Scaffolds
Chapter 296-874, WAC |
Effective
Date: 10/06/07 |
Contents
Helpful
Tools
Index
Download

Your Responsibility
To make sure all scaffolds meet these requirement
You must

General Requirements for Scaffolds
WAC 296-874-20002
Make sure scaffolds are properly designed
and constructed
You must
- Make sure scaffolds are:
- – Designed by a qualified person
and
- – Constructed according to that
design.
- Prohibit the use of shore and lean-to
scaffolds.
| 
|
Definition:
- A qualified person
is one who has demonstrated the ability to solve problems
related to the subject matter, work, or project. This
can be done by having either:
- – A recognized degree, certificate,
or professional standing
or
- – Extensive knowledge, training,
and experience.
|
WAC
296-874-20004
Make sure scaffolds are erected, moved,
altered, or dismantled by appropriate persons
You must
- Make sure scaffolds are erected, moved, altered,
or dismantled only when the work is:
- – Supervised and directed by a competent
person qualified in scaffold erections, moving, dismantling
or alteration
and
- – Done by experienced and trained
employees selected by the competent person.
| 
|
Definition:
- A competent person
is someone who:
- – Is capable of identifying
existing and predictable hazards in the surroundings
or working conditions which are unsanitary, hazardous,
or dangerous to employees
and
- – Has the authority to take
prompt corrective measures to eliminate them.
|
WAC
296-874-20006
Maintain structural integrity when
intermixing scaffold components
You must
- Make sure intermixed scaffold components:
- – Fit together without force
and
- – Maintain the scaffold’s structural
integrity.
- Make sure a qualified person determines that
modifying components in order to intermix them will result in
a structurally sound scaffold.
- Make sure scaffold components made of different
metals aren't used together.
 |
Exemption:
- Different types of metals may be used
together if a competent person determines that galvanic
action won't reduce the strength of any component to less
than the minimum strength required.
|
| 
|
Reference:
- The minimum strength requirements are
found in the following sections:
|
WAC
296-874-20008
Make sure platforms are properly planked
or decked
You must
- Fully plank or deck each platform between
the front uprights and the guardrail supports on all working
levels of a scaffold so that there's no more than one inch (2.5
cm):
- – Between adjacent units
and
- – Between the platform and the uprights.
 |
Exemption:
- There may be more than one inch between
platform units if all of the following are met:
- – You can demonstrate that
a wider space is necessary, such as to fit around
uprights when side brackets are used to extend the
platform width
- – The platform is planked
or decked as fully as possible
- – The open space between the
platform and the guardrail supports is 9-1/2 inches
(24.1 cm) or less.
- Platforms used solely as walkways or
only by employees erecting or dismantling scaffolds, don't
have to be fully decked or planked if:
- – The planking provided makes
for safe working conditions
and
- – Employees on those platforms
are protected from falling.
|
| 
|
Reference:
Fall protection requirements for employees
|
Are located in the following chapters
|
In the following sections
|
On walkways within
scaffolds
|
Chapter 296-874, WAC Scaffolds |
WAC
296-874-20056 |
| Erecting or dismantling
supported scaffolds |
Chapter 296-874, WAC
Scaffolds |
WAC 296-874-40010 |
Erecting or dismantling
suspended scaffolds in
general industry
|
Chapter
296-24, WAC General Safety and Health Standards |
Part
J-1, Working Surfaces, Guarding Floors and Wall
Openings, Ladders
and
Part
J-3, Powered Platforms |
| Erecting or dismantling
suspended scaffolds in
construction work |
Chapter
296-155, WAC Safety Standards for Construction Work |
Part
C-1, Fall Restraint and Fall Arrest
and
Part
K, Floor Openings, Wall Openings, and Stairways |
|
You must
- Make sure wood platforms aren't covered with
an opaque finish.
 |
Exemption:
- Platform edges may be covered or marked
for identification.
|
| 
|
Note:
- Platforms may be coated periodically
with wood preservatives, fire-retardant finishes, or slip-resistant
finishes if the coating doesn't obscure the top or bottom
wood surfaces.
|
WAC
296-874-20010
Make sure platforms meet minimum width requirements
You must
- Make sure scaffold platforms meet the minimum
width requirements of Table 1, Minimum Platform Width.
