable, enclosure,
or raceway. Conductors of one or more Class 2 circuits are permitted
within the same cable, enclosure, or raceway with conductors of power-limited
fire protective signaling circuits provided that the insulation of Class
2 circuit conductors in the cable, enclosure, or raceway is at least
that needed for the power-limited fire protective signaling circuits.
(e) Identification. Fire protective signaling circuits shall be identified
at terminal and junction locations in a manner which will prevent unintentional
interference with the signaling circuit during testing and servicing.
Power-limited fire protective signaling circuits shall be durably marked
as such where plainly visible at terminations.
(5) Communications systems.
(a) Scope. These provisions for communication systems apply
to such systems as central-station-connected and noncentral-station-connected
telephone circuits, radio and television receiving and transmitting
equipment, including community antenna television and radio
distribution systems, telegraph, district messenger, and outside
wiring for fire and burglar alarm, and similar central station
systems. These installations need not comply with the provisions
of WAC
296-24-95605 through 296-24-95615(4)
except 296-24-95607
(3)(a) and 296-24-95613(2).
(b) Protective devices.
(i) Communication circuits so located as to be exposed to accidental
contact with light or power conductors operating at over 300 volts
shall have each circuit so exposed provided with a protector approved
for the purpose.
(ii) Each conductor of a lead-in from an outdoor antenna shall be
provided with an antenna discharge unit or other suitable means that
will drain static charges from the antenna system.
(c) Conductor location.
(i) Outside of buildings.
(A) Receiving distribution lead-in or aerial-drop cables attached
to buildings and lead-in conductors to radio transmitters shall
be so installed as to avoid the possibility of accidental contact
with electric light or power conductors.
(B) The clearance between lead-in conductors and any lightning
protection conductors may not be less than 6 feet.
(ii) On poles. Where practicable, communication conductors on poles
shall be located below the light or power conductors. Communications
conductors may not be attached to a crossarm that carries light or
power conductors.
(iii) Inside of buildings. Indoor antennas, lead-ins, and other communication
conductors attached as open conductors to the inside of buildings
shall be located at least 2 inches from conductors of any light or
power or Class 1 circuits unless a special and equally protective
method of conductor separation, approved for the purpose, is employed.
(d) Equipment location. Outdoor metal structures supporting antennas,
as well as self-supporting antennas such as vertical rods or dipole
structures, shall be located as far away from overhead conductors of
electric light and power circuits of over 150 volts to ground as necessary
to avoid the possibility of the antenna or structure falling into or
making accidental contact with such circuits.
(e) Grounding.
(i) Lead-in conductors. If exposed to contact with electric light
and power conductors, the metal sheath of aerial cables entering buildings
shall be grounded or shall be interrupted close to the entrance to
the building by an insulating joint or equivalent device. Where protective
devices are used, they shall be grounded in an approved manner.
(ii) Antenna structures. Masts and metal structures supporting antennas
shall be permanently and effectively grounded without splice or connection
in the grounding conductor.
Equipment enclosures. Transmitters shall be enclosed in a metal frame
or grill or separated from the operating space by a barrier, all metallic
parts of which are effectively connected to ground. All external metal
handles and controls accessible to the operating personnel shall be
effectively grounded. Unpowered equipment and enclosures shall be
considered grounded where connected to an attached coaxial cable with
an effectively grounded metallic shield.
[Statutory Authority: RCW 49.17.040 and
49.17.050. 82-08-026 (Order 82-10), 296-24-95615, filed 3/30/82.]
WAC 296-24-95617
Reserved.
[Statutory Authority: Chapter 49.17 RCW.
91-24-017 (Order 91-07), 296-24-95617, filed 11/22/91, effective 12/24/91.
Statutory Authority: RCW 49.17.040 and 49.17.050. 82-08-026 (Order 82-10),
296-24-95617, filed 3/30/82.]
WAC 296-24-95699
Appendices.
Appendix A - Reference documents. The following
references provide information which can be helpful in understanding and
complying with the requirements contained in WAC 296-24-956 through 296-24-95615.
ANSI A17.1-71 Safety Code for
Elevators, Dumbwaiters, Escalators and Moving Walks.
