Respirators
Chapter 296-842, WAC |
Effective
Date: 04/01/07 |
Contents
Helpful
Tools
Index
Download
Air
Quality for Self-Contained Breathing Apparatus (SCBA) and
Air-Line Respirators
|
For
printing |
| Make
sure breathing air and oxygen meet established specifications |
WAC 296-842-20005 |
Prevent conditions that
could create a hazardous breathing air supply |
WAC
296-842-20010 |
Make
sure compressors don’t create a hazardous breathing
air supply |
WAC
296-842-20015 |
WAC 296-842-20005
Make sure breathing air and oxygen meet
established specifications
(1) Make sure that all SCBAs and air-line
respirators are provided with safe breathing air and oxygen.
(2) Compressed breathing air must meet
the following specifications for Grade D air:
- (a) Oxygen (volume/volume) within 19.5-23.5%
- (b) Hydrocarbon (condensed): no more than 5 milligrams per
cubic meter of air
- (c) Carbon monoxide (CO): no more than 10
parts per million (ppm)
- (d) Carbon dioxide (CO2): no more than 1,000
ppm
- (e) No noticeable odor
| 
|
Reference:
See the American National Standards Institute
- Compressed Gas Association Commodity Specification for
Air (G-7.1.1989) for more information. Contact your local
library to access a copy. |
(3) Make sure the moisture content of
the air supplied meets the following:
(a) Air supplied to respirators from
cylinders must not exceed a dew point of -50°F (or -45.6°C)
at 1 atmospheric pressure.
(b) Compressor supplied air must not exceed a dew point
of 10°F (or 5.56°C) below the use temperature at 1
atmospheric pressure.
(4)
Cylinders of breathing air purchased or otherwise obtained from a supplier must have a certificate of analysis from the supplier verifying each cylinder's contents meet Grade D breathing air requirements and dew point standards.
(5) Compressed and liquid oxygen must
meet the United States Pharmacopoeia requirements for medical
or breathing oxygen.
WAC 296-842-20010
Prevent conditions that could create a hazardous
breathing air supply
(1) Use SCBA and air-line respirators safely:
– Do not
supply compressed oxygen to SCBAs or air-line respirators that
previously used compressed air.
| 
|
Note:
Compressed air leaves residues containing
hydrocarbons such as oil or grease. Fire or explosion can
occur if compressed oxygen makes contact with these residues. |
(2) Use breathing
air couplings on air-line respirators that are not
compatible with couplings for nonrespirable air or other gas
systems, for example, utility air used for manufacturing purposes.
(3) Do not allow asphyxiating substances to enter breathing air lines;
for example, don’t flush nitrogen through worksite air
lines also used for breathing air.
(4) Use equipment
specifically designed for oxygen service or distribution if oxygen concentrations greater than 23.5% are used.
| 
|
Note:
Respiratory equipment not
designed for oxygen service or distribution can create fire
or explosion hazards in oxygen concentrations higher than
23.5%. |
(5) Make sure cylinders used to supply
breathing air for SCBAs or air-line respirators are tested and
maintained as described in the federal Department of Transportation’s
(DOT) Shipping Container Specification Regulations, Title 49
CFR.
| 
|
Note:
• Use only cylinders marked (with
serial number, cylinder pressure, DOT exemption number,
and test dates) according to these DOT regulations
• To find any Code of Federal
Regulations (CFR) visit: www.access.gpo.gov.
|
: WAC 296-842-20015
Make sure compressors don’t create
a hazardous breathing air supply
Important:
• Ambient-air movers (or pumps) used to
supply air to respirators must be used according to the manufacturer’s
instructions.
• Respirators used with ambient-air movers must be approved
by NIOSH to operate within the pressure ranges of the air mover.
(1) Locate or modify
compressor intakes so they won’t pick up contaminated air
or exhaust gases such as carbon monoxide (CO) from:
• Fuel-powered vehicles
or
• The internal combustion motor of the compressor
or
• Other contaminant sources in the area, for example,
a ventilation system discharge.
| 
|
Note:
• You may need to reposition or extend the compressor’s
intake or engine exhaust pipe or outlet, especially if they
are located near each other.
• Be aware that exhaust gases may not adequately
disperse when the compressor is operated in:
– An enclosed space such as a
small room, a corner, or near a wall
or
– In turbulent wind conditions.
|
(2)
Equip compressors with suitable air-purifying filters, water traps,
and sorbents (such as charcoal beds) and maintain them as follows:
(a) Periodically change or clean them
according to the manufacturer or supplier’s instructions
(b) Keep a tag at the compressor with the following information:
– When the sorbent and filters were
last replaced or cleaned
– The date of the most recent changes
or cleaning
– The signature of the person authorized
by the employer to perform changes or cleaning.
| 
|
Note:
To be sure you are providing the recommended
operating pressure for respirators, you may need to install
a delivery pressure gauge where the respirator's airline hose attaches to the manifold or other air outlet. |
(3) Make sure the
carbon monoxide (CO) level in breathing air from compressors does
not exceed 10 parts per million (ppm). Maintain CO levels below 10 ppm
in oil lubricated compressors by using at least one of the following:
(a) An effective
CO alarm
(b) An effective
high temperature alarm and testing the air
supply often enough to prevent CO levels from exceeding 10 ppm.
| 
|
Note:
- If you do not have a reliable CO-free area available for locating your compressor intake, consider these examples of methods to prevent CO contamination of the air supply:
- - Use of continuous and effective carbon monoxide alarms and filters
- - Conduct frequent monitoring of air quality
- - Use a CO converter (converts CO to carbon dioxide).
• How often to test depends on a
number of considerations, for example:
– Compressor age
– Maintenance history of the compressor
– Stability of CO readings
• If the CO or high temperature alarm
can’t be heard by the employee, a flashing light or
other effective alternative to an audio alarm needs to be
used
• Safeguards,
such as alarms, are necessary to prevent CO contamination
resulting from compressor overheating.
When alarms are provided, proper maintenance practices such as periodic inspections and calibration will help make sure alarms remain effective
• Any type
of oil-lubricated compressor, such as screw or piston types,
may produce dangerous levels of CO if overheating occurs
– Old compressors are known to
leak oil due to worn parts, increasing the possibility
for overheating. Newer compressors may also overheat if
maintenance practices are poor. For example, poor maintenance
practices may lead to disconnected or incorrectly set
alarms, inoperative shut-offs, or an impaired cooling
system
– You need to instruct employees
to move to a safe area when the alarm sounds and
to stop using respirators.
|
|