Table 1
Minimum Platform Width
| Type of scaffold |
Minimum platform
width required |
- Ladder jack scaffold
- Pump jack scaffold
- Roof bracket scaffold
- Top plate bracket scaffold
|
12 inches (20 cm) |
| |
No minimum width |
| |
18 inches (46 cm)
Exemption:
- Platforms and walkways may be less
than 18 inches (46 cm) wide if all of
the following are met:
- – You can demonstrate that
the area is so narrow that the platform or walkway
can't be at least 18 inches (46 cm) wide
- – The platform or walkway
is as wide as feasible
- – Employees on those platforms
or walkways are protected from falling by using guardrails
or personal fall arrest systems
|
WAC
296-874-20012
Meet these requirements when using shorter
platforms to create a longer platform
You must
- Make sure, when platforms are overlapped
to create a longer platform, that:
- – The overlap is over a support
and
- – The platforms are either:
- Overlapped by at least 12 inches (30
cm)
or
- Are nailed together or otherwise prevented
from moving.
- Make sure, when platforms are butted together
to create a longer platform, that each abutted platform end
rests on a separate support surface.
| 
|
Note:
- Platforms may butt together on a common
support member if the member is designed to support abutting
platforms, such as either:
- - A "T" section
or
- - Hook-on platforms designed to rest
on common supports.
|
WAC
296-874-20014
Lay platform planks properly when the platform
changes direction
You must
- Do the following whenever platforms
overlap to change direction:
- – First lay the platform that rests
on a bearer at an angle other than a right angle
then
- – Lay the platform that's perpendicular
to the bearer.
WAC
296-874-20016
Stabilize the ends of platforms
You must
- Make sure each end of a platform:
- – Is cleated or restrained by hooks
or equivalent means
or
- – Extends over the centerline of
its support at least 6 inches (15 cm).
- Make sure the cantilevered portion of a platform
meets at least one of the following:
- – Is designed and installed to support
employees or material without tipping
- – Has guardrails which block employee
access to the cantilevered end
- – Extends over its support not more
than:
- 12 inches (30 cm) if the platform
length is 10 feet or less
or
- 18 inches (46 cm) if the platform
length is greater than 10 feet.
| 
|
Note:
The cantilevered portion of a platform
is the portion that isn't supported on one end. |
WAC
296-874-20018
Keep platform sag within acceptable limits
You must
- Make sure a
loaded platform doesn't sag more than 1/60 of the span.
WAC
296-874-20020
Provide safe access to scaffolds
You must
- Provide scaffold platforms more than 2 feet
(0.6 m) above or below a point of access with at least one of
the following means of access:
- – Portable, hook-on, or attachable
ladder
- – Stairway-type ladder
- – Ladder stand
- – Stair tower (scaffold stairway
or tower)
- – Ramp
- – Walkway
- – Integral prefabricated scaffold
access
- – Direct access from another scaffold,
structure, personnel hoist, or similar surface.
- Make sure crossbraces aren't used as a means
of access.
| 
|
Reference:
For requirements about integral prefabricated
scaffold access, go to WAC
296-874-40020. |
WAC
296-874-20022
Make sure portable, hook-on, and attachable
ladders meet these requirements
You must
- Position portable, hook-on, and attachable
ladders so they don't tip the scaffold.
- Make sure hook-on and attachable ladders
meet all of the following:
- – Specifically designed and used
for that type of scaffold
- – Have rungs that are:
- Uniformly spaced
- Not more than 16-3/4 inches apart
- At least 11-1/2 inches (29 cm) long
- Lined up vertically between rest
platforms.
- Position the bottom rung not more
than 24 inches (61 cm) above the scaffold supporting
level.
- Have rest platforms at vertical
intervals not greater than 24 feet (7.3m) on supported
scaffolds.
WAC
296-874-20024
Make sure stairway-type ladders meet these
requirements
You must
- Make sure stairway-type ladders meet all of
the following:
- – Position the bottom step not more
than 24 inches (61 cm) above the scaffold supporting level
- – Have rest platforms not more than
12 feet (3.7 m) apart vertically
- – Have slip-resistant surfaces on
treads and landings
- – Have steps that:
- Are at least 16 inches (41 cm) wide
and
- Line-up vertically between rest
platforms.
- Make sure mobile ladder stands have steps
that are at least 11-1/2 inches (30 cm) wide.
| 
|
Definition:
A ladder stand is a mobile, fixed-size,
self-supporting ladder consisting of a wide flat tread ladder
in the form of stairs. |
WAC
296-874-20026
Make sure stair towers meet these requirements
You must
- Make sure stair towers (scaffold stairways
or towers) meet all of the following:
- – Are positioned so the bottom step
isn't more than 24 inches (61 cm) above the scaffold supporting
level
- – Are at least 18 inches (45.7 cm)
wide between stair rails
- – Have slip-resistant surfaces on
treads and landings
- – Are installed at an angle of 40
to 60 degrees from the horizontal.