ANSI B9.1-71 Safety Code for
Mechanical Refrigeration.
ANSI B30.2-76 Safety Code for
Overhead and Gantry Cranes.
ANSI B30.3-75 Hammerhead Tower
Cranes.
ANSI B30.4-73 Safety Code for
Portal, Tower, and Pillar Cranes.
ANSI B30.5-68 Safety Code for
Crawler, Locomotive, and Truck Cranes.
ANSI B30.6-77 Derricks.
ANSI B30.7-77 Base Mounted
Drum Hoists.
ANSI B30.8-71 Safety Code for
Floating Cranes and Floating Derricks.
ANSI B30.11-73 Monorail Systems
and Underhung Cranes.
ANSI B30.12-75 Handling Loads
Suspended from Rotorcraft.
ANSI B30.13-77 Controlled Mechanical
Storage Cranes.
ANSI B30.15-73 Safety Code
for Mobile Hydraulic Cranes.
ANSI B30.16-73 Overhead Hoists.
ANSI C2-81 National Electrical
Safety Code.
ANSI C33.27-74 Safety Standard
for Outlet Boxes and Fittings for Use in Hazardous Locations, Class
I, Groups A, B, C, and D, and Class II, Groups E, F, and G.
ANSI K61.1-72 Safety Requirements
for the Storage and Handling of Anhydrous Ammonia.
ASTM D2155-66 Test Method for
Autoignition Temperature of Liquid Petroleum Products.
ASTM D3176-74 Method for Ultimate
Analysis of Coal and Coke.
ASTM D3180-74 Method for Calculating
Coal and Coke Analyses from as Determined to Different Bases.
IEEE 463-77 Standard for Electrical
Safety Practices in Electrolytic Cell Line Working Zones.
NFPA 20-76 Standard for the
Installation of Centrifugal Fire Pumps.
NFPA 30-78 Flammable and Combustible
Liquids Code.
NFPA 32-74 Standard for Drycleaning
Plants.
NFPA 33-73 Standard for Spray
Application Using Flammable and Combustible Materials.
NFPA 34-74 Standard for Dip
Tanks Containing Flammable or Combustible Liquids.
NFPA 35-76 Standard
for the Manufacture of Organic Coatings.
NFPA 36-74 Standard for Solvent
Extraction Plants.
NFPA 40-74 Standard for the
Storage and Handling of Cellulose Nitrate Motion Picture Film.
NFPA 56A-73 Standard for the
Use of Inhalation Anesthetics (Flammable and Nonflammable).
NFPA 56F-74 Standard for Nonflammable
Medical Gas Systems.
NFPA 58-76 Standard for the
Storage and Handling of Liquefied Petroleum Gases.
NFPA 59-76 Standard for the
Storage and Handling of Liquefied Petroleum Gases at Utility Gas Plants.
NFPA 70-78 National Electrical
Code.
NFPA 70C-74 Hazardous Locations
Classification.
NFPA 70E Standard for the Electrical
Safety Requirements for Employee Workplaces.
NFPA 71-77 Standard for the
Installation, Maintenance, and Use of Central Station Signaling Systems.
NFPA 72A-75 Standard for the
Installation, Maintenance, and Use of Local Protective Signaling Systems
for Watchman, Fire Alarm, and Supervisory Service.
NFPA 72B-75 Standard for the
Installation, Maintenance, and Use of Auxiliary Protective Signaling
Systems for Fire Alarm Service.
NFPA 72C-75 Standard for the
Installation, Maintenance, and Use of Remote Station Protective Signaling
Systems.
NFPA 72D-75 Standard for the
Installation, Maintenance, and Use of Proprietary Protective Signaling
Systems for Watchman, Fire Alarm, and Supervisory Service.
NFPA 72E-74 Standard for Automatic
Fire Detectors.
NFPA 74-75 Standard for Installation,
Maintenance, and Use of Household Fire Warning Equipment.
NFPA 76A-73 Standard for Essential
Electrical Systems for Health Care Facilities.
NFPA 77-72 Recommended Practice
on Static Electricity.
NFPA 80-77 Standard for Fire
Doors and Windows.
NFPA 86A-73 Standard for Ovens
and Furnaces; Design, Location and Equipment.
NFPA 88A-73 Standard for Parking
Structures.
NFPA 88B-73 Standard for Repair
Garages.
NFPA 91-73 Standard for the
Installation of Blower and Exhaust Systems for Dust, Stock, and Vapor
Removal, or Conveying.
NFPA 101-78 Code for Safety
to Life from Fire in Buildings and Structures. (Life Safety Code.)
NFPA 325M-69 Fire-Hazard Properties
of Flammable Liquids, Gases, and Volatile Solids.
NFPA 493-75 Standard for Intrinsically
Safe Apparatus for Use in Class I Hazardous Locations and its Associated
Apparatus.
NFPA 496-74 Standard for Purged
and Pressurized Enclosures for Electrical Equipment in Hazardous Locations.
NFPA 497-75 Recommended Practice
for Classification of Class I Hazardous Locations for Electrical Installations
in Chemical Plants.
NFPA 505-75 Fire Safety Standard
for Powered Industrial Trucks Including Type Designations and Areas
of Use.
NMAB 353-1-79 Matrix of Combustion-Relevant
Properties and Classification of Gases, Vapors, and Selected Solids.
NMAB 353-2-79 Test Equipment
for Use in Determining Classifications of Combustible Dusts.
NMAB 353-3-80 Classification
of Combustible Dusts in Accordance with the National Electrical Code.
[Statutory Authority: RCW 49.17.040 and
49.17.050. 82-08-026 (Order 82-10), 296-24-95699, filed 3/30/82.]
WAC 296-24-960 Working
on or near exposed energized parts.
(1) Application. This section applies to work performed on exposed live
parts (involving either direct contact or contact by means of tools or
materials) or near enough to them for employees to be exposed to any hazard
they present.
(2) Work on energized equipment. Only qualified persons shall work on
electric circuit parts or equipment that have not been deenergized
under the procedures of WAC
296-24-975(2). Such persons shall be capable of working safely
on energized circuits and shall be familiar with the proper use
of special precautionary techniques, personal protective equipment,
insulating and shielding materials, and insulated tools.
(3) General requirements - high voltage lines.
(a) Minimum clearance.
(i) No work shall be performed, no material shall be piled, stored
or otherwise handled, no scaffolding, commercial signs, or structures
shall be erected or dismantled, nor any tools, machinery or equipment
operated within the specified minimum distances from any energized
high voltage electrical conductor capable of energizing the material
or equipment; except where the electrical distribution and transmission
lines have been deenergized and visibly grounded at point of work,
or where insulating barriers not a part of or an attachment to the
equipment have been erected, to prevent physical contact with the
lines, equipment shall be operated proximate to, under, over, by,
or near powerlines only in accordance with the following:
(ii) For lines rated 50 kv. or below, minimum clearance between the
lines and any part of the equipment or load shall be 10 feet.
(iii) For lines rated over 50 kv. minimum, clearance between the
lines and any part of the equipment or load shall be 10 feet plus
0.4 inch for each 1 kv. over 50 kv., or twice the length of the line
insulator but never less than 10 feet.
(b) Overhead electric lines. Where overhead electric conductors are
encountered in proximity to a work area, the employer shall be responsible
for:
(i) Ascertaining the voltage and minimum clearance distance required,
and
(ii) Maintaining the minimum clearance distance, and
(iii) Ensuring that the requirements of subsection (3) of this section
are complied with.
(c) Not covered: Employees working under chapters
296-32 and 296-45
WAC.
(4) Low voltage lines. When work is being carried out in proximity to
energized electrical service conductors operating at 750 volts or less,
such work shall be performed in a manner to prevent contact by any worker
with the energized conductors.
(5) Overhead lines. If work is to be performed near overhead lines, the
lines shall be deenergized and grounded, or other protective measures
shall be provided before work is started. If the lines are to be deenergized,
arrangements shall be made with the person or organization that operates
or controls the electric circuits involved to deenergize and ground them.
If protective measures, such as guarding, isolating, or insulating, these
precautions shall prevent employees from contacting such lines directly
with any part of their body or indirectly through conductive materials,
tools, or equipment.