- Provide a landing platform at least 18 inches
(45.7 cm) wide by 18 inches (45.7 cm) long at each level.
- Provide guardrails on the open sides and
ends of each landing.
| 
|
Reference:
For requirements about guardrails, go
to WAC 296-874-20064. |
You must
- Make sure steps meet all of the following
requirements:
- – Line-up vertically between rest
platforms
- – Have uniform tread depth, within
1/4 inch (0.6 cm), for each flight of stairs
- – Have uniform riser height, within
1/4 inch (0.6 cm), for each flight of stairs.
| 
|
Note:
- Riser height may have larger variations
at the top step and bottom step of the entire stair system,
but not at the top and bottom steps within each flight
of stairs.
|
WAC
296-874-20028
Make sure stair rails and handrails meet
these requirements
You must
- Provide a stair rail that meets all
of the following on each side of a scaffold stairway:
- – Has a toprail and midrail
- – Has a toprail that can serve as
a handrail if a separate handrail isn't provided
- – Is at least 28 inches (71 cm)
but not more than 37 inches (94 cm) high.
You must
- Make sure stair rail systems and handrails
have:
- - A surface that prevents employees from:
- Being injured by punctures or lacerations
or
- Snagging their clothing.
- - Ends that don't create a projection
hazard.
- Make sure handrails, and top rails that are
used as handrails:
- – Provide an adequate handhold for
employees to grasp to avoid falling
and
- – Are at least 3 inches (7.6 cm)
from other objects.
WAC
296-874-20030
Make sure ramps and walkways used to access
scaffolds meet these requirements
You must
- Make sure ramps and walkways aren't inclined
at a slope steeper than one vertical in 3 horizontal (1:3 or
20 degrees from the horizontal).
- Make sure ramps and walkways that are inclined
at a slope steeper than one vertical in 8 horizontal (1:8) have
cleats to provide footing which are:
- – Securely fastened to the planks
and
- – Spaced not more than 14 inches
(35 cm) apart.
| 
|
Reference:
Ramps and walkways that are 4 feet (1.2
m) or more above a lower level need to have a guardrail
system. Those requirements are found in other chapters.
- - For general industry activities,
go to:
- - For construction activities, go
to:
|
WAC
296-874-20032
Make sure surfaces used to access scaffolds
are close enough to use safely
You must
- Make sure a surface used to provide access
to or from a scaffold isn't further from the scaffold than:
- – 14 inches (36 cm) horizontally
- – 24 inches (61 cm) vertically.
WAC
296-874-20034
Inspect scaffolds and scaffold components
You must
- Make sure scaffolds and scaffold components
are inspected for visible defects by a competent person:
- – Before each work shift
and
- – After anything occurs that could
affect the scaffold’s structural integrity.
WAC
296-874-20036
Make sure damaged or weakened scaffolds
meet minimum strength requirements
You must
- Make sure any scaffold or scaffold component
that’s been damaged or weakened so that it no longer meets
the minimum strength requirements of this chapter, is immediately
either:
- – Repaired, replaced, or braced to meet the minimum strength requriements;
or
- – Removed from service until repaired.
| 
|
Reference:
For information on minimum strength requirements
for suspended and supported scaffolds, go to the following
sections within this chapter:
- – Make sure suspended scaffolds
and suspended components meet these strength requirements,
WAC
296-874-30002
- – Make sure supported scaffolds
and supported components meet these strength requirements,
WAC 296-874-40002.
|
WAC
296-874-20038
Make sure scaffolds are properly loaded
You must
- Load scaffolds as specified in the:
- – Manufacturer’s instructions
or
- – Design of the qualified person.
- Make sure scaffolds and scaffold components
don't exceed their maximum intended load or rated load, whichever
is less.
WAC
296-874-20040
Protect employees when moving scaffolds
You must
- Make sure scaffolds aren't moved horizontally
while employees are on them.
 |
Exemption:
- A scaffold may be moved horizontally
with employees on it if the scaffold:
- – Has been specifically designed
for such movement by a registered professional engineer
or
- – Is a mobile scaffold that
meets the requirements of the section, Meet these
requirements when moving mobile scaffolds, WAC 296-874-40012.
|
WAC
296-874-20042
Increase employee working level height on
scaffolds safely
You must
- Make sure makeshift devices, such as boxes
and barrels, aren't used on scaffold platforms to increase the
working level height for employees.