(6) Unqualified persons. When an unqualified person is working in an
elevated position, or on the ground, near overhead lines, the location
shall be such that the person and the longest conductive object he or
she may contact cannot come closer to any unguarded, energized overhead
line than the following distances:
(a) For voltages to ground 50kV or below--10 ft.;
(b) For voltages to ground over 50kV--10 ft. plus 0.4 inch for every
1 kV over 50 kV.
(7) Qualified persons. When a qualified person is working in the vicinity
of overhead lines, whether in an elevated position or on the ground, the
person shall not approach or take any conductive object without an approved
insulating handle closer to exposed energized parts than shown in subsections
(3) and (4) of this section unless:
(a) The person is insulated from the energized part (gloves, with sleeves
if necessary, rated for the voltage involved are considered to be insulation
of the person from the energized part on which work is performed); or
(b) The energized part is insulated both from all other conductive
objects at a different potential and from the person; or
(c) The person is insulated from all conductive objects at a potential
different from that of the energized part.
(8) Vehicular and mechanical equipment.
(a) Any vehicle or mechanical equipment capable of having parts of
its structure elevated near energized overhead lines shall be operated
so that a clearance of 10 ft. is maintained. If the voltage is higher
than 50kV, the clearance shall be increased 0.4 inch for every 1kV over
that voltage. However, under any of the following conditions, the clearance
may be reduced:
(i) If the vehicle is in transit with its structure lowered, the
clearance may be reduced to 4 ft. If the voltage is higher than 50kV,
the clearance shall be increased 0.4 inch for every 1kV over that
voltage.
(ii) If insulating barriers are installed to prevent contact with
the lines, and if the barriers are rated for the voltage of the line
being guarded and are not a part of or an attachment to the vehicle
or its raised structure, the clearance may be reduced to a distance
within the designed working dimensions of the insulating barrier.
(b) If the equipment is an aerial lift insulated for the voltage involved,
and if the work is performed by a qualified person, the clearance (between
the uninsulated portion of the aerial lift and the power line) may be
reduced to the distance given in subsections (3) and (4) of this section.
(c) Employees standing on the ground shall not contact the vehicle
or mechanical equipment or any of its attachments, unless:
(i) The employee is using protective equipment rated for the voltage;
or
(ii) The equipment is located so that no uninsulated part of its
structure (that portion of the structure that provides a conductive
path to employees on the ground) can come closer to the line than
permitted in this section.
(d) If any vehicle or mechanical equipment capable of having parts
of its structure elevated near energized overhead lines is intentionally
grounded, employees working on the ground near the point of grounding
shall not stand at the grounding location whenever there is a possibility
of overhead line contact. Additional precautions, such as the use of
barricades or insulation, shall be taken to protect employees from hazardous
ground potentials, depending on earth resistivity and fault currents,
which can develop within the first few feet or more outward from the
grounding point.
(9) Illumination.
(a) Employees shall not enter spaces containing exposed energized parts,
unless illumination is provided that enables the employees to perform
the work safely.
(b) Where lack of illumination or an obstruction precludes observation
of the work to be performed, employees shall not perform tasks near
exposed energized parts. Employees shall not reach blindly into areas
which may contain energized parts.
(10) Confined or enclosed work spaces. When an employee works in a confined
or enclosed space (such as a manhole or vault) that contains exposed energized
parts, the employer shall provide, and the employee shall use, protective
shields, protective barriers, or insulating materials as necessary to
avoid inadvertent contact with these parts. Doors, hinged panels, and
the like shall be secured to prevent their swinging into an employee and
causing the employee to contact exposed energized parts.
(11) Conductive materials and equipment. Conductive materials and equipment
that are in contact with any part of an employee's body shall be handled
in a manner that will prevent them from contacting exposed energized conductors
or circuit parts. If an employee must handle long dimensional conductive
objects (such as ducts and pipes) in areas with exposed live parts, the
employer shall institute work practices (such as the use of insulation,
guarding, and material handling techniques) which will minimize the hazard.
(12) Portable ladders. Portable ladders shall have nonconductive siderails
if they are used where the employee or the ladder could contact exposed
energized parts.