- Meet all of the following when using
stilts on scaffolds:
- – Use stilts only on large area
scaffolds
- – Increase the height of a guardrail
system used for fall protection by an amount equal to the
height of the stilts being used
- – Make sure
scaffold platforms where stilts are used are flat and free
of:
- Pits, holes, and obstructions such
as debris
and
- Other tripping or falling hazards.
- – Make sure stilts are:
- Properly maintained
and
- The original equipment isn't altered
without the manufacturer’s approval
- Meet all of the following when using ladders
on scaffolds:
- – Use ladders only on large area
scaffolds
- – Secure the platform units to the
scaffold to prevent movement
- – Secure the scaffold against the
sideways thrust exerted by the ladder if the ladder is placed
against a structure that’s not part of the scaffold
- – Make sure the ladder legs are:
- Secured to prevent them from slipping
or being pushed off the platform
and
- On the same scaffold platform, or
use other means, to stabilize the ladder against uneven
platform deflection.
WAC
296-874-20044
Control loads being hoisted near scaffolds
You must
- Use a tag line or equivalent measures to
control loads being hoisted onto or near a scaffold if the load
could swing and contact the scaffold.
WAC
296-874-20046
Protect employees from energized power lines
You must
- Make sure scaffolds are erected, moved, altered,
or dismantled so that they, and any conductive material handled
on them, are kept at least as far from exposed and energized
power lines as shown in Table 2, Minimum Separation Distance
from Energized Power Lines.
Table 2
Minimum Separation Distance from Energized Power Lines
| Voltage |
Minimum
Separation Distance |
| Less than 300 volts (insulated lines) |
3 feet (0.9 m) |
| Less than 300 volts (uninsulated lines) |
10 feet (3.1 m) |
| 300 volts to 50 kv |
10 feet (3.1 m) |
| More than 50 kv |
10 feet (3.1 m) + 0.4 inches (1.0
cm)
for each 1 kv over 50 kv
Note:
You may use alternative minimum separation distance of 2
times the length of the line insulator, but never less than
10 feet (3.1 m). |
 |
Exemption
- Scaffolds and conductive materials handled
on scaffolds may be closer to power lines than the minimum
separation distance specified in Table 2 if all
of the following are met:
- – Less clearance is necessary
to do the work
- – The utility company or electrical
system operator has been notified of the need to work
closer to the power lines
- – The utility company or electrical
system operator has done at least one of the following:
- De-energized the lines
- Relocated the lines to meet
the minimum separation distance requirement
- Installed protective coverings
over the lines to prevent accidental contact
|
WAC
296-874-20048
Protect employees from weather hazards
You must
- Prohibit work on or from scaffolds during
storms or high winds unless both of the following are met:
- Make sure wind screens aren't used unless
the scaffold is secured against the anticipated wind forces.
WAC
296-874-20050
Protect employees from slipping and tripping
hazards
You must
- Make sure debris doesn't accumulate on platforms.
- Prohibit employees from working on scaffolds
covered with snow, ice, or other slippery material.
 |
Exemption:
- Employees may be on scaffolds as necessary
to remove the slipping hazard.
|
WAC
296-874-20052
Provide fall protection for employees on
scaffolds
You must
- Protect each employee on a scaffold more than
10 ft. (3.1 m) above a lower level, from falling to the lower
level, by providing either:
- – A personal fall arrest system
or
- – Guardrails.
- Make sure employees erecting the scaffold
install the guardrail system, if required, before the scaffold
is used by any other employees.
| 
|
Reference:
|
WAC
296-874-20054
Provide fall protection if a scaffold is
too far from the work face
You must
- Provide a guardrail system along the front
edge of the platform, or have employees use a personal fall
arrest system, if the distance from the front edge of the platform
to the work face is greater than:
- – 18 inches (46 cm) for scaffolds
used for plastering and lathing operations.
- – 14 inches (36 cm) for all other
scaffolds
WAC
296-874-20056
Provide specific fall protection for specific
types of scaffolds
You must
- Use a personal fall arrest system to protect
employees on the following scaffolds:
- – Boatswain's chair
- – Catenary scaffold
- – Float scaffold
- – Ladder jack scaffold
- – Needle beam scaffold.
- Use a personal fall arrest system and
a guardrail system to protect employees on:
- – Single-point adjustable suspension
scaffolds
and
- – Two-point adjustable suspension
scaffolds.
- Protect employees working on a self-contained
adjustable scaffold that has the platform:
- – Supported by the frame structure,
using a guardrail system with a minimum 200 lb. toprail
capacity.
- – Suspended by ropes, using:
- A guard rail system with a minimum
200 lb. toprail capacity
and
- A personal fall arrest system.
- Protect employees on walkways located within
a scaffold by using a guardrail system that meets all of the
following:
- – Has a minimum 200 lb. toprail
capacity
- – Is installed within 9-1/2 inches
(24.1 cm) of the walkway
- – Is installed along at least one
side of the walkway.
WAC
296-874-20058
Make sure personal fall arrest systems meet
these requirements
You must
- Make sure personal fall arrest systems used
on scaffolds for general industry activities, meet the requirements
of Personal Fall Arrest System, Appendix C, Part 1, WAC
296-24-88050, in Powered Platforms, Part
J-3, found in General Safety and Health Standards,
Chapter 296-24,
WAC.
- Make sure personal fall arrest systems are
attached by a lanyard to one of the following:
- – Vertical lifeline
- – Horizontal lifeline
- – Appropriate structural member of
the scaffold
| 
|
Reference:
Requirements for personal fall arrest
systems used on scaffolds for construction activities are
in Fall Restraint and Fall Arrest, Part
C-1, found in Safety Standards for Construction Work,
Chapter
296-155, WAC. |
WAC
296-874-20060
Make sure vertical lifelines used with personal
fall arrest systems meet these requirements
You must
- Make sure vertical lifelines are all of the
following:
- – Fastened to a fixed, safe point
of anchorage
- – Independent of the scaffold
- – Protected from sharp edges and
abrasion.
| 
|
Note:
- Safe points of anchorage include structural
members of buildings, but do not include:
- - Standpipes, vents, or other piping
systems
- - Electrical conduit
- - Outrigger beams
- - Counterweights
|
You must
- Make sure vertical lifelines, independent
support lines, and suspension ropes are not
attached to any of the following:
- – Each other
- – The same point of anchorage
- – The same point on the scaffold.
- Make sure vertical lifelines, independent
support lines, and suspension ropes don't use the same point
of anchorage.
- Make sure independent support lines and suspension
ropes aren't attached to a personal fall arrest system.
- Make sure vertical lifelines aren't used
with single-point or two-point adjustable suspension scaffolds
that have overhead components such as overhead protection or
additional platform levels.
WAC
296-874-20062
Make sure horizontal lifelines used with
personal fall arrest systems meet these requirements
You must
- Equip single-point or two-point adjustable
suspension scaffolds that use horizontal lifelines or structural
members of the scaffold for fall protection with both of the
following:
- – Additional independent support lines
that are equal in number and equivalent in strength to the
suspension ropes
- – Automatic locking devices capable
of stopping the scaffold from falling if one or both of the
suspension ropes fail.
- Make sure horizontal lifelines are secured
to either:
- – Two or more structural members of
the scaffold
or
- – Looped around both the suspension
ropes and independent support lines above the hoist and brake
attached to the end of the scaffold.
- Make sure independent support lines and suspension
ropes are not
- – Attached to each other or the
same point on the scaffold
- – Attached to or use the same point
of anchorage.
- Make sure independent support lines and suspension
ropes aren't attached to either:
- – A personal fall arrest system
or
- – The same point on the scaffold as
a personal fall arrest system.
- Make sure, if a horizontal lifeline is used
where it may become a vertical lifeline, that the device used
to connect a lanyard to the horizontal lifeline is capable of
locking in both directions on the lifeline.
WAC
296-874-20064
Make sure guardrail systems meet these requirements
You must
 |
Exemption:
- For employees doing overhand bricklaying
operations from a supported scaffold, a guardrail isn't
required on the side next to the wall.
|
| 
|
Definition:
Overhand bricklaying
is the process of laying bricks and masonry units so that
the surface of the wall is on the opposite side of the
wall from the mason, requiring the mason to lean over
the wall to complete the work. It includes mason tending
and electrical installation incorporated into the brick
wall.
|
You must
- Make sure the height of the toprail top edge,
or the equivalent member, of supported scaffolds is:
- – At least 36 inches (0.9 m) and
not more than 45 inches
(1.2 m) above the platform surface for scaffolds manufactured
or first placed in service before January 1, 2000
- – At least 38 inches (0.97 m) and
not more than 45 inches
(1.2 m) above the platform surface for scaffolds manufactured
or first placed in service after January 1, 2000.