(13) Conductive apparel. Conductive articles of jewelry and clothing
(such as watch bands, bracelets, rings, key chains, necklaces, metalized
aprons, cloth with conductive thread, or metal headgear) shall not be
worn if they might contact exposed energized parts.
(14) Housekeeping duties.
(a) Where live parts present an electrical contact hazard, employees
shall not perform housekeeping duties at such close distances to the
parts that there is a possibility of contact, unless adequate safeguards
(such as insulating equipment or barriers) are provided.
(b) Electrically conductive cleaning materials (including conductive
solids such as steel wool, metalized cloth, and silicon carbide, as
well as conductive liquid solutions) shall not be used in proximity
to energized parts unless procedures are followed which will prevent
electrical contact.
Interlocks. Only a qualified person following the requirements of this
section may defeat an electrical safety interlock, and then only temporarily
while he or she is working on the equipment. The interlock system shall
be returned to its operable condition when this work is completed.
[Statutory Authority: Chapter 49.17 RCW.
94-15-096 (Order 94-07), 296-24-960, filed 7/20/94, effective 9/20/94;
91-24-017 (Order 91-07), 296-24-960, filed 11/22/91, effective 12/24/91.
Statutory Authority: RCW 49.17.040 and 49.17.050. 82-13-045 (Order 82-22),
296-24-960, filed 6/11/82; 82-02-003 (Order 81-32), 296-24-960, filed
12/24/81.]
WAC 296-24-965 Safety-related
work practices.
(1) Scope. Covered work by both qualified and unqualified persons.
The provisions of WAC
296-24-960 through 296-24-985
cover electrical safety-related work practices for both qualified
persons (those who have training in avoiding the electrical hazards
of working on or near exposed energized parts) and unqualified
persons (those with little or no such training) working on, near,
or with the following installations:
(a) Premises wiring. Installations of electric conductors and equipment
within or on buildings or other structures, and on other premises such
as yards, carnival, parking, and other lots, and industrial substations;
(b) Wiring for connection to supply. Installations of conductors that
connect to the supply of electricity;
(c) Other wiring. Installations of other outside conductors on the
premises; and
(d) Optical fiber cable. Installations of optical fiber cable where
such installations are made along with electric conductors.
Note: See WAC
296-24-95601 for the definition of "qualified person." See
WAC
296-24-970 for training requirements that apply to qualified
and unqualified persons.
(2) Other covered work by unqualified persons. The provisions
of WAC
296-24-960 through 296-24-985
also cover work performed by unqualified persons on, near, or
with the installations listed in subsection (3) of this section.
(3) Excluded work by qualified persons. The provisions of WAC
296-24-960 through 296-24-985
do not apply to work performed by qualified persons on or directly
associated with the following installations:
(a) Generation, transmission, and distribution installations. Installations
for the generation, control, transformation, transmission, and distribution
of electric energy (including communication and metering) located in
buildings used for such purposes or located outdoors.
Note 1: Work on or directly associated with installations
of utilization equipment used for purposes other than generating, transmitting,
or distributing electric energy (such as installations which are in
office buildings, warehouses, garages, machine shops, or recreational
buildings, or other utilization installations which are not an integral
part of a generating installation, substation, or control center) is
covered under subsection (1)(a) of this section.
Note 2: Work on or directly associated with generation,
transmission, or distribution installations includes:
1. Work performed directly on such installations, such as repairing
overhead or underground distribution lines or repairing a feed-water
pump for the boiler in a generating plant.
2. Work directly associated with such installations, such as line-clearance
tree trimming and replacing utility poles.
3. Work on electric utilization circuits in a generating plant provided
that:
a. Such circuits are commingled with installations of power generation
equipment or circuits; and
b. The generation equipment or circuits present greater electrical
hazards than those posed by the utilization equipment or circuits
(such as exposure to higher voltages or lack of overcurrent protection).
(b) Communications installations. Installations of communication equipment
to the extent that the work is covered under chapter
296-32 WAC.
(c) Installations in vehicles. Installations in ships, watercraft,
railway rolling stock, aircraft, or automotive vehicles other than mobile
homes and recreational vehicles.
Railway installations. Installations of railways for generation, transformation,
transmission, or distribution of power used exclusively for operation
of rolling stock or installations of railways used exclusively for signaling
and communication purposes.
[Statutory Authority: Chapter 49.17 RCW.
91-24-017 (Order 91-07), 296-24-965, filed 11/22/91, effective 12/24/91.]
WAC 296-24-970 Training.
(1) Scope. The training requirements contained in this section
apply to employees who face a risk of electric shock that is not
reduced to a safe level by the electrical installation requirements
of WAC
296-24-95605 through 296-24-95615.
Note: Employees in occupations listed in Table S-4
face such a risk and are required to be trained. Other employees who also
may reasonably be expected to face a comparable risk of injury due to
electric shock or other electrical hazards must also be trained.
(2) Content of training.
(a) Practices addressed in this standard. Employees shall be
trained in and familiar with the safety-related work practices
required by WAC
296-24-960 through
296-24-985 that pertain to their respective job assignments.
(b) Additional requirements for unqualified persons. Employees
who are covered by subsection (1) of this section but who are
not qualified persons shall also be trained in and familiar
with any electrically related safety practices not specifically
addressed by WAC
296-24-960 through
296-24-985 but which are necessary for their safety.
(c) Additional requirements for qualified persons. Qualified persons
(i.e., those permitted to work on or near exposed energized parts) shall,
at a minimum, be trained in and familiar with the following:
(i) The skills and techniques necessary to distinguish exposed live
parts from other parts of electric equipment;
(ii) The skills and techniques necessary to determine the nominal
voltage of exposed live parts; and
(iii) The clearance distances specified in WAC
296-24-960 and the corresponding voltages to which the
qualified person will be exposed.
Note 1: For the purposes of WAC
296-24-960 through 296-24-985
a person must have the training required by (c) of this subsection
in order to be considered a qualified person.
Note 2: Qualified persons whose work on energized
equipment involves either direct contact or contact by means
of tools or materials must also have the training needed to
meet WAC
296-24-960.
(3) Type of training. The training required by this section shall be
of the classroom or on-the-job type. The degree of training provided shall
be determined by the risk to the employee.
TABLE S-4.--TYPICAL
OCCUPATIONAL CATEGORIES OF EMPLOYEES FACING A
HIGHER THAN
NORMAL RISK OF ELECTRICAL ACCIDENT
| Occupation |
| Blue collar supervisors.1 |
| Electrical and electronic engineers.1 |
| Electrical and electronic technicians.1 |
| Electricians. |
| Industrial machine operators.1 |
| Material handling equipment operators.1 |
| Mechanics and repairers. 1 |
| Painters. 1 |
| Riggers and roustabouts. 1 |
| Stationary engineers. 1 |
| Welders. |
1Workers in these groups do not need to be trained if their
work or the work of those they supervise does not bring them or the employees
they supervise close enough to exposed parts of electric circuits operating
at 50 volts or more to ground for a hazard to exist.
[Statutory Authority: Chapter 49.17 RCW.
91-24-017 (Order 91-07), 296-24-970, filed 11/22/91, effective 12/24/91.]
WAC 296-24-975 Selection
and use of work practices.
(1) General. Safety-related work practices shall be employed to prevent
electric shock or other injuries resulting from either direct or indirect
electrical contacts, when work is performed near or on equipment or circuits
which are or may be energized. The specific safety-related work practices
shall be consistent with the nature and extent of the associated electrical
hazards.
(a) Deenergized parts. Live parts to which an employee may be exposed
shall be deenergized before the employee works on or near them, unless
the employer can demonstrate that deenergizing introduces additional
or increased hazards or is infeasible due to equipment design or operational
limitations. Live parts that operate at less than 50 volts to ground
need not be deenergized if there will be no increased exposure to electrical
burns or to explosion due to electric arcs.
Note 1: Examples of increased or additional hazards
include interruption of life support equipment, deactivation of emergency
alarm systems, shutdown of hazardous location ventilation equipment,
or removal of illumination for an area.