- Make sure the height of the toprail top edge,
or the equivalent member, of suspended scaffolds that require
guardrails and personal fall arrest systems, is at least 36
inches (0.9 m) and not more than 45 inches (1.2 m) above the
platform surface.
WAC
296-874-20064
 |
Exemption:
- When conditions warrant, the height
of the top edge of the toprail may be greater than 45
inches if the guardrail system meets all other criteria
of this chapter.
|
You must
- Make sure the top edge of the toprail doesn’t
drop below the required height when the minimum load, shown
in Table 3, Minimum Toprail and Midrail Strength Requirements,
is used.
- Each toprail and midrail,
or equivalent member, of a guardrail system must be able to
withstand, without failure, the force shown in Table 3, Minimum
Toprail and Midrail Strength Requirements, when the force is
applied as follows:
- – To the toprail in a downward or
horizontal direction at any point along its top edge
- – To the midrail in a downward or
horizontal direction at any point.
| 
|
Note:
Midrail includes screens, mesh, intermediate
vertical members, solid panels, and equivalent structural
members of the guardrail system. |
|
Table 3
Minimum Toprail and Midrail Strength Requirements |
Type
of Scaffold |
Toprail
Capacity |
Midrail Capacity |
- Single-point adjustable suspension
scaffolds
- Two-point adjustable suspension scaffolds
|
100 lbs. (445 n) |
75 lbs. (333 n) |
- All other scaffoldsWalkways within a
scaffold
|
200
lbs. (890 n) |
150 lbs. (666 n) |
You must
- Install midrails, screens, mesh, intermediate
vertical members, solid panels, or equivalent structural members
as follows:
- – Midrails at a height approximately
midway between the top edge of the guardrail system and the
platform surface
- – Screens and mesh:
- From the top edge of the guardrail
system to the scaffold platform
and
- Along the entire opening between the
supports
- – Intermediate members, such as balusters
or additional rails, not more than 19 inches (48 cm) apart.
- Make sure steel or plastic banding isn't used
as a toprail or midrail.
WAC
296-874-20064
You must
- Have a competent person inspect manila rope
and plastic or other synthetic rope that's used as a toprail
or midrail as frequently as necessary to make sure it continues
to meet the strength requirements for a toprail or midrail.
|

|
Note:
Crossbraces may be used as a toprail or
midrail in a guardrail system if they meet the following
requirements:
- - The crossing point of the 2 braces
is between:
- 20 inches and 30 inches above
the work platform when used as a midrail
- 38 inches and 48 inches above
the work platform when used as a toprail
- - The end points at each upright aren't
more than 48 inches apart.
|
You must
- Make sure guardrails have a surface that
prevents:
- – Puncture and laceration injuries
and
- – Snagging clothing.
- Make sure any rail extending beyond the post
of a guardrail doesn't create a projection hazard.
WAC
296-874-20066
Provide falling object protection
You must
- Protect employees from being struck by tools,
materials, or equipment falling from a scaffold by doing one
or more of the following
:
- – Use a barricade to keep employees
out of the area where falling objects could be a hazard
- – Install a toeboard along the edge
of the platform anywhere an object could fall on an employee
below
- – Install paneling or screening that
covers from the top of the guardrail to the toeboard or platform
anywhere the toeboard is not high enough
to keep objects from falling off the platform
- – Install a guardrail system with
openings small enough to keep potential falling objects from
passing through
- – Erect a canopy structure, debris
net, or catch platform over employees that does all of the
following:
- Will contain or deflect falling objects
- Is strong enough to withstand the impact
forces
- Is installed between the falling object
hazard and the employees.
- Make sure potential falling objects that are
too large or heavy to be contained or deflected by the falling
object protection you're using, are:
- – Moved away from the edge of the
surface they could fall from
and
- – Secured, as necessary, to prevent
falling
| 
|
Reference:
Hardhats and possibly other personal protective
equipment has to be used to protect employees exposed to
overhead hazards.
– Those requirements are found
in the Safety and Health Core Rules, Chapter
296-800 WAC. Go to the section titled Personal Protective
Equipment (PPE), WAC
296-800-160.
|
WAC
296-874-20068
Pr |