Note 2: Examples of work that may be performed
on or near energized circuit parts because of infeasibility due to equipment
design or operational limitations include testing of electric circuits
that can only be performed with the circuit energized and work on circuits
that form an integral part of a continuous industrial process in a chemical
plant that would otherwise need to be completely shut down in order
to permit work on one circuit or piece of equipment.
Note 3: Work on or near deenergized parts is covered
by subsection (2) of this section.
(b) Energized parts. If the exposed live parts are not deenergized
(i.e., for reasons of increased or additional hazards or infeasibility),
other safety-related work practices shall be used to protect
employees who may be exposed to the electrical hazards involved.
Such work practices shall protect employees against contact
with energized circuit parts directly with any part of their
body or indirectly through some other conductive object. The
work practices that are used shall be suitable for the conditions
under which the work is to be performed and for the voltage
level of the exposed electric conductors or circuit parts. Specific
work practice requirements are detailed in WAC
296-24-960.
(2) Working on or near exposed deenergized parts.
(a) Application. This subsection applies to work on exposed deenergized
parts or near enough to them to expose the employee to any electrical
hazard they present. Conductors and parts of electric equipment
that have been deenergized but have not been locked out or tagged
according to this subsection shall be treated as energized parts,
and WAC
296-24-960 applies to work on or near them.
(b) Lockout and tagging. While any employee is exposed to contact with
parts of fixed electric equipment or circuits which have been deenergized,
the circuits energizing the parts shall be locked out or tagged or both
according to the requirements of this section. The requirements shall
be followed in the order in which they are presented (i.e., (b)(i) of
this subsection first, then (b)(ii) of this subsection.
Note 1: As used in this section, fixed equipment
refers to equipment fastened in place or connected by permanent wiring
methods.
Note 2: Lockout and tagging procedures
that comply with chapter
296-803 WAC Lockout/tagout (control of hazardous energy)
will also be deemed to comply with (b) of this subsection provided
that:
1. The procedures address the electrical safety hazards covered by
this part; and
2. The procedures also incorporate the requirements of (b)(iii)(D)
and (b)(iv)(B) of this subsection.
(i) Procedures. The employer shall maintain a written copy of the
procedures outlined in (b) of this subsection and shall make it available
for inspection by employees and by the director and his or her authorized
representatives.
Note: The written procedures may be in the form
of a copy of subsection (2) of this section.
(ii) Deenergizing equipment.
(A) Safe procedures for deenergizing circuits and equipment shall
be determined before circuits or equipment are deenergized.
(B) The circuits and equipment to be worked on shall be disconnected
from all electric energy sources. Control circuit devices, such
as push buttons, selector switches, and interlocks, shall not be
used as the sole means for deenergizing circuits or equipment. Interlocks
for electric equipment shall not be used as a substitute for lockout
and tagging procedures.
(C) Stored electric energy which might endanger personnel shall
be released. Capacitors shall be discharged and high capacitance
elements shall be short-circuited and grounded, if the stored electric
energy might endanger personnel.
Note: If the capacitors or associated equipment
are handled in meeting this requirement, they shall be treated as
energized.
(D) Stored nonelectrical energy in devices that could reenergize
electric circuit parts shall be blocked or relieved to the extent
that the circuit parts could not be accidentally energized by the
device.
(iii) Application of locks and tags.
(A) A lock and a tag shall be placed on each disconnecting means
used to deenergize circuits and equipment on which work is to be
performed, except as provided in subitems (C) and (E) of this item.
The lock shall be attached to prevent persons from operating the
disconnecting means unless they resort to undue force or the use
of tools.
(B) Each tag shall contain a statement prohibiting unauthorized
operation of the disconnecting means and removal of the tag.
(C) If a lock cannot be applied, or if the employer can demonstrate
that tagging procedures will provide a level of safety equivalent
to that obtained by the use of a lock, a tag may be used without
a lock.
(D) A tag used without a lock, as permitted by subitem (C) of this
item, shall be supplemented by at least one additional safety measure
that provides a level of safety equivalent to that obtained by the
use of a lock. Examples of additional safety measures include the
removal of an isolating circuit element, blocking of a controlling
switch, or opening of an extra disconnecting device.
(E) A lock may be placed without a tag only under the following
conditions:
(I) Only one circuit or piece of equipment is deenergized; and
(II) The lockout period does not extend beyond the work shift;
and
(III) Employees exposed to the hazards associated with reenergizing
the circuit or equipment are familiar with this procedure.
(iv) Verification of deenergized condition. The requirements of this
subsection shall be met before any circuits or equipment can be considered
and worked as deenergized.
(A) A qualified person shall operate the equipment operating controls
or otherwise verify that the equipment cannot be restarted.
(B) A qualified person shall use test equipment to test the circuit
elements and electrical parts of equipment to which employees will
be exposed and shall verify that the circuit elements and equipment
parts are deenergized. The test shall also determine if any energized
condition exists as a result of inadvertently induced voltage or
unrelated voltage backfeed even though specific parts of the circuit
have been deenergized and presumed to be safe. If the circuit to
be tested is over 600 volts, nominal, the test equipment shall be
checked for proper operation immediately before and immediately
after this test.
(v) Reenergizing equipment. These requirements shall be met, in the
order given, before circuits or equipment are reenergized, even temporarily.
(A) A qualified person shall conduct tests and visual inspections,
as necessary, to verify that all tools, electrical jumpers, shorts,
grounds, and other such devices have been removed, so that the circuits
and equipment can be safely energized.
(B) Employees exposed to the hazards associated with reenergizing
the circuit or equipment shall be warned to stay clear of circuits
and equipment.
(C) Each lock and tag shall be removed by the employee who applied
it or under his or her direct supervision. However, if this employee
is absent from the workplace, then the lock or tag may be removed
by a qualified person designated to perform this task provided that:
(I) The employer ensures that the employee who applied the lock
or tag is not available at the workplace; and
(II) The employer ensures that the employee is aware that the
lock or tag has been removed before he or she resumes work at
that workplace.
There shall be a visual determination that all employees are clear of
the circuits and equipment.
[Statutory Authority: Chapter 49.17 RCW.
94-15-096 (Order 94-07), 296-24-975, filed 7/20/94, effective 9/20/94;
91-24-017 (Order 91-07), 296-24-975, filed 11/22/91, effective 12/24/91.]
WAC 296-24-980 Safeguards
for personnel protection.
(1) Use of protective equipment.
(a) Personal protective equipment.
(i) Employees working in areas where there are potential electrical
hazards shall be provided with, and shall use, electrical protective
equipment that is appropriate for the specific parts of the body to
be protected and for the work to be performed.
Note: Personal protective equipment
requirements are contained in chapter
296-24 WAC Part L, and WAC
296-800-160.
(ii) Protective equipment shall be maintained in a safe,
reliable condition and shall be periodically inspected or
tested, as required by chapter
296-24 WAC Part L, and WAC
296-800-160.
(iii) If the insulating capability of protective equipment may be
subject to damage during use, the insulating material shall be protected.
(For example, an outer covering of leather is sometimes used for the
protection of rubber insulating material.)
(iv) Employees shall wear nonconductive head protection wherever
there is a danger of head injury from electric shock or burns due
to contact with exposed energized parts.
(v) Employees shall wear protective equipment for the eyes or face
wherever there is danger of injury to the eyes or face from electric
arcs or flashes or from flying objects resulting from electrical explosion.
(b) General protective equipment and tools.
(i) When working near exposed energized conductors or circuit parts,
each employee shall use insulated tools or handling equipment if the
tools or handling equipment might make contact with such conductors
or parts. If the insulating capability of insulated tools or handling
equipment is subject to damage, the insulating material shall be protected.
(A) Fuse handling equipment, insulated for the circuit voltage,
shall be used to remove or install fuses when the fuse terminals
are energized.
(B) Ropes and handlines used near exposed energized parts shall
be nonconductive.
(ii) Protective shields, protective barriers, or insulating materials
shall be used to protect each employee from shock, burns, or other
electrically related injuries while that employee is working near
exposed energized parts which might be accidentally contacted or where
dangerous electric heating or arcing might occur. When normally enclosed
live parts are exposed for maintenance or repair, they shall be guarded
to protect unqualified persons from contact with the live parts.
(2) Alerting techniques. The